Learn how Siemens SIPROTEC 5 7VU85 HSBT works, including motor-bus transfer principles, transfer algorithms, DIGSI 5 configuration, Omicron RelaySimTest and Digital Twin testing.
Introduction to High-Speed Busbar Transfer (HSBT)
In many industrial plants and power generation facilities, the continuous availability of electrical power is essential for safe and reliable operation. Critical motors, pumps, compressors, fans, and other auxiliary equipment depend on a stable electrical supply. Even a short interruption can cause process disturbances, equipment shutdowns, production losses, and significant financial consequences.
This is particularly important in installations where large induction motors are connected to medium-voltage busbars. When the normal power source is interrupted, these motors do not stop immediately. Instead, they continue rotating and generate a decaying residual voltage on the motor bus.
The magnitude, frequency, and phase angle of this residual voltage change over time. Consequently, reconnecting the motor bus to an alternative power source requires careful consideration of the electrical and mechanical conditions at the moment of switching.
This is where a High-Speed Busbar Transfer (HSBT) system becomes essential. The Siemens SIPROTEC 5 7VU85 is a dedicated high-speed busbar transfer device designed to transfer motor-bus loads between power sources while minimizing the interruption to critical industrial and power plant processes.
SIPROTEC 5 7VU85
The SIPROTEC 5 7VU85 is a multifunctional protection and automation device specifically designed for High-Speed Busbar Transfer applications.
Its primary purpose is to supervise the normal incoming supply, motor busbar voltage, and alternative incoming supply. When the normal supply becomes unavailable or a transfer condition is detected, the device initiates an appropriate switching sequence to disconnect the faulty or unavailable source and connect the motor bus to an alternative healthy source.
The objective is to restore the electrical supply as quickly and safely as the system conditions permit.
The 7VU85 is based on the flexible SIPROTEC 5 platform and supports different busbar arrangements, including:
- Single busbar with multiple incomers.
- Sectionalized single busbar.
- Double busbar arrangements.
- Configurations with multiple alternative power sources.
Depending on the selected application and device configuration, the system can accommodate complex arrangements involving up to 20 circuit breakers.
Main objectives of the 7VU85
The main objectives of a high-speed busbar transfer system include:
- Minimizing interruption time for critical motor loads.
- Reducing process disturbances following the loss of a power source.
- Avoiding unnecessary motor shutdowns.
- Maintaining production continuity.
- Reducing the risk of unsuccessful or unsafe asynchronous switching.
- Providing flexible transfer sequences for different electrical network configurations.
Applications
High-speed busbar transfer is particularly useful in facilities where electrical continuity is essential and motor loads represent a significant portion of the total demand.
Thermal power plants
Thermal power plants use large auxiliary motors for essential processes, including:
- Forced Draft (FD) fans.
- Induced Draft (ID) fans.
- Boiler Feed Water pumps.
- Cooling Water pumps.
- Coal handling and auxiliary drives.
If a generating unit trips, its auxiliary electrical supply may also be affected. A fast transfer to an alternative station source can help restore the supply to critical auxiliaries and reduce the time required to return the generating unit to service.
High-inertia fan loads can have a significant influence on motor-bus residual-voltage characteristics.
Petrochemical and chemical industries
Petrochemical facilities often contain large compressor trains, pumps, agitators, and other continuously operating motor loads.
An interruption in electrical supply can disturb the process, cause equipment trips, and lead to costly production losses.
A suitable bus transfer arrangement can help maintain process continuity by transferring the motor bus to an independent healthy supply.
Oil and gas facilities
Oil and gas installations use electrically driven compressors, pumps, cooling systems, and other critical equipment.
The availability of alternative electrical sources and a properly engineered bus transfer system can improve the reliability of these installations.
Continuous process industries
Other applications include:
- Pharmaceutical manufacturing.
- Pulp and paper plants.
- Cement production.
- Steel manufacturing.
- Water treatment facilities.
- Semiconductor manufacturing.
The suitability of an HSBT system depends on the electrical network arrangement, motor characteristics, process requirements, and available alternative power sources.
Motor-Bus Residual Voltage
When an induction motor is disconnected from its electrical source, its rotor continues rotating because of its mechanical inertia.
The rotating magnetic field and residual magnetism produce a voltage at the motor terminals. When several induction motors are connected to the same busbar, their combined behavior contributes to the residual voltage measured at the motor bus.
This voltage does not disappear immediately.
Instead, the motor-bus voltage gradually changes in:
- Magnitude.
- Frequency.
- Phase angle relative to the alternative source.
The rate of decay depends on several factors, including:
- Motor type and rating.
- Total connected motor load.
- Motor inertia.
- Mechanical loading.
- Electrical characteristics of the motors.
- Capacitor banks connected to the busbar.
- Network and transformer characteristics.
If the alternative source is connected while the residual motor-bus voltage has a significant phase-angle difference from the incoming source, the resulting electrical transient can produce high currents and mechanical torque disturbances.
Therefore, the bus transfer system must evaluate the conditions at the expected moment of circuit-breaker contact closure, rather than considering only the conditions when the closing command is issued.
This is one of the most important principles of HSBT engineering.
Main Operating Principles of SIPROTEC 7VU85
The 7VU85 continuously supervises the relevant electrical quantities and switching conditions required for the configured transfer application. The transfer process generally involves the following stages:
- Monitoring the normal incoming supply and motor-bus conditions.
- Detecting a transfer-start condition.
- Evaluating whether the transfer is permitted or blocked.
- Selecting the applicable transfer direction and sequence.
- Opening the normal incoming circuit breaker when required.
- Evaluating the motor-bus residual voltage and its relationship with the alternative source.
- Selecting an appropriate transfer algorithm.
- Issuing the closing command to the alternative incoming circuit breaker.
- Supervising the resulting switching operation and recording the transfer event.
The exact sequence depends on the application configuration, transfer direction, transfer sequence, and selected operating conditions.
Transfer-start conditions
A transfer can be initiated through different criteria, depending on the application design. Typical start conditions include:
- Electrical fault start.
- Non-electrical fault start.
- Circuit-breaker inadvertent opening.
- Undervoltage start.
- Underfrequency start.
- Manual transfer start.
- Additional user-defined start criteria.
For example, in a generating station, a unit-trip signal may initiate the transfer.
In some industrial installations, the transfer device must independently detect the loss of the incoming supply using electrical measurements such as undervoltage, underfrequency, or rate of change of frequency (df/dt).
The selection and coordination of these start criteria are important parts of the engineering design.
Blocking conditions
A transfer should not take place under every operating condition.
The system must evaluate whether the transfer is safe and permitted.
Depending on the application, blocking conditions can include:
- Motor-bus or busbar fault conditions.
- Unhealthy alternative power source.
- Voltage transformer circuit supervision problems.
- Circuit-breaker status inconsistencies.
- Circuit-breaker test or withdrawn position.
- Manual switching conditions.
- Device or application errors.
- Other project-specific interlocking conditions.
Correctly engineering and testing the blocking logic is just as important as verifying the transfer-start conditions.
Transfer Sequences
Different electrical network arrangements require different switching sequences.
The SIPROTEC 7VU85 supports configurable transfer sequences, including:
Simultaneous transfer
In a simultaneous transfer, the required switching operations for the transfer direction are initiated as part of a coordinated transfer sequence.
This approach is useful when the application requires the motor-bus sections to be transferred together.
Sequential transfer
In a sequential transfer, the switching operations are carried out in a defined order.
This can be useful where different bus sections or loads must be transferred one after another, according to the plant’s electrical and operational requirements.
Parallel transfer
Parallel transfer involves connecting the alternative source while the normal source is still connected, subject to the required synchronization and safety conditions.
Because this can result in the temporary paralleling of two power sources, synchronization, circuit-breaker interlocking, and network operating requirements must be carefully considered.
The selected transfer sequence must match the actual single-line diagram and the operating philosophy of the installation.
Understanding the SIPROTEC 7VU85 Transfer Algorithms
One of the most important features of the 7VU85 is its ability to select different transfer methods according to the electrical conditions of the motor bus.
The available transfer modes include:
FAST Transfer
FAST transfer is intended to reconnect the motor bus to the alternative source as quickly as possible, while the residual voltage and phase relationship remain within the configured permissible limits.
It is generally the preferred transfer strategy when the electrical conditions allow a safe fast transfer.
The objective is to minimize the interruption and reduce the electrical and mechanical stresses associated with reconnecting the motor loads.
REAL-TIME FAST Transfer
The SIPROTEC 7VU85 also incorporates an improved Real-Time Fast Transfer algorithm.
This algorithm is designed to achieve very fast switching by evaluating the relevant motor-bus and source conditions in real time.
Siemens specifies switching times of up to 10 ms for the improved 7VU85 algorithm, with approximately 1 ms closing times achievable using high-speed binary output contacts.
Actual performance depends on the complete application, measurement configuration, output circuit, circuit-breaker characteristics, and system conditions.
IN-PHASE Transfer
If the conditions required for a fast transfer are no longer satisfied, an in-phase transfer can be considered.
The device evaluates the changing phase-angle relationship between the decaying motor-bus voltage and the alternative source.
The closing command is issued in advance, considering the expected circuit-breaker closing time, so that the electrical contacts close when the two voltage systems are close to the required phase relationship.
This is particularly important because the phase angle can continue changing during the mechanical closing operation of the circuit breaker.
RESIDUAL-VOLTAGE Transfer
If the fast and in-phase transfer conditions cannot be achieved, residual-voltage transfer can be used when the application permits it.
The device waits until the motor-bus residual voltage decreases below the configured threshold before connecting the alternative source.
This method generally results in a longer interruption.
It is important to consider the high restarting currents that can occur when several motors are re-energized together.
The motor thermal limits, protection settings, transformer capacity, and process requirements must be checked during engineering.
LONG-TIME Transfer
Long-time transfer is another transfer strategy available in the 7VU85.
It is intended for situations in which the faster transfer opportunities are no longer available and the application allows a longer interruption before restoring the supply.
The exact operating criteria and sequence must be taken from the applicable device manual and project configuration.
Important: The transfer algorithms are not interchangeable. Their application depends on the motor-bus characteristics, source conditions, circuit-breaker operating time, configured settings, and the actual operating philosophy.
Practical Applications
The best transfer strategy cannot be selected simply by looking at the nominal voltage or the total motor load.
Different motor combinations can produce very different residual-voltage characteristics.
Thermal power plant example
In one documented thermal power plant application involving a 210 MW generating unit, the motor-bus spin-down characteristics were investigated following the tripping of a lightly loaded unit board.
The observations included:
- Approximately 240 ms for the bus voltage to fall to 80% of its rated value.
- Approximately 146 ms for the phase difference to exceed 20 degrees relative to the normal source.
- Less than one cycle of dead-bus time during the demonstrated simultaneous fast transfer.
The high-inertia motor loads contributed to a relatively gradual change in the motor-bus voltage and phase relationship.
This created a suitable operating window for fast transfer.
Continuous process industry example
A different example involved a continuously operating PVC resin manufacturing plant.
The installation included:
- Two incoming 220 kV lines from independent substations.
- Approximately 10.7 MW of motor load.
- An 8 MVAR capacitor bank.
- A mixture of compressor, pump, fan, agitator, and other motor loads.
The capacitor bank supported the bus voltage during motor coast-down. However, the low-inertia loads resulted in a relatively rapid frequency decay.
The bus completed an entire slip cycle relative to the alternate source within approximately 21 cycles.
In this application, both fast transfer and in-phase transfer were demonstrated.
The transfer system also needed to detect the incoming supply contingency independently. The instantaneous df/dt criterion was selected in the described trial, with detection taking approximately 3–4 cycles.
The demonstrated fast transfer had approximately seven cycles of total dead-bus time, while the in-phase transfer involved approximately 21 cycles.
These examples demonstrate why engineers must study the actual motor-bus behavior before deciding on transfer settings and operating strategies.
The numerical values are specific to the described installations and should not be treated as universal 7VU85 settings or guaranteed performance values.
SIPROTEC 7VU85 Configuration in DIGSI 5
The SIPROTEC 7VU85 is engineered using DIGSI 5, the configuration and engineering software for the SIPROTEC 5 platform.
The configuration process involves more than assigning binary inputs and outputs. Engineers must translate the actual electrical network and operating philosophy into a correctly configured HSBT application.
Important engineering activities include:
Define the electrical network
Start with the plant single-line diagram. Identify:
- Normal incoming sources.
- Alternative incoming sources.
- Motor-bus sections.
- Bus couplers and section breakers.
- Circuit-breaker operating arrangements.
- Voltage and current measurement points.
- Required transfer directions.
Configure the HSBT function
Configure the relevant HSBT function group and application according to the selected network arrangement.
The transfer direction defines which circuit breakers must open and close during a particular transfer operation.
Configure transfer priorities
When several alternative sources are available, transfer priorities help define the preferred order of the alternative supplies.
This is particularly important for complex busbar configurations.
Configure start and blocking logic
Define the signals that initiate a transfer and the conditions that prevent it.
The logic must be coordinated with the protection system, circuit-breaker control, interlocking, and process requirements.
Configure circuit-breaker signals
Verify the complete circuit-breaker signal chain, including:
- Open commands.
- Close commands.
- Breaker auxiliary contacts.
- Open and closed status indications.
- Breaker availability.
- Breaker operating times.
- Circuit-breaker failure or unsuccessful operation conditions.
Verify measurement assignments
Ensure that the voltage and current measurements are correctly assigned to the relevant sources and motor-bus sections.
Incorrect measurement assignment or polarity can lead to incorrect transfer decisions.
The complete configuration should be checked against the actual project design and the relevant Siemens 7VU85 manual.

Testing and Commissioning of SIPROTEC 7VU85
Testing an HSBT system requires more than checking whether the device can issue an open or close command.
The transfer algorithms depend on changing voltage, frequency, phase angle, and circuit-breaker operating time.
Therefore, a comprehensive testing strategy should include both static logic verification and dynamic simulation.
Static testing using DIGSI 5
Static testing is useful for checking:
- HSBT readiness.
- Start conditions.
- Blocking conditions.
- Transfer-direction selection.
- Transfer sequence logic.
- Circuit-breaker open and close commands.
- Binary input and output assignments.
- Status feedback and interlocking.
However, static tests alone cannot reproduce the complete behavior of a motor bus during coast-down.
Dynamic simulation using Omicron RelaySimTest
Omicron RelaySimTest can be used to simulate the dynamic electrical behavior of the motor-bus system.
A suitable simulation model can include:
- Two independent incoming sources.
- Motor-bus sections.
- Bus-tie circuit breaker.
- Motor loads.
- Voltage and current measurement points.
- Circuit-breaker status signals.
- Opening and closing commands.
By changing motor loading, source conditions, and circuit-breaker operating times, engineers can investigate the response of the HSBT system under different operating scenarios.
Important test cases include:
- Normal fast transfer.
- In-phase transfer.
- Residual-voltage transfer.
- Unexpected incoming circuit-breaker opening.
- Electrical fault on an incoming source.
- Different motor loading conditions.
- Loss of the alternative source.
- Transfer blocking conditions.
- Failure of a circuit breaker to operate.
Dynamic simulation is particularly useful for evaluating the interaction between residual-voltage decay, phase-angle evolution, and the predicted breaker closing instant.
Physical testing
Physical testing verifies the actual interface between the test equipment, relay, and external circuits.
It should include checks of:
- Secondary voltage and current injection.
- Binary input signals.
- Binary output contacts.
- Circuit-breaker command circuits.
- Auxiliary contact feedback.
- Output timing.
- Signal mapping and wiring.
- Communication and synchronization between test equipment, where applicable.
Physical testing remains essential for confirming the actual installation and its interfaces.
Digital Twin testing
Digital Twin technology provides another approach to application verification.
A virtual representation of the SIPROTEC 5 device can be used with a simulation environment to evaluate the configured application before commissioning the physical equipment.
In the demonstrated workflow, the configured application is exported from DIGSI 5 and connected to the simulation environment through the appropriate interface.
RelaySimTest supplies simulated electrical and binary signals, while the virtual IED executes the configured logic and returns its responses.
This allows engineers to test the interaction between the simulated network, the HSBT logic, and the switching sequence.
Digital Twin testing can help identify configuration and application problems before site commissioning.
It does not replace all physical commissioning activities, including wiring verification, secondary injection, actual circuit-breaker timing measurements, and end-to-end checks.
HSBT Testing Checklist
| Test category | What should be verified |
|---|---|
| Readiness | HSBT ready and available conditions |
| Transfer start | Electrical, non-electrical and manual starts |
| Unexpected opening | Inadvertent incomer breaker opening |
| Undervoltage | Correct start and blocking response |
| Underfrequency | Correct detection and logic response |
| df/dt | Contingency detection, where configured |
| Fast transfer | Permissible voltage and phase conditions |
| Real-Time Fast | Dynamic transfer behavior |
| In-phase transfer | Predicted closing instant |
| Residual-voltage transfer | Configured voltage threshold |
| Long-time transfer | Long-time operating conditions |
| Blocking | Bus fault, source unavailability and other configured blocks |
| Circuit breaker | Open/close commands and auxiliary feedback |
| Transfer sequence | Simultaneous, sequential or parallel operation |
| Load variation | Different motor loading and coast-down behavior |
| Digital Twin | Application logic and simulated signal exchange |
The actual acceptance criteria must be based on the approved project settings, manufacturer documentation, and applicable engineering requirements.
The Siemens SIPROTEC 5 7VU85 is a dedicated solution for high-speed busbar transfer applications where continuity of electrical supply to critical motor loads is essential.
Its application requires a clear understanding of motor-bus residual voltage, frequency decay, phase-angle behavior, circuit-breaker operating time, and the operating philosophy of the electrical installation.
By combining the appropriate transfer algorithms with correctly engineered start conditions, blocking logic, transfer sequences, and comprehensive testing, engineers can develop reliable bus transfer applications for power plants and continuous process industries.
The key to successful HSBT engineering is not simply transferring the bus as quickly as possible. It is transferring the motor bus at the right moment, under the right electrical conditions, and with a fully verified switching sequence.
For technical credibility, link to the original Siemens documentation:
- Siemens – SIPROTEC 7VU85 official product page
- Siemens – SIPROTEC 7VU85 V9.50 manual
- Siemens – High-Speed Busbar Transfer expert tutorial
Enroll our SIPROTEC 7VU Training now
Learn SIPROTEC 5 7VU85 HSBT with Practical Engineering Training

Understanding the 7VU85 requires more than reading a device manual or reviewing individual parameter descriptions. Engineers need to understand the relationship between:
- Electrical network configuration.
- Motor-bus residual voltage.
- Transfer-start conditions.
- Internal HSBT logic.
- Transfer sequences.
- Transfer algorithms.
- Circuit-breaker operating times.
- Testing and commissioning procedures.
A structured practical training program can help protection and commissioning engineers understand the complete application, from the basic operating principle to the verification of the configured system.