- 1. Introduction to MiCOM P921
- 2. Main Applications of MiCOM P921
- 3. Main Protection Functions
- 4. Undervoltage Protection – ANSI 27
- 5. Overvoltage Protection – ANSI 59
- 6. Residual Overvoltage Protection – ANSI 59N
- 7. Voltage Transformer Connections
- 8. MiCOM P921 Settings and Configuration
- 9. Binary Inputs, Output Relays and Programmable Logic
- 10. Communication and Substation Integration
- 11. Measurements, Events and Indications
- 12. MiCOM P921 Engineering Workflow
- 13. Testing and Commissioning of MiCOM P921
- 14. Common MiCOM P921 Problems and Troubleshooting
- 15. MiCOM P921 Compared with P922 and P923
- 16. Advantages and Limitations of MiCOM P921
- 17. MiCOM P921 Training by Elec-Engg
- 18. Conclusion
1. Introduction to MiCOM P921
The MiCOM P921 is a dedicated voltage protection relay designed to monitor electrical system voltage and detect abnormal voltage conditions.
It is part of the MiCOM P92x voltage protection family, which includes the P921, P922 and P923 models. Unlike the P922 and P923, which offer additional voltage and frequency management functions, the P921 focuses on three principal voltage protection functions:
- Undervoltage protection (ANSI 27).
- Overvoltage protection (ANSI 59).
- Residual overvoltage protection (ANSI 59N).
The P921 is suitable for applications where reliable voltage supervision and protection are required without the more extensive frequency and load-shedding features available in other P92x models. Schneider Electric+2
Legacy product The MiCOM P92x product range has been discontinued. The P921 remains relevant for engineers maintaining existing installations, testing protection panels and planning relay replacement. Schneider Electric Thailand
2. Main Applications of MiCOM P921
The P921 can be applied wherever voltage conditions must be monitored and abnormal voltage levels must initiate an alarm or trip.
Typical applications include:
- Medium-voltage switchgear.
- High-voltage substation voltage monitoring panels.
- Busbar voltage protection.
- Transformer secondary voltage supervision.
- Industrial power distribution systems.
- Undervoltage protection schemes.
- Overvoltage protection schemes.
- Residual voltage monitoring.
- Voltage-based load disconnection schemes.
The relay is particularly useful where dedicated voltage protection is required independently of the main feeder or transformer protection relay.
3. Main Protection Functions
The MiCOM P921 provides three main protection functions.
| Protection function | ANSI code | Main purpose |
|---|---|---|
| Undervoltage | 27 | Detects voltage below the configured threshold |
| Overvoltage | 59 | Detects voltage above the configured threshold |
| Residual overvoltage | 59N | Detects excessive residual or zero-sequence voltage |
Each protection function has three stages, with configurable thresholds and operating delays. The P921 supports definite-time and inverse-time characteristics as documented for the voltage protection stages. ManualZilla+1
Important: The P921 does not provide the underfrequency, overfrequency, negative-sequence overvoltage and positive-sequence undervoltage functions listed for the P922 and P923. These model differences are important when selecting a relay for a project. Schneider Electric Downloads+1
4. Undervoltage Protection – ANSI 27
Undervoltage protection detects when the measured voltage falls below a configured threshold.
A voltage reduction can indicate:
- Short-circuit faults.
- Transformer or feeder problems.
- Loss of supply.
- Heavy loading.
- Network instability.
- Abnormal switching conditions.
The P921 provides three undervoltage protection stages.
4.1 Three-stage undervoltage protection
The three stages allow engineers to establish different protection thresholds and time delays.
For example, a protection design may use:
- Stage 1 for an initial undervoltage alarm or delayed disconnection.
- Stage 2 for more severe voltage depression.
- Stage 3 for a lower voltage condition requiring faster operation.
The actual application and settings depend on the system study.
4.2 AND and OR logic
An important engineering feature is the ability to configure undervoltage detection according to the required phase logic.
OR logic: The protection operates when the selected voltage condition is detected on any one of the monitored phases.
AND logic: The protection operates when the selected condition is detected on all three phases.
This distinction is particularly important when designing protection for complete loss of supply versus a voltage reduction affecting only one phase.
4.3 Definite-time and inverse-time characteristics
The P921 supports definite-time and inverse-time characteristics for the applicable voltage protection stages.
For definite-time protection:
\[ t=t_{\text{set}} \]
For an inverse-time characteristic, operating time changes according to the magnitude of the measured voltage relative to the configured threshold.
The exact inverse-time equation and available characteristic options should be taken from the relevant P921 technical guide. Studylib
5. Overvoltage Protection – ANSI 59
Overvoltage protection detects when the measured voltage exceeds the configured threshold.
Possible causes include:
- Sudden load rejection.
- Voltage regulator malfunction.
- Transformer tap-changer problems.
- Incorrect system switching.
- Abnormal network operating conditions.
- Ferroresonance or other resonant phenomena, depending on the system.
The P921 provides three overvoltage stages.
5.1 Overvoltage settings
Important settings include:
- Voltage pickup threshold.
- Operating delay.
- Selected time characteristic.
- Phase measurement configuration.
- Alarm or trip output assignment.
- Blocking and reset logic.
The protection engineer must coordinate the settings with equipment insulation levels, transformer ratings, generator limits where applicable, and the network operating philosophy.
6. Residual Overvoltage Protection – ANSI 59N
Residual overvoltage protection detects an abnormal residual voltage component.
The residual voltage is related to the three phase-to-neutral voltages:
\[ 3V_0=V_A+V_B+V_C \]
Where:
- \(V_A\) is phase-A voltage.
- \(V_B\) is phase-B voltage.
- \(V_C\) is phase-C voltage.
- \(3V_0\) is the residual voltage.
A significant residual voltage may indicate an earth fault in an unearthed, impedance-earthed or otherwise suitable network arrangement.
The P921 provides three stages of residual overvoltage protection. The available measurement arrangement depends on the relay configuration and VT wiring. ManualZilla+1
6.1 Residual voltage measurement
Residual voltage can be obtained using a suitable VT secondary connection or a configured derived residual voltage arrangement, depending on the selected relay configuration.
Engineers must verify:
- VT connection type.
- Residual voltage input arrangement.
- Phase polarity.
- Neutral connections.
- Relay configuration.
- Correct voltage scaling.
Do not assume that every P921 hardware configuration has a dedicated residual voltage input.
7. Voltage Transformer Connections
Correct voltage transformer connections are essential for accurate P921 operation.
The P921 catalogue identifies several available voltage input configurations:
- Three phase-to-neutral voltage inputs.
- Two phase-to-phase voltage inputs plus residual voltage.
- Two phase-to-neutral voltage inputs plus residual voltage.
- One phase-to-phase voltage input plus residual voltage.
The selected configuration must match the actual VT secondary wiring and the required protection functions. ManualZilla
7.1 Three phase-to-neutral connection
The relay receives three phase-to-neutral voltages:
- \(V_{AN}\)
- \(V_{BN}\)
- \(V_{CN}\)
This arrangement is suitable for three-phase undervoltage and overvoltage monitoring.
7.2 Phase-to-phase connection
The relay can also be configured for phase-to-phase voltage measurement.
In this arrangement, the engineer must ensure that the selected voltage inputs correspond to the actual secondary connections.
7.3 Connection with residual voltage
Where residual voltage protection is required, the VT arrangement must provide the appropriate residual voltage measurement.
The wiring and relay configuration must be checked together. Incorrect phase identification or polarity can cause incorrect residual voltage measurement and unwanted protection operation.
8. MiCOM P921 Settings and Configuration
The P921 has a relatively straightforward configuration compared with more advanced protection IEDs.
Its engineering involves selecting the voltage measurement arrangement, configuring protection thresholds and delays, assigning inputs and outputs, and defining the required blocking and trip logic.
8.1 General settings
Important general parameters include:
- Nominal system frequency.
- VT primary voltage.
- VT secondary voltage.
- Voltage measurement configuration.
- Relay identification.
- Communication settings.
- Output contact configuration.
8.2 Undervoltage settings
For each enabled stage, configure:
- Pickup threshold.
- Operating time.
- Definite-time or inverse-time characteristic, where available.
- AND/OR phase selection.
- Output assignment.
- Reset behaviour.
8.3 Overvoltage settings
For each stage, configure:
- Pickup threshold.
- Operating time.
- Time characteristic.
- Alarm or trip assignment.
- Reset behaviour.
8.4 Residual overvoltage settings
Configure:
- Residual voltage measurement arrangement.
- Pickup threshold.
- Operating delay.
- Output assignment.
- Reset behaviour.
8.5 Setting groups
The P921 catalogue identifies one setting group. It should therefore not be treated as having the multiple protection setting groups available in some larger MiCOM protection relays. ManualZilla
9. Binary Inputs, Output Relays and Programmable Logic
The P921 provides a compact arrangement of binary inputs and output contacts.
According to the MiCOM protection relay guide, the P921 provides:
- 2 programmable binary inputs.
- 4 output relays.
- Configurable LED indications.
- Output contact latching.
- Blocking logic.
- Circuit breaker state monitoring. ManualZilla
9.1 Binary inputs
Binary inputs can be assigned to external signals according to the application.
Examples include:
- External blocking.
- Protection reset.
- Circuit breaker status.
- External alarm.
- Scheme interlocking.
The actual input assignment should be documented in the approved logic diagram.
9.2 Output relay assignment
The four output relays can be assigned to protection and control signals.
A typical design may use outputs for:
- Undervoltage trip.
- Overvoltage trip.
- Residual overvoltage trip.
- Common alarm.
The actual output assignment depends on the panel design and protection philosophy.
9.3 Output contact latching
The P921 supports output contact latching.
This allows an output to remain operated after the initiating protection condition has disappeared, until the configured reset condition is satisfied.
Engineers should verify the latching arrangement during commissioning, particularly where the relay output operates a circuit breaker trip circuit.
10. Communication and Substation Integration
The P921 supports serial communication for remote monitoring and integration.
The documented communication interfaces include:
- RS232.
- RS485.
Supported transmission protocols include:
- Courier.
- Modbus.
- IEC 60870-5-103. ManualZilla+1
10.1 Modbus integration
Modbus can be used to retrieve information such as:
- Relay measurements.
- Protection status.
- Alarm indications.
- Device information.
- Available remote data.
The communication master must be configured according to the relay address and communication parameters.
10.2 IEC 60870-5-103
IEC 60870-5-103 can be used for communication with compatible substation control and monitoring systems.
The communication design should include:
- Physical interface selection.
- Relay address.
- Baud rate.
- Protocol configuration.
- Signal mapping.
- Master station configuration.
- Communication testing.
10.3 Courier communication
Courier is a MiCOM communication protocol used for relay configuration and data access through compatible engineering and communication tools.
For existing installations, confirm the appropriate software version, interface hardware and operating-system compatibility before attempting to connect to the relay.
11. Measurements, Events and Indications
The P921 provides voltage measurements and protection status indications.
Engineers can use these values to assess:
- Normal system voltage.
- Phase voltage imbalance.
- Voltage reduction.
- Excessive voltage.
- Residual voltage conditions.
- Protection pickup and operation.
The relay’s LEDs can be configured to indicate relevant protection conditions.
The available event and fault information should be checked in the specific relay version and technical documentation.
12. MiCOM P921 Engineering Workflow
A typical engineering workflow includes:
- Review the single-line diagram.
- Identify the protected busbar or voltage measurement point.
- Confirm the relay model and hardware configuration.
- Review the VT secondary circuit.
- Confirm voltage input configuration.
- Calculate the voltage scaling.
- Develop undervoltage settings.
- Develop overvoltage settings.
- Develop residual overvoltage settings.
- Configure the phase logic.
- Assign binary inputs and output relays.
- Configure communication parameters.
- Review alarms and LED indications.
- Save and document the final settings.
- Perform secondary injection and functional testing.
The final settings must be approved through the project’s protection engineering process.
13. Testing and Commissioning of MiCOM P921
Testing should verify the relay’s measurement accuracy, protection pickup levels, operating delays, logic and output contacts.
13.1 Initial inspection
Before testing, verify:
- Relay model and serial number.
- Auxiliary supply.
- VT wiring.
- Voltage input terminals.
- Binary input wiring.
- Output contact wiring.
- Earthing.
- Communication connections.
- Relay self-supervision status.
13.2 Voltage measurement testing
Apply balanced three-phase voltage using a suitable secondary injection test set.
Verify:
- Phase-A voltage.
- Phase-B voltage.
- Phase-C voltage.
- Phase-to-phase voltage, where applicable.
- Residual voltage.
- Correct voltage scaling.
Compare the relay measurements with the injected values.
13.3 Undervoltage protection testing
For each enabled stage:
- Apply normal voltage.
- Reduce the voltage below the pickup threshold.
- Confirm protection pickup.
- Measure the operating time.
- Verify the assigned output relay.
- Increase the voltage to confirm reset.
- Repeat using the required AND or OR phase logic.
13.4 Overvoltage protection testing
For each enabled stage:
- Apply normal voltage.
- Increase the voltage above the configured threshold.
- Verify pickup.
- Measure the operating time.
- Verify the output contact.
- Reduce the voltage and confirm reset.
13.5 Residual overvoltage testing
Apply suitable unbalanced phase voltages or a residual voltage signal according to the selected VT configuration.
Verify:
- Residual voltage measurement.
- Pickup threshold.
- Operating delay.
- Output contact operation.
- Reset behaviour.
13.6 Binary input testing
Test each configured binary input by applying the appropriate external signal.
Confirm:
- Input status.
- Blocking operation.
- Reset operation.
- Circuit breaker status indication.
- Logic response.
13.7 Output relay testing
Test all four output relays.
Confirm:
- Correct protection assignment.
- Contact operation.
- Contact reset.
- Latching behaviour.
- Alarm indication.
- Circuit breaker trip circuit operation, where applicable.
13.8 Communication testing
Verify the selected serial communication interface and protocol.
Test:
- RS232 or RS485 connection.
- Relay address.
- Baud rate.
- Courier communication.
- Modbus communication.
- IEC 60870-5-103 communication, where used.
- Measurement retrieval.
- Protection status retrieval.
13.9 Final functional testing
Where the P921 is installed in a complete voltage protection panel, perform an integrated test from secondary voltage injection through to the final alarm or circuit breaker trip output.
Record all pickup values, operating times, logic states and output contact results.
14. Common MiCOM P921 Problems and Troubleshooting
| Problem | Possible cause | Recommended checks |
|---|---|---|
| Undervoltage protection operates unexpectedly | Incorrect VT ratio or wiring | Check voltage inputs and scaling |
| Overvoltage protection does not operate | Incorrect threshold or configuration | Review settings and injected voltage |
| Residual voltage is incorrect | Incorrect VT connection or polarity | Verify residual voltage circuit |
| Protection operates on the wrong phase | Phase identification error | Check phase assignment and wiring |
| Protection does not reset | Latching or reset configuration | Review output latching and reset logic |
| Trip output does not operate | Incorrect output assignment | Check output configuration and wiring |
| External blocking does not work | Incorrect binary input assignment | Check input configuration and logic |
| Communication fails | Incorrect serial settings or wiring | Check RS232/RS485, address and baud rate |
| Incorrect voltage measurement | VT ratio or connection configuration | Verify VT primary/secondary data |
Always check the measured values and event indications before changing protection settings.
15. MiCOM P921 Compared with P922 and P923
The three relays belong to the same voltage protection family but have different application capabilities.
| Function | P921 | P922 | P923 |
|---|---|---|---|
| Phase undervoltage (27) | Yes | Yes | Yes |
| Phase overvoltage (59) | Yes | Yes | Yes |
| Residual overvoltage (59N) | Yes | Yes | Yes |
| Negative-sequence overvoltage (47) | No | Yes | Yes |
| Positive-sequence undervoltage (27D) | No | Yes | Yes |
| Undervoltage/overvoltage frequency-independent protection | Yes | Yes | Yes |
| Underfrequency/overfrequency (81) | No | Yes | Yes |
| Rate of change of frequency (81R) | No | No | Yes |
| Delta U / Delta T | No | No | Yes |
| Load-shedding applications | Basic voltage protection | Extended | Extended |
The table summarizes the principal model differences. Exact availability and configuration should be checked against the applicable technical documentation. Schneider Electric Downloads+1
16. Advantages and Limitations of MiCOM P921
Advantages
- Dedicated voltage protection.
- Three-stage undervoltage protection.
- Three-stage overvoltage protection.
- Three-stage residual overvoltage protection.
- Definite-time and inverse-time characteristics for applicable stages.
- Configurable AND/OR phase logic.
- Compact binary input and output arrangement.
- Serial communication support.
- Suitable for existing voltage protection panels.
Limitations
- No dedicated underfrequency or overfrequency protection.
- No negative-sequence overvoltage protection.
- No positive-sequence undervoltage protection.
- Only one setting group.
- Limited binary input and output capacity compared with more advanced IEDs.
- Discontinued product range.
If frequency protection, load shedding or more extensive voltage management is required, engineers should evaluate the P922, P923 or a suitable modern replacement.
17. MiCOM P921 Training by Elec-Engg
Elec-Engg provides practical power system protection and substation automation training for engineers working in utilities, power plants, industrial facilities and engineering companies.
Our training programs cover:
- Voltage protection fundamentals.
- Undervoltage and overvoltage protection.
- Residual voltage and earth fault principles.
- Voltage transformer circuits and connections.
- Protection coordination and settings.
- MiCOM relay configuration and engineering.
- Binary inputs, output relays and protection logic.
- Modbus and IEC 60870-5-103 communication.
- Secondary injection testing using Omicron CMC and Test Universe.
- Commissioning and troubleshooting.
- Disturbance and event analysis.
Available training methods:
- Online live training.
- Structured self-paced training.
- Face-to-face technical training.
- Customized in-house training for companies and utilities.
Training can be adapted to the relay models installed at your facility and the practical requirements of protection, commissioning, operation and maintenance engineers.
Visit Elec-Engg for power system protection and substation automation courses.
18. Conclusion
The MiCOM P921 is a dedicated voltage protection relay providing three-stage undervoltage, overvoltage and residual overvoltage protection.
Its configurable measurement arrangements, phase logic, output contacts and serial communication make it suitable for a range of voltage protection applications.
For engineers working with existing MiCOM P921 installations, understanding VT connections, voltage scaling, protection characteristics and output logic is essential for reliable operation.
The P921 should not be confused with the P922 and P923, which provide additional voltage and frequency protection functions.