ABB REB650 Busbar Protection Relay – Complete Technical Guide

Table Of Contents
  1. 1. Introduction to ABB REB650
  2. 2. Applications of ABB REB650
  3. 3. Principle of Busbar Differential Protection
  4. 4. High-Impedance Differential Protection in REB650
  5. 5. HZPDIF – High-Impedance Differential Protection Function
  6. 6. Check-Zone Protection
  7. 7. Busbar Protection Configurations
  8. 8. CT Requirements for High-Impedance Busbar Protection
  9. 9. High-Impedance Differential Stability Calculation
  10. 10. Supporting Protection Functions in REB650
  11. 11. Busbar Protection Trip Logic
  12. 12. PCM600 Engineering for ABB REB650
  13. 13. IEC 61850 Communication in REB650
  14. 14. Testing and Commissioning of ABB REB650
  15. 15. Common REB650 Problems and Troubleshooting
  16. 16. ABB REB650 Compared with REB670
  17. 17. Practical REB650 Engineering and Commissioning Checklist
  18. 18. ABB REB650 Training by Elec-Engg
  19. 19. Frequently Asked Questions About ABB REB650
  20. 20. Conclusion

1. Introduction to ABB REB650

The ABB REB650 Busbar Protection Relay is a numerical protection and control IED belonging to the ABB Relion 650 series. It is designed to provide busbar protection for high-voltage and extra-high-voltage substations.

Busbar protection is one of the most important protection systems in a substation. A fault on a busbar can involve a large number of connected circuits and may result in severe equipment damage, extensive outages and significant system instability.

The REB650 is designed around high-impedance differential protection technology. It can protect busbar arrangements using dedicated differential protection zones and can include a check-zone arrangement to improve security.

The relay also provides supporting protection functions, including:

  • High-impedance differential protection
  • Phase overcurrent protection
  • Residual overcurrent protection
  • Negative-sequence overcurrent protection
  • Breaker failure protection
  • Pole discordance protection
  • Undervoltage protection
  • Overvoltage protection
  • Residual overvoltage protection
  • Circuit-breaker control and supervision, depending on configuration

The REB650 is particularly relevant for engineers involved in substation protection design, relay configuration, testing and commissioning.

Important distinction: REB650 and REB670 are not identical busbar protection solutions. The REB650 applications described in its product documentation use high-impedance differential protection (HZPDIF). REB670 is a different busbar protection platform with a low-impedance differential protection architecture. Their engineering and CT circuit requirements should not be mixed.

ABB REB650 Busbar Protection Relay – Complete Technical Guide

2. Applications of ABB REB650

The REB650 can be applied to different busbar configurations depending on the selected hardware, protection configuration and project requirements.

2.1 Single busbar protection

A single busbar arrangement is one of the simplest substation configurations.

All incoming and outgoing feeders are connected to one common busbar.

A busbar fault requires the isolation of all circuits connected to the affected busbar.

The REB650 can provide a dedicated high-impedance differential protection scheme for this arrangement.

2.2 Double busbar protection

A double busbar arrangement normally includes:

  • Busbar 1
  • Busbar 2
  • Bus coupler or bus-section circuit breaker
  • Incoming feeders
  • Outgoing feeders
  • Bus selector disconnectors

Each busbar section requires an appropriate protection zone.

The relay application must identify which feeders are connected to each busbar and assign their CT currents to the correct differential zone.

A typical arrangement includes:

  • Zone 1 – Busbar 1 protection
  • Zone 2 – Busbar 2 protection
  • Check zone – Supervision covering the relevant busbar arrangement

The actual number of zones and the implementation depend on the selected REB650 configuration.

2.3 Double busbar with transfer bus

Some substations use a transfer bus arrangement to allow maintenance and switching flexibility.

The protection design must account for the transfer bus operating condition and the changing electrical connections.

The busbar protection scheme must correctly identify the active protection zone during normal and transfer operations.

2.4 Busbar protection in industrial substations

The REB650 can also be considered for industrial substations where busbar faults must be cleared rapidly to protect transformers, feeders, motors and other connected equipment.

The application must be checked against the switchgear arrangement, CT characteristics, short-circuit level and required protection philosophy.

3. Principle of Busbar Differential Protection

Busbar differential protection is based on Kirchhoff’s current law.

Under normal operating conditions, the vector sum of all currents entering and leaving a protected busbar zone is approximately zero.

For a simplified busbar with three connected feeders:

I1 + I2 + I3 = 0

The differential current is:

Idiff = |I1 + I2 + I3|

Under normal operating conditions:

Idiff ≈ 0

During an external fault, the current entering the busbar zone and the current leaving it should still balance, assuming correct CT polarity, ratio and circuit connections.

During an internal busbar fault, the current balance is disturbed.

The differential current increases and the protection system identifies the fault as being inside the protected zone.

A busbar differential protection system must therefore provide two essential characteristics:

  1. Dependability for internal busbar faults.
  2. Stability for external faults and normal operating conditions.

The REB650 uses high-impedance differential protection to achieve this through a carefully engineered CT secondary circuit and a high-impedance measuring arrangement.

4. High-Impedance Differential Protection in REB650

The main busbar differential protection function in REB650 is HZPDIF.

High-impedance differential protection is a well-established technique for busbar protection, particularly where the connected CTs have suitable characteristics and can be engineered into a common differential circuit.

4.1 How high-impedance differential protection works

In a high-impedance differential scheme, the CT secondary circuits associated with the protected zone are connected in parallel with correct polarity.

The differential relay is connected across the common differential circuit.

During normal load and external faults, the CT secondary currents should balance.

Under an internal busbar fault, the CT currents no longer balance, creating a differential current that produces an operating voltage across the high-impedance circuit.

The relay operates when the voltage or corresponding operating quantity exceeds its configured threshold.

4.2 Why high impedance is used

The high-impedance arrangement is designed to maintain stability during severe external faults, including conditions where one CT may saturate.

If a CT saturates during an external fault, its secondary current may no longer reproduce the primary current accurately.

This can create an apparent differential current.

The high-impedance scheme uses a stabilizing arrangement so that the voltage developed during an external fault remains below the relay operating level, provided the CT and circuit design satisfy the required stability conditions.

4.3 Stabilizing resistor

A stabilizing resistor is an important part of a conventional high-impedance differential scheme.

Its purpose is to raise the effective impedance of the differential circuit and help maintain stability during external faults.

The resistor value is determined through engineering calculations.

Important inputs include:

  • CT secondary resistance
  • CT excitation characteristics
  • Maximum external through-fault current
  • CT ratio
  • Secondary cable resistance
  • Relay operating voltage
  • Required stability margin

The stabilizing resistor must not be selected arbitrarily.

4.4 Non-linear voltage-limiting resistor

A non-linear resistor, commonly known as a Metrosil-type voltage-limiting resistor, may be used in high-impedance differential schemes.

Its purpose is to limit excessive voltage that may develop across the differential circuit during internal faults.

This is important because the voltage developed in a high-impedance circuit can be significant during severe internal faults.

The correct selection must consider the operating voltage, energy duty and manufacturer recommendations.

4.5 High-impedance versus low-impedance differential protection

CharacteristicHigh-impedance differentialLow-impedance differential
Measuring principleHigh-impedance voltage-based arrangementNumerical current differential calculation
CT secondary arrangementCommon differential circuitIndividual CT inputs
CT requirementsStrict CT matching and suitabilityMore flexible CT application, subject to design
Stabilizing resistorTypically required in conventional schemesNot used as the same differential stabilizing principle
CT saturation stabilityAchieved through high-impedance circuit design and CT performanceAchieved through numerical stabilization algorithms
Zone selectionApplication-specific CT circuit and zone arrangementNumerical busbar replica and zone selection
Typical ABB exampleREB650REB670

It is essential to understand this distinction when working with ABB busbar protection systems.

5. HZPDIF – High-Impedance Differential Protection Function

HZPDIF is the principal differential protection function used in the REB650 busbar protection application.

It is associated with ANSI device number 87.

The function is applied to the differential protection zones and phases required by the selected configuration.

The REB650 application documentation describes multiple HZPDIF instances for implementing busbar zones and, where configured, a check zone.

5.1 Differential protection zones

For a double busbar application, separate HZPDIF instances can be used for the individual busbar zones.

For example:

  • Zone 1 – Busbar 1
  • Zone 2 – Busbar 2
  • Zone 3 – Check zone

The exact instance allocation and phase arrangement must be verified in the relevant product version and application configuration.

5.2 Phase-wise protection

Three-phase busbar protection normally requires differential protection for each phase.

The engineering must verify:

  • CT phase identification
  • CT polarity
  • CT ratio
  • CT secondary circuit continuity
  • Differential circuit connections
  • Relay input allocation

An incorrect CT connection can cause unwanted operation or loss of sensitivity.

5.3 Differential operating level

The differential operating level must be selected based on the protection study and the actual CT circuit.

The setting must provide adequate sensitivity for internal busbar faults while maintaining stability during external faults.

The engineer must consider the complete CT circuit rather than treating the relay setting as an independent parameter.

6. Check-Zone Protection

A check zone is an additional differential supervision zone used to improve the security of a busbar protection scheme.

In a double busbar arrangement, the individual busbar zones are associated with the actual busbar connections.

A check zone can cover the wider busbar arrangement and provide independent supervision of the differential trip decision.

The check zone helps protect against incorrect zone selection or certain CT switching and disconnector status errors.

6.1 Why is a check zone important?

Consider a double busbar substation with several feeders and a bus coupler.

If a feeder is incorrectly assigned to a busbar zone because of an erroneous disconnector indication, the individual zone may receive an incorrect current contribution.

A check-zone arrangement can provide an additional criterion before the overall busbar trip is permitted.

6.2 Check-zone logic

The exact logic depends on the application design.

A simplified conceptual arrangement is:

  1. The individual busbar zone detects a differential condition.
  2. The check zone independently evaluates the overall busbar differential condition.
  3. The protection logic combines the required operating conditions.
  4. The appropriate circuit breakers are tripped.

The actual REB650 application logic and wiring must be verified in the product-specific application manual.

A check zone should not be treated as a substitute for correct CT wiring, correct protection-zone design or proper commissioning.

7. Busbar Protection Configurations

ABB provides configured REB650 application solutions.

The documented REB650 configurations include different arrangements for busbar protection.

7.1 A03 configuration

The A03 application is designed for a double busbar arrangement with two busbar protection zones and the possibility of a check zone.

Its application can include:

  • Two busbar sections
  • Feeder current inputs
  • Bus coupler current inputs
  • Individual busbar differential zones
  • Check-zone differential protection
  • Supporting protection functions
  • Trip logic

The exact hardware and input/output requirements must be checked against the ordered configuration.

7.2 Other application arrangements

The suitability of the REB650 for a particular busbar arrangement depends on the configured application and the available hardware.

Before selecting the relay, engineers should confirm:

  • Number of busbar sections
  • Number of connected bays
  • Number of CT circuits
  • Required differential zones
  • Check-zone requirements
  • CT secondary circuit design
  • Required binary inputs and outputs
  • Circuit-breaker trip requirements

The configured application should be selected based on the actual single-line diagram rather than assuming that every REB650 has the same I/O arrangement.

8. CT Requirements for High-Impedance Busbar Protection

Current transformers are critical components in high-impedance differential protection.

A high-impedance scheme requires CTs that are suitable for the expected through-fault conditions and the required stability voltage.

8.1 CT ratio

All CTs associated with a differential zone must be selected and connected in accordance with the scheme design.

The primary and secondary ratios must be considered during the engineering calculations.

8.2 CT class

The CT class and excitation characteristics must be suitable for the high-impedance protection application.

The engineer should not select CTs based only on their nominal accuracy class.

The knee-point voltage, winding resistance and excitation characteristics are particularly important.

8.3 CT knee-point voltage

The CT knee-point voltage is a key parameter in high-impedance differential protection.

The CT must be capable of developing the required secondary voltage without excessive saturation under the specified external fault conditions.

The required knee-point voltage is calculated based on the stabilizing voltage, CT resistance, cable resistance and the applicable design margin.

The exact calculation method must follow the relevant ABB application manual and the applicable CT standards.

8.4 CT secondary resistance

The CT secondary winding resistance contributes to the total resistance of the differential circuit.

A higher resistance can increase the voltage developed during an external fault.

The engineer must use the correct CT resistance data, normally corrected to the applicable operating temperature where required.

8.5 CT cable resistance

The resistance of the secondary cables between the CTs and the relay panel must be included.

For a two-wire secondary circuit, the total loop resistance must be calculated using the actual conductor length and cross-sectional area.

Cable resistance is particularly important for remote bays and large substations.

8.6 CT polarity

Incorrect CT polarity can create an artificial differential current.

Polarity verification should be completed before the relay is placed into service.

The complete current circuit should be checked against the approved drawings and the high-impedance differential scheme design.

9. High-Impedance Differential Stability Calculation

A high-impedance differential protection scheme requires a detailed stability calculation.

The objective is to ensure that the protection does not operate during the maximum specified external fault current.

The calculation normally considers:

  • Maximum external fault current
  • CT ratio
  • CT secondary resistance
  • CT excitation voltage
  • Secondary cable resistance
  • Relay operating voltage
  • Stabilizing resistor
  • Non-linear resistor characteristics

A simplified conceptual expression for the stability voltage is:

Vstab ≈ Ifault,sec × (Rct + Rlead + Rrelay-path)

Where:

  • Ifault,sec is the secondary current associated with the external fault
  • Rct is the relevant CT secondary winding resistance
  • Rlead is the applicable secondary cable loop resistance
  • Rrelay-path represents the relevant circuit resistance

This expression is only a conceptual illustration. Actual high-impedance protection calculations must use the specific CT circuit topology and ABB’s prescribed calculation method.

The engineer must also consider the minimum internal fault current required for dependable operation.

A satisfactory design must demonstrate both stability and sensitivity.

10. Supporting Protection Functions in REB650

In addition to high-impedance differential protection, REB650 includes supporting protection functions depending on the ordered configuration.

10.1 Four-step phase overcurrent – OC4PTOC

OC4PTOC provides four-step phase overcurrent protection.

It can be used as backup protection for busbar-connected equipment or as part of the configured protection scheme.

The available stages can be configured with different pickup levels and operating delays.

10.2 Four-step residual overcurrent – EF4PTOC

EF4PTOC provides residual or earth-fault overcurrent protection.

It can be applied to detect earth faults in the connected network.

Its settings must be coordinated with the system grounding arrangement and other earth-fault protection devices.

10.3 Negative-sequence overcurrent – DNSPTOC

DNSPTOC provides negative-sequence-based overcurrent protection.

Negative-sequence current can indicate unbalanced system conditions, including phase faults and certain abnormal operating conditions.

The function can provide additional protection and supervision depending on the application.

10.4 Breaker failure protection – CCRBRF

CCRBRF is the circuit-breaker failure protection function associated with ANSI 50BF.

It supervises whether a circuit breaker successfully interrupts the current after receiving a trip command.

If the breaker fails to clear the fault within the configured conditions, the breaker failure logic initiates the required backup tripping.

Typical settings include:

  • Breaker failure initiation
  • Current supervision
  • Retrip logic
  • Breaker failure timer
  • Backup trip matrix
  • Reset conditions

For busbar protection, breaker failure operation must be coordinated with the connected bay and busbar protection philosophy.

10.5 Pole discordance – CCRPLD

CCRPLD supervises disagreement between circuit-breaker pole positions.

It can identify situations where one or more breaker poles remain in a different state from the others.

This function is important in applications involving independent pole operation.

10.6 Two-step undervoltage – UV2PTUV

UV2PTUV provides two-step undervoltage protection.

It can be used for busbar voltage supervision and other configured application requirements.

10.7 Two-step overvoltage – OV2PTOV

OV2PTOV provides two-step overvoltage protection.

It can be applied to detect abnormal busbar voltage conditions.

10.8 Residual overvoltage – ROV2PTOV

ROV2PTOV provides residual overvoltage protection.

It can be used for earth-fault detection and network supervision, depending on the voltage transformer arrangement and grounding method.

10.9 Other protection and control functions

The complete REB650 function inventory depends on product version, ordering information and configuration.

Engineers should refer to the relevant product guide rather than assuming that every function is enabled in every delivered relay.

11. Busbar Protection Trip Logic

The trip logic is a critical part of the busbar protection scheme.

When an internal busbar fault is detected, the protection system must disconnect all circuit breakers connected to the affected zone.

For a double busbar arrangement, the tripping strategy must distinguish between the two busbar sections.

A typical conceptual sequence is:

  1. The differential protection detects an internal fault.
  2. The corresponding zone protection issues an operating signal.
  3. The required check-zone supervision is evaluated, where configured.
  4. The trip logic identifies the affected busbar zone.
  5. All relevant circuit breakers are tripped.
  6. The protection system records the event and fault information.

The exact logic must follow the approved protection philosophy.

11.1 Busbar trip matrix

A trip matrix defines which breakers must open for each protection zone.

For example:

Protection zoneTypical breakers to trip
Busbar 1All circuit breakers connected to Busbar 1
Busbar 2All circuit breakers connected to Busbar 2
Check zoneDepends on the approved scheme and trip philosophy

The final matrix must account for the bus coupler, bus selector disconnectors, transfer bus arrangements and all relevant switching conditions.

11.2 Bus coupler considerations

The bus coupler is an important part of double busbar protection.

Its CT contribution and breaker status must be correctly considered in the differential zone design.

The engineer must verify the behavior of the protection scheme during:

  • Bus coupler closed
  • Bus coupler open
  • Busbar transfer
  • Busbar maintenance
  • Disconnector switching

12. PCM600 Engineering for ABB REB650

ABB PCM600 is used for engineering and configuration of compatible Relion 650 series IEDs.

The software supports the configuration of protection functions, application logic, signal connections and communication parameters.

12.1 Creating a PCM600 project

The engineer creates a new project and adds the REB650 IED.

The correct product version and configuration must be selected.

12.2 Parameter setting

Important engineering parameters include:

  • CT ratios
  • Differential protection settings
  • Operating voltage
  • Stabilizing circuit data
  • Supporting overcurrent settings
  • Breaker failure settings
  • Voltage protection settings
  • Binary input and output assignments
  • Communication parameters

The exact available settings depend on the selected HZPDIF function instance and product configuration.

12.3 Application configuration

The application configuration defines how the protection functions and logic blocks interact.

Typical tasks include:

  • Connecting differential protection outputs
  • Configuring zone trip signals
  • Connecting check-zone supervision
  • Assigning breaker trip signals
  • Configuring breaker failure initiation
  • Mapping alarms and indications
  • Configuring control logic

12.4 Signal matrix configuration

The signal matrix is used to connect internal IED signals to physical inputs and outputs and supported communication interfaces.

Engineers should verify each signal path against the approved logic diagrams and wiring drawings.

12.5 Hardware configuration

The actual installed hardware must match the engineered configuration.

Check:

  • Current input modules
  • Voltage input modules
  • Binary input modules
  • Binary output modules
  • Auxiliary supply
  • Communication modules

The number of required I/O points must be calculated for the complete application.

12.6 Configuration download and verification

Before downloading a new configuration:

  • Save the existing configuration.
  • Confirm the correct IED identity.
  • Verify the project version.
  • Review all modified settings.
  • Confirm the approved change procedure.
  • Check the final configuration after download.

Never modify an in-service busbar protection relay without appropriate authorization and an approved outage or protection-management procedure.

13. IEC 61850 Communication in REB650

The REB650 can be integrated into IEC 61850-based substation automation systems, depending on the product version and ordered communication configuration.

IEC 61850 enables standardized data exchange between protection IEDs, bay controllers and station-level systems.

13.1 Logical nodes

IEC 61850 uses logical nodes to represent protection, measurement, control and supervision functions.

Examples of logical node classes relevant to a busbar protection application include:

  • PDIF – Differential protection
  • PTOC – Overcurrent protection
  • PTUV – Undervoltage protection
  • PTOV – Overvoltage protection
  • PTRC – Protection trip conditioning
  • XCBR – Circuit breaker
  • MMXU – Measurement
  • GGIO – Generic input/output

The actual logical nodes and data objects depend on the REB650 product version and implemented functions.

13.2 MMS communication

MMS communication is commonly used for supervisory communication between the REB650 and the station control system.

Typical information includes:

  • Protection alarms
  • Relay status
  • Measurements
  • Events
  • Circuit-breaker indications
  • Disturbance information
  • Control information

13.3 GOOSE communication

GOOSE provides fast peer-to-peer communication between IEC 61850 IEDs.

Depending on the application, GOOSE may be used for:

  • Interlocking signals
  • Breaker failure intertripping
  • Protection blocking
  • Transfer trip signals
  • Bay-to-bay communication
  • Protection and control status exchange

The use of GOOSE must follow the approved system architecture and application design.

13.4 SCL engineering

Substation Configuration Language is used to describe IEC 61850 system configurations.

Common file types include:

  • ICD – IED Capability Description
  • CID – Configured IED Description
  • SCD – Substation Configuration Description
  • IID – Instantiated IED Description

The correct SCL file and revision must be maintained throughout the engineering and commissioning process.

13.5 Communication testing

Communication testing should include:

  • MMS connectivity
  • GOOSE publishing
  • GOOSE subscription
  • Dataset verification
  • Communication supervision
  • Time synchronization
  • SCADA signal mapping
  • Alarm and event verification

Tools such as IEDScout and Wireshark can assist engineers in IEC 61850 troubleshooting.

14. Testing and Commissioning of ABB REB650

Testing and commissioning of busbar protection require particular care because an incorrect trip can disconnect a large part of the substation.

Commissioning should cover the complete protection scheme, not only the relay itself.

14.1 Visual inspection

Check:

  • Relay model and ordering code
  • Hardware configuration
  • Auxiliary supply
  • CT terminal connections
  • Differential circuit wiring
  • Stabilizing resistor
  • Non-linear resistor, where specified
  • Binary inputs and outputs
  • Earthing
  • Communication connections

14.2 CT circuit verification

CT circuit testing is one of the most important commissioning activities.

Verify:

  • CT ratios
  • CT polarity
  • CT phase identification
  • CT secondary resistance
  • Cable resistance
  • CT earthing arrangement
  • Differential circuit continuity
  • Terminal tightness
  • Correct phase connections

The test must follow the approved CT circuit design.

14.3 CT excitation and knee-point verification

For high-impedance differential protection, CT excitation characteristics are particularly important.

The commissioning engineer should verify the available CT test reports and perform appropriate CT tests where required.

Confirm that the installed CTs satisfy the calculated application requirements.

14.4 Stabilizing resistor verification

Verify the installed stabilizing resistor value against the approved protection design.

Check the resistor’s rated voltage, power and physical installation.

The resistor must be installed and wired according to the manufacturer’s instructions.

14.5 Non-linear resistor verification

Where a voltage-limiting non-linear resistor is specified, verify its type and suitability against the approved design.

The installed component must match the calculated duty and manufacturer’s requirements.

14.6 Relay secondary injection testing

A suitable relay test set, such as an Omicron CMC, can be used to test the REB650 protection functions.

Testing should include:

  • HZPDIF operating behavior
  • Differential protection trip output
  • Alarm and indication signals
  • Overcurrent protection
  • Residual overcurrent protection
  • Breaker failure protection
  • Pole discordance
  • Voltage protection
  • Logic and binary I/O

The test procedure must be suitable for the high-impedance measuring arrangement. Do not apply generic low-impedance differential test methods without checking the HZPDIF function’s measurement principle and test requirements.

14.7 Stability testing

The scheme must be checked for stability under simulated external fault conditions.

The objective is to verify that the differential protection does not operate when the CT secondary currents are expected to balance.

The testing method must follow the ABB commissioning instructions and the approved scheme design.

14.8 Internal fault operation testing

Where permitted by the commissioning procedure, simulate the conditions representing an internal busbar fault.

Verify the correct differential protection operation and trip logic.

14.9 Check-zone testing

Where a check zone is configured, verify its operating and supervision logic.

Test the intended combination of individual zone and check-zone conditions.

14.10 Trip matrix testing

Test the complete breaker trip matrix.

Verify that each protection zone operates the correct circuit breakers and does not trip breakers associated with an unaffected busbar section.

14.11 Breaker failure testing

Test:

  • Breaker failure initiation
  • Current supervision
  • Retrip logic
  • Breaker failure timer
  • Backup tripping
  • Reset conditions

14.12 IEC 61850 testing

For IEC 61850 installations, verify the communication services and configured signals.

Check the GOOSE and MMS communication paths, including the actual status and control information exchanged with other IEDs.

14.13 Final commissioning documentation

Prepare and retain:

  • Final relay settings
  • PCM600 project
  • Approved protection logic
  • CT test reports
  • Secondary injection test reports
  • Trip matrix test results
  • IEC 61850 test records
  • As-built drawings
  • Commissioning report

15. Common REB650 Problems and Troubleshooting

Problem 1: Unwanted differential protection operation

Possible causes:

  • Incorrect CT polarity
  • Incorrect CT ratio
  • CT secondary wiring errors
  • Incorrect differential circuit connections
  • Incorrect zone allocation
  • Incorrect protection settings

Recommended action:

Check the CT circuits, polarity, phase identification and differential scheme drawings before changing relay settings.

Problem 2: Differential protection does not operate during an internal fault test

Possible causes:

  • Incorrect test connections
  • Incorrect HZPDIF configuration
  • Incorrect relay input allocation
  • Incorrect trip logic
  • Incorrect binary output mapping
  • Test quantities not appropriate for the function

Recommended action:

Review the relay configuration, test method, HZPDIF settings and complete trip signal path.

Problem 3: Instability during external faults

Possible causes:

  • CT saturation
  • Incorrect CT selection
  • Excessive CT secondary circuit resistance
  • Incorrect stabilizing resistor
  • Incorrect cable resistance assumptions
  • Incorrect protection design calculations

Recommended action:

Reassess the high-impedance stability calculations and verify the actual CT and cable characteristics.

Problem 4: Check-zone protection does not operate

Possible causes:

  • Incorrect check-zone CT circuit
  • Incorrect function configuration
  • Incorrect phase connections
  • Incorrect operating settings
  • Logic or trip matrix errors

Recommended action:

Check the complete check-zone circuit and the relevant HZPDIF instance configuration.

Problem 5: Incorrect busbar zone tripping

Possible causes:

  • Incorrect busbar selection logic
  • Incorrect disconnector status signals
  • Incorrect CT allocation
  • Incorrect trip matrix
  • Incorrect bus coupler logic

Recommended action:

Review the single-line diagram, switching conditions, input signals and approved trip matrix.

Problem 6: IEC 61850 communication failure

Possible causes:

  • Incorrect IP address
  • Incorrect SCL configuration
  • GOOSE dataset mismatch
  • Incorrect VLAN settings
  • Network switch configuration problems
  • Communication supervision alarms

Recommended action:

Check the communication configuration, SCL files, network switches and IED diagnostics.

16. ABB REB650 Compared with REB670

Both REB650 and REB670 are ABB Relion busbar protection products, but their protection architectures differ.

FeatureREB650REB670
Main applicationBusbar protectionBusbar protection
Main differential principleHigh impedanceLow impedance
Main differential functionHZPDIFLow-impedance numerical differential functions
CT arrangementCommon high-impedance differential circuitIndividual CT current inputs
Stabilizing resistorTypically required by the schemeNot used as the same high-impedance scheme component
CT engineeringStrict CT suitability and circuit calculationsNumerical CT supervision and differential stabilization
Busbar zone arrangementApplication-specific configured zonesNumerical zone selection and busbar replica
Check-zone arrangementAvailable in documented applicationsAvailable according to configuration
Engineering softwarePCM600PCM600
IEC 61850SupportedSupported

Which relay should be selected?

The selection depends on the substation design and protection philosophy.

REB650 is suitable where a high-impedance busbar protection scheme is appropriate and the CT installation satisfies the required design conditions.

REB670 is a different solution that uses numerical low-impedance differential protection and is intended for applications requiring that architecture.

The two relays should not be treated as interchangeable without reviewing the CT arrangement, protection design, functionality and project specifications.

17. Practical REB650 Engineering and Commissioning Checklist

Protection design

  • Review the substation single-line diagram
  • Identify the busbar arrangement
  • Define all differential protection zones
  • Define check-zone requirements
  • Calculate maximum external fault current
  • Verify CT ratios and characteristics
  • Calculate CT secondary circuit resistance
  • Calculate the stabilizing resistor
  • Verify the non-linear resistor requirements
  • Check internal fault sensitivity
  • Prepare the protection trip matrix

PCM600 engineering

  • Select the correct REB650 product version
  • Verify the hardware configuration
  • Configure HZPDIF instances
  • Configure supporting protection functions
  • Configure check-zone logic
  • Configure breaker failure logic
  • Map binary inputs and outputs
  • Verify trip logic
  • Configure IEC 61850 communication

Commissioning

  • Inspect relay hardware and wiring
  • Verify CT polarity and ratio
  • Test CT secondary circuits
  • Verify CT excitation characteristics
  • Verify stabilizing resistor
  • Verify non-linear resistor, where specified
  • Test HZPDIF functions
  • Test differential stability
  • Test internal fault operation
  • Test check-zone logic
  • Test trip matrix
  • Test breaker failure protection
  • Verify IEC 61850 communication
  • Save final settings and test reports

18. ABB REB650 Training by Elec-Engg

Elec-Engg provides practical power system protection and substation automation training for engineers working with ABB Relion protection systems.

Training can be customized for utilities, power plants, industrial companies, EPC contractors and protection engineering teams.

Customized company training

Training programs can be tailored to the installed protection relays, substation configurations and technical requirements of the engineering team.

A company course can focus specifically on high-impedance busbar differential protection, CT engineering, relay configuration and commissioning.

Online instructor-led training

Online training can cover the theoretical and practical engineering aspects of REB650, including protection principles, PCM600 configuration, protection settings, IEC 61850 and testing procedures.

Face-to-face training

Face-to-face courses can be arranged at the client’s premises or at an agreed training location, subject to scheduling and practical arrangements.

Practical training topics

A customized ABB REB650 training program may include:

  • Introduction to ABB Relion 650 series
  • REB650 hardware and architecture
  • High-impedance differential protection principles
  • CT selection for busbar protection
  • CT knee-point voltage calculations
  • Stabilizing resistor calculations
  • Non-linear resistor application
  • Differential protection zone design
  • Check-zone protection
  • Double busbar protection schemes
  • PCM600 engineering and configuration
  • IEC 61850 MMS and GOOSE
  • Secondary injection testing
  • Busbar protection commissioning
  • Troubleshooting and maintenance

The training duration, technical depth and delivery method can be adapted to the client’s requirements.

For ABB REB650 training, customized busbar protection courses, online instruction or face-to-face training, contact Elec-Engg:

Website: https://elec-engg.com/

19. Frequently Asked Questions About ABB REB650

What is ABB REB650?

ABB REB650 is a numerical busbar protection and control IED from the Relion 650 series.

What is the main protection function in REB650?

The main differential protection function is HZPDIF, which provides high-impedance differential protection.

Is REB650 a high-impedance or low-impedance busbar relay?

REB650 uses high-impedance differential protection in its documented busbar applications. REB670 uses a different low-impedance numerical differential protection architecture.

What is HZPDIF?

HZPDIF is ABB’s high-impedance differential protection function. It is used to detect internal faults within a protected differential zone.

Does REB650 support double busbar protection?

Yes. Documented REB650 applications include double busbar protection with individual busbar zones and the possibility of a check zone.

What is a check zone in busbar protection?

A check zone is an additional differential supervision zone that helps improve the security of the busbar protection scheme.

Why is a stabilizing resistor required?

A stabilizing resistor is used in conventional high-impedance differential schemes to maintain stability during external faults, including conditions involving CT saturation.

What is the purpose of a Metrosil resistor?

A non-linear voltage-limiting resistor can be used to limit excessive voltage across the high-impedance differential circuit during severe internal faults.

Which software is used to configure REB650?

ABB PCM600 is the engineering platform used for compatible Relion 650 series IEDs.

Can REB650 communicate through IEC 61850?

Yes. REB650 supports IEC 61850-based substation automation integration, subject to the product version and communication configuration.

Can REB650 be tested using Omicron CMC?

Suitable Omicron CMC test equipment can be used for secondary injection testing. The test procedure must be designed for the high-impedance differential arrangement and the actual HZPDIF configuration.

What is the difference between REB650 and REB670?

REB650 uses high-impedance differential protection in its documented applications, while REB670 uses low-impedance numerical busbar differential protection. Their CT circuits, engineering methods and application requirements are different.

20. Conclusion

The ABB REB650 is a dedicated busbar protection and control IED based on high-impedance differential protection technology.

Its application requires a strong understanding of CT characteristics, CT secondary circuit design, differential protection principles, stabilizing resistor calculations, check-zone supervision and breaker trip logic.

For protection and commissioning engineers, the most important part of REB650 engineering is not simply configuring the relay. It is ensuring that the complete CT and differential circuit has been correctly designed, installed, tested and commissioned.

A properly engineered REB650 scheme can provide dependable protection for important busbar installations and help reduce the consequences of internal busbar faults.

For engineers working with ABB protection systems, understanding REB650 provides valuable practical knowledge of high-impedance differential protection and its application in modern substations.

Leave a Comment