GE Multilin 850 Feeder Protection Relay: Complete Technical Guide to Protection Functions, Settings, Configuration, IEC 61850 and Testing

Table Of Contents
  1. 1. Introduction
  2. 2. GE Multilin 850 Relay Overview
  3. 3. Feeder Protection Philosophy
  4. 4. GE Multilin 850 Architecture
  5. 5. CT Configuration and Engineering
  6. 6. VT Configuration
  7. 7. Phase Overcurrent Protection – ANSI 50/51
  8. 8. Practical Overcurrent Setting Example
  9. 9. Earth-Fault Protection – ANSI 50N/51N and 50G/51G
  10. 10. Directional Overcurrent Protection – ANSI 67 and 67N
  11. 11. Voltage Protection – ANSI 27 and 59
  12. 12. Frequency Protection – ANSI 81
  13. 13. Breaker Failure Protection – ANSI 50BF
  14. 14. Autoreclosing – ANSI 79
  15. 15. Feeder Protection Coordination
  16. 16. Programmable Logic and Trip Matrix
  17. 17. GE Multilin 850 Configuration Workflow
  18. 18. IEC 61850 and Substation Automation
  19. 19. Testing and Commissioning of the GE Multilin 850
  20. 20. Common GE Multilin 850 Troubleshooting Problems
  21. 21. GE Multilin 850 Commissioning Checklist
  22. 22. GE Multilin 850 Compared with Other Feeder Protection Relays
  23. 23. Training on GE Multilin Feeder Protection Relays by Elec-Engg
  24. 24. Conclusion
  25. 25. Frequently Asked Questions

1. Introduction

The GE Multilin 850 Feeder Protection Relay is a numerical protection platform designed for feeder protection and control applications in utility and industrial electrical distribution systems.

Feeder circuits connect substations, transformers, distribution networks and industrial loads. Their protection systems must detect short circuits and earth faults, isolate the affected circuit and coordinate with other protection devices to maintain continuity of supply.

Modern feeder protection also requires accurate measurement, event recording, programmable logic, communication and integration with substation automation systems.

The GE Multilin 850 is intended for applications requiring a combination of feeder protection, monitoring and control capabilities. The exact available functions depend on the installed hardware, firmware and product configuration.

This article explains the practical engineering considerations for applying the GE Multilin 850, including:

  • Relay architecture and application
  • CT and VT configuration
  • Phase overcurrent protection (ANSI 50/51)
  • Earth-fault protection
  • Directional overcurrent protection (ANSI 67/67N)
  • Voltage and frequency protection
  • Breaker failure protection
  • Autoreclosing
  • Protection coordination
  • Programmable logic
  • IEC 61850 and SCADA integration
  • Configuration and settings management
  • Secondary injection testing
  • Commissioning and troubleshooting

2. GE Multilin 850 Relay Overview

The GE Multilin 850 belongs to the feeder protection relay family.

It is designed for feeder applications where protection, measurement, monitoring and control are required in a numerical IED.

Typical applications include:

  • Medium-voltage distribution feeders
  • Industrial power distribution
  • Utility substations
  • Transformer outgoing feeders
  • Industrial plant incomers
  • Radial distribution systems
  • Ring distribution networks, where the required directional scheme is supported
  • Critical industrial feeder circuits

The relay receives electrical measurements from CTs and, where required, VTs. It processes these signals and evaluates the configured protection functions.

When a protection element operates, the relay can initiate an alarm or trip through the configured logic and output circuits.

A complete feeder protection installation may include:

  1. Current transformers.
  2. Voltage transformers.
  3. Numerical protection relay.
  4. Circuit breaker.
  5. Breaker auxiliary contacts.
  6. Trip and close circuits.
  7. DC auxiliary supply.
  8. Communication network.
  9. SCADA or substation automation system.

The protection relay must be engineered as part of this complete system.

3. Feeder Protection Philosophy

The primary objective of feeder protection is to detect faults and isolate the affected feeder without unnecessarily disconnecting healthy parts of the electrical network.

The protection design must account for:

  • Maximum normal load current
  • Emergency loading
  • Minimum and maximum short-circuit current
  • Phase-to-phase faults
  • Three-phase faults
  • Single-phase earth faults
  • Double-phase earth faults
  • Transformer inrush
  • Motor starting
  • Neutral-earthing arrangement
  • Cable and overhead-line thermal limits
  • Upstream and downstream protection
  • Circuit-breaker clearing time

A radial feeder often uses non-directional overcurrent protection. However, ring networks, parallel feeders and multiple-source systems may require directional protection to achieve selectivity.

The final protection philosophy should be based on a short-circuit study, load-flow information and a protection coordination study.

4. GE Multilin 850 Architecture

A numerical feeder relay combines measurement, protection processing, logic, inputs, outputs and communication.

4.1 Current Measurement

Current transformers provide scaled current signals to the relay.

The relay uses these signals to calculate:

  • Phase currents
  • Residual or ground current, depending on the measurement arrangement
  • Overcurrent operating quantities
  • Directional operating quantities, where supported
  • Other current-derived measurements

The CT ratio and input rating must be configured correctly.

4.2 Voltage Measurement

Where voltage inputs are installed and used, the relay can measure voltage quantities for applicable protection and monitoring functions.

These may include:

  • Phase voltage
  • Phase-to-phase voltage
  • Frequency
  • Directional polarizing quantities
  • Voltage supervision

The actual measurements depend on the installed hardware and configuration.

4.3 Protection Processing

The protection algorithms evaluate the measured quantities against configured thresholds and characteristics.

Typical feeder functions include phase overcurrent and earth fault. Additional functions depend on the installed configuration.

4.4 Binary Inputs and Outputs

Binary inputs can receive external status and control signals, such as:

  • Breaker open
  • Breaker closed
  • External trip
  • External blocking
  • Local/remote selection
  • Protection permissive

Binary outputs can be assigned to:

  • Breaker trip
  • Alarm
  • Lockout
  • External control
  • Other configured functions

The actual I/O quantity and electrical ratings must be verified from the order code and hardware documentation.

4.5 Event and Disturbance Records

Event and disturbance information can support fault analysis and maintenance.

Depending on the relay configuration, useful records may include:

  • Protection operation events
  • Breaker status changes
  • Measurements
  • Disturbance waveforms
  • Relay alarms
  • Sequence-of-events information

Correct time synchronization is important when comparing records from multiple IEDs.

5. CT Configuration and Engineering

Correct CT configuration is essential for accurate protection.

Consider an illustrative 11 kV feeder with a maximum operating current of 320 A.

Assume a CT ratio of:

[
400/1\ A
]

The secondary current at maximum load is:

[
I_s=\frac{320}{400}
]

[
I_s=0.8\ A
]

The relay should measure approximately 0.8 A at rated primary load, assuming an ideal CT and compatible 1 A input.

5.1 CT Selection

The CT should be selected considering:

  • Primary rated current
  • Secondary rated current
  • Accuracy class
  • Burden
  • Short-time thermal withstand
  • Dynamic withstand
  • Fault current
  • Saturation performance
  • Secondary cable resistance

5.2 CT Polarity

Correct polarity is particularly important for:

  • Directional overcurrent protection
  • Residual current calculation
  • Power measurement
  • Differential schemes in associated equipment

The engineer should verify polarity against approved drawings and actual CT terminal markings.

5.3 CT Saturation

CT saturation can distort the secondary current waveform during high fault currents.

The impact depends on:

  • Fault magnitude
  • Fault X/R ratio
  • CT core characteristics
  • Secondary burden
  • Cable resistance
  • Remanent flux
  • Protection operating time

CT saturation should be considered when designing fast protection schemes and when high fault levels are expected.

6. VT Configuration

Voltage transformers may be required for directional protection, voltage protection, frequency measurement and other functions.

Verify:

  • Primary voltage
  • Secondary voltage
  • VT ratio
  • Phase sequence
  • Phase assignment
  • Secondary earthing
  • Fuse supervision
  • Voltage input configuration

6.1 Example of VT Ratio

For an 11 kV system with a 110 V phase-to-phase secondary:

[
K_V=\frac{11000}{110}=100
]

The configured ratio and measurement reference must correspond to the actual VT connection.

Incorrect VT configuration can affect voltage measurements and directional protection decisions.

7. Phase Overcurrent Protection – ANSI 50/51

Phase overcurrent protection detects excessive current resulting from short circuits or overload conditions.

7.1 Instantaneous Overcurrent – ANSI 50

ANSI 50 is used for high-current fault detection.

The pickup setting must be selected to avoid unwanted operation during:

  • Motor starting
  • Transformer energization
  • Load switching
  • Downstream faults that should be cleared by another device

The engineer must verify that the setting provides sufficient sensitivity for faults within the intended protection zone.

7.2 Time Overcurrent – ANSI 51

ANSI 51 operates when current exceeds a configured pickup for a defined time.

Possible characteristics include:

  • Definite time
  • Standard inverse
  • Very inverse
  • Extremely inverse

The available characteristics must be confirmed for the exact relay configuration.

7.3 IEC Standard Inverse Equation

A commonly used IEC standard inverse equation is:

[
t=TMS\times\frac{0.14}{(I/I_s)^{0.02}-1}
]

Where:

  • (t) = operating time
  • (TMS) = time multiplier setting
  • (I) = measured current
  • (I_s) = pickup current

This equation is an illustrative standard characteristic. The actual relay curve implementation must be checked against manufacturer documentation.

8. Practical Overcurrent Setting Example

Consider the following feeder:

ParameterValue
System voltage11 kV
Maximum load current320 A
CT ratio400/1 A
Assumed pickup380 A
Maximum fault current7,000 A

The secondary pickup is:

[
I_s=\frac{380}{400}
]

[
I_s=0.95\ A
]

At a primary fault current of 7,000 A:

[
I_{\text{fault,secondary}}=\frac{7000}{400}
]

[
I_{\text{fault,secondary}}=17.5\ A
]

These are ideal values before considering CT saturation and measurement limitations.

The assumed 380 A pickup is not a recommended universal setting. Final settings must be based on the maximum operating load, emergency conditions, minimum fault level and coordination requirements.

9. Earth-Fault Protection – ANSI 50N/51N and 50G/51G

Earth-fault protection detects current associated with an unintended connection between a phase conductor and earth.

Common causes include:

  • Cable insulation failure
  • Switchgear insulation breakdown
  • Moisture ingress
  • Damaged conductors
  • Contaminated insulation
  • Winding insulation failure

9.1 Residual Current Calculation

Where three phase CT measurements are used:

[
I_{\text{res}}=I_A+I_B+I_C
]

Under balanced conditions:

[
I_{\text{res}}\approx0
]

An earth fault can produce a non-zero residual current.

9.2 Dedicated Earth-Fault CT

A core-balance CT can be installed around all three phase conductors.

It measures the residual current directly and may provide sensitive earth-fault detection.

9.3 Neutral-Earthing Arrangement

The earth-fault protection philosophy depends on whether the network is:

  • Solidly earthed
  • Resistance-earthed
  • Reactance-earthed
  • Isolated
  • Resonant-earthed

For resistance-earthed systems, the neutral resistor often limits the earth-fault current. The pickup must be selected with reference to the available fault current and required sensitivity.

9.4 Setting Considerations

Consider:

  • Minimum earth-fault current
  • Maximum residual current during normal operation
  • CT accuracy
  • Cable charging current
  • Neutral-earthing impedance
  • Downstream protection
  • Upstream protection
  • Required operating time

Do not select sensitive earth-fault settings without evaluating normal residual current and the network’s earthing method.

10. Directional Overcurrent Protection – ANSI 67 and 67N

Directional overcurrent protection is important where the direction of fault current is required for selectivity.

Typical applications include:

  • Ring networks
  • Parallel feeders
  • Multiple-source systems
  • Industrial networks with embedded generation
  • Interconnected distribution systems

10.1 Operating Principle

Directional overcurrent protection evaluates current magnitude and its relationship with a polarizing reference.

The relay determines whether the fault is in the defined forward or reverse direction.

10.2 Phase Directional Protection

ANSI 67 combines phase overcurrent pickup with directional supervision.

Both the current threshold and directional criteria must be satisfied.

10.3 Directional Earth-Fault Protection

ANSI 67N evaluates residual or neutral current against an appropriate polarizing quantity.

Possible methods depend on the relay design and the system’s neutral-earthing arrangement.

10.4 Commissioning Directional Elements

Verify:

  • CT polarity
  • VT polarity
  • Phase sequence
  • Phase assignment
  • Voltage reference
  • Current reference
  • Forward direction
  • Reverse direction
  • Characteristic angle
  • Operating and blocking conditions

The directional method and available polarizing options must be confirmed for the installed 850 version.

11. Voltage Protection – ANSI 27 and 59

Voltage protection may be required to detect abnormal supply conditions.

11.1 Undervoltage – ANSI 27

Undervoltage protection can be applied to:

  • Industrial feeder supervision
  • Motor load protection
  • Load shedding
  • Abnormal network conditions

11.2 Overvoltage – ANSI 59

Overvoltage protection detects excessive voltage that may stress connected equipment.

11.3 Voltage Protection Engineering

Consider:

  • Normal system voltage range
  • Emergency operating conditions
  • VT accuracy
  • VT fuse failure
  • Voltage transformer supervision
  • Downstream equipment requirements
  • Coordination with upstream protection

Verify that the required voltage functions and input configuration are supported by the installed relay.

12. Frequency Protection – ANSI 81

Frequency protection can be used to detect abnormal network frequency.

Typical functions include:

  • Underfrequency (81U)
  • Overfrequency (81O)

Applications may include:

  • Automatic load shedding
  • Industrial islanding schemes
  • Generator-connected distribution systems
  • Abnormal supply supervision

The engineer must verify the available frequency elements and required voltage measurement configuration.

13. Breaker Failure Protection – ANSI 50BF

Breaker failure protection detects failure of a circuit breaker to interrupt fault current following a trip command.

A typical scheme includes:

  1. Protection trip initiation.
  2. Breaker trip command.
  3. Current supervision.
  4. Breaker auxiliary contact supervision.
  5. Breaker failure timer.
  6. Retrip or backup trip logic.

13.1 Timer Selection

The breaker failure timer must account for:

  • Relay output delay
  • Breaker opening time
  • Current interruption
  • Auxiliary contact response
  • Safety margin
  • Backup protection coordination

The availability and implementation of ANSI 50BF must be confirmed in the exact 850 configuration. External logic may be required in some schemes.

14. Autoreclosing – ANSI 79

Autoreclosing is used mainly on overhead-line feeders where temporary faults are common.

A typical sequence includes:

  • Protection trip
  • Dead time
  • Reclose command
  • Reclaim time
  • Shot counter
  • Reclose blocking
  • Lockout

14.1 Dead Time

Dead time is the interval between breaker opening and the next close attempt.

It allows temporary faults, such as those caused by lightning or transient contact, to disappear.

14.2 Reclaim Time

Reclaim time defines the period during which a successful reclose must remain stable before the sequence is considered reset.

14.3 Reclose Blocking

Reclosing may be blocked for conditions such as:

  • Manual trip
  • Transformer protection operation
  • Busbar protection operation
  • Breaker failure
  • Lockout
  • Breaker not ready
  • Other project-defined conditions

Autoreclosing should not be applied indiscriminately to every feeder. Verify the function’s availability and suitability for the actual circuit.

15. Feeder Protection Coordination

Protection coordination ensures that the device closest to a fault operates first.

For a radial distribution system, downstream protection normally clears faults before upstream protection.

15.1 Coordination Time Interval

A simplified coordination relationship is:

[
t_{\text{upstream}}\geq t_{\text{downstream}}+CTI
]

The required coordination margin depends on:

  • Relay operating time
  • Circuit-breaker clearing time
  • Relay overshoot
  • CT performance
  • Protection philosophy
  • Project standards

15.2 Time-Current Curve Assessment

A coordination study should plot the operating curves of:

  • Downstream feeder relay
  • GE Multilin 850
  • Upstream transformer relay
  • Fuse links, where applicable
  • Motor protection relays
  • Reclosers, where applicable

The curves should be checked at minimum and maximum fault current.

15.3 Protection Sensitivity

A setting must be sensitive enough to detect the minimum fault current within the intended zone.

At the same time, it must remain stable during normal load, motor starting and permissible transient conditions.

16. Programmable Logic and Trip Matrix

Programmable logic allows protection elements and external signals to be combined into application-specific operating logic.

A simplified feeder trip expression is:

[
TRIP=50\ OR\ 51\ OR\ 50N\ OR\ 51N
]

This is an illustrative logic expression, not a universal F650 or 850 configuration.

A practical trip matrix may include:

  • Phase overcurrent
  • Earth fault
  • Directional protection
  • External trip
  • Breaker failure initiation
  • Lockout
  • Blocking
  • Remote trip
  • Interlocking conditions

The final logic must be documented and tested against the approved protection and control drawings.

17. GE Multilin 850 Configuration Workflow

The applicable engineering software depends on the exact relay model and firmware.

The following is a general engineering process.

Step 1 – Identify the Relay

Record:

  • Exact model
  • Order code
  • Serial number
  • Firmware version
  • Hardware options
  • CT and VT input configuration
  • Communication options

Step 2 – Retrieve Existing Settings

Connect through a supported communication interface.

Retrieve the existing settings where possible and save an original backup.

Step 3 – Configure CT and VT Inputs

Enter the correct ratios and input references.

Verify phase assignment, polarity and measurement scaling.

Step 4 – Configure Protection Elements

Apply the approved settings for the required protection functions.

These may include:

  • Phase overcurrent
  • Earth fault
  • Directional protection
  • Voltage protection
  • Frequency protection
  • Other application-specific functions

Step 5 – Configure Time-Current Curves

Select the required characteristic and time multiplier according to the approved coordination study.

Step 6 – Configure Logic and Outputs

Map protection operations to alarm and trip outputs.

Verify external blocking, permissive, breaker status and interlocking signals.

Step 7 – Configure Communication

Where required, configure:

  • Network interface
  • Protocol
  • IP address
  • Communication parameters
  • SCADA point mapping
  • Time synchronization
  • IEC 61850 services, where supported

Step 8 – Validate and Save

Compare the final configuration with the approved settings schedule and project drawings.

Save the final settings file with a clear revision identifier.

18. IEC 61850 and Substation Automation

IEC 61850 provides a standardized approach to communication and data modelling in substation automation systems.

Where supported by the installed GE Multilin 850 configuration, IEC 61850 can support communication between the relay and other substation devices.

18.1 MMS Communication

Manufacturing Message Specification (MMS) is commonly used for client-server communication.

Typical information includes:

  • Measurements
  • Protection status
  • Breaker status
  • Alarms
  • Events
  • Reports
  • Control operations

The actual supported services depend on the relay implementation.

18.2 GOOSE Communication

Generic Object Oriented Substation Event (GOOSE) communication provides fast event-based data exchange between compatible IEDs.

Potential applications include:

  • Interlocking
  • Blocking
  • Trip transfer
  • Permissive signals
  • Breaker status exchange

GOOSE engineering requires correct configuration of:

  • Publisher and subscriber
  • Dataset
  • GOOSE control block
  • APPID
  • VLAN ID
  • Multicast MAC address
  • Network settings

18.3 SCL Files

IEC 61850 engineering may use:

  • ICD
  • CID
  • IID
  • SCD

The engineering process depends on the manufacturer’s tools and the project’s system configuration workflow.

Do not assume that all IEC 61850 services are supported in every relay version. Verify the conformance information for the exact installed product.

18.4 Testing IEC 61850

Useful engineering tools include IEDScout and Wireshark.

They can help engineers inspect:

  • Device communication
  • Data attributes
  • Reports
  • GOOSE messages
  • Dataset mapping
  • Network traffic
  • Communication errors

Use these tools in accordance with site cybersecurity and network-access procedures.

19. Testing and Commissioning of the GE Multilin 850

A complete commissioning process should verify the protection functions, measurement circuits, logic, outputs and communication.

19.1 Initial Inspection

Check:

  • Relay identity
  • Auxiliary supply
  • CT wiring
  • VT wiring
  • Binary inputs
  • Binary outputs
  • Communication connections
  • Earthing
  • Approved settings

19.2 Current Measurement Test

Inject balanced three-phase currents.

Verify:

  • Phase A measurement
  • Phase B measurement
  • Phase C measurement
  • Current scaling
  • Phase sequence
  • Residual current

19.3 Voltage Measurement Test

Where voltage inputs are used, inject the appropriate voltage quantities.

Verify:

  • Phase-to-phase voltage
  • Phase-to-neutral voltage, where applicable
  • Phase sequence
  • Phase angles
  • Frequency measurement

19.4 Overcurrent Protection Testing

Test ANSI 50 and 51 elements.

Verify:

  • Pickup current
  • Operating time
  • Characteristic curve
  • Reset behaviour
  • Trip logic
  • Alarm indication
  • Event recording

19.5 Earth-Fault Protection Testing

Test the actual residual or dedicated ground-current measurement arrangement.

Verify:

  • Pickup
  • Operating time
  • Reset
  • Alarm and trip outputs
  • Measurement scaling

19.6 Directional Protection Testing

Where directional protection is installed, test forward and reverse operating conditions.

Verify the current-voltage phase relationship and the selected directional characteristic.

19.7 Breaker Failure Testing

Where 50BF is implemented, test:

  • Initiation
  • Current supervision
  • Timer
  • Retrip
  • Backup trip
  • Breaker status supervision

19.8 Autoreclosing Testing

Where ANSI 79 is implemented, test:

  • Initiation
  • Dead time
  • Reclose command
  • Breaker-ready supervision
  • Reclose blocking
  • Reclaim time
  • Shot counter
  • Lockout

19.9 Binary I/O Testing

Verify all configured inputs and outputs.

Check the physical wiring and logic response against the approved drawings.

19.10 Communication Testing

Verify SCADA and IEC 61850 communication, where applicable.

Test:

  • Measurements
  • Status indications
  • Events
  • Reports
  • GOOSE signals
  • Control operations
  • Time synchronization
  • Communication-loss alarms

19.11 Complete Trip Circuit Test

Confirm the complete physical trip path:

  1. Protection element operation.
  2. Relay trip logic.
  3. Output contact operation.
  4. Interposing relay, where installed.
  5. Breaker trip coil energization.
  6. Breaker opening.
  7. Auxiliary contact change.
  8. Alarm and event recording.

All tests must follow approved isolation, switching and electrical safety procedures.

20. Common GE Multilin 850 Troubleshooting Problems

ProblemPossible causeRecommended engineering check
Incorrect current measurementCT ratio or wiring errorVerify CT ratio, polarity and phase assignment
Unwanted overcurrent tripIncorrect pickup or coordinationReview load current and fault study
Earth-fault alarmResidual current or wiring issueInspect CT circuits and neutral earthing
Directional operation incorrectCT/VT polarity or reference errorVerify phase sequence and directional reference
Incorrect operating timeWrong curve or time multiplierCompare settings with coordination study
Breaker does not tripOutput mapping or trip circuit faultTrace the complete trip chain
Autoreclose unsuccessfulBlocking condition or breaker not readyReview sequence logic and breaker feedback
GOOSE signal missingDataset or network configurationVerify publisher, subscriber and VLAN
SCADA values incorrectScaling or point mapping issueCheck communication configuration
Communication unavailableInterface or network problemVerify physical connection and settings

Always investigate the actual cause before changing protection settings.

21. GE Multilin 850 Commissioning Checklist

Hardware and measurement

  • Correct relay model and order code
  • Firmware version recorded
  • Auxiliary supply verified
  • CT ratios checked
  • CT polarity checked
  • VT configuration checked, where applicable
  • Binary inputs and outputs verified

Protection functions

  • ANSI 50/51 tested
  • Earth-fault protection tested
  • Directional protection tested, where installed
  • Voltage protection tested, where installed
  • Frequency protection tested, where installed
  • Breaker failure logic tested, where implemented
  • Autoreclosing tested, where implemented

Logic and communication

  • Trip matrix verified
  • External blocking checked
  • Breaker status verified
  • SCADA point mapping checked
  • IEC 61850 MMS tested, where applicable
  • GOOSE tested, where applicable
  • Time synchronization verified

Documentation

  • Final settings saved
  • Original settings backed up
  • Test report completed
  • Drawings updated
  • Commissioning approval recorded

22. GE Multilin 850 Compared with Other Feeder Protection Relays

RelayGeneral application
GE Multilin 350Feeder protection
GE Multilin 850Advanced feeder protection
GE Multilin F650Feeder protection and bay control applications
GE Multilin UR familyApplication-specific protection platforms

The correct relay selection depends on:

  • Required protection functions
  • Number and type of measurement inputs
  • Binary I/O requirements
  • Communication protocols
  • IEC 61850 requirements
  • Control and interlocking requirements
  • Project specifications
  • Lifecycle support

A detailed comparison should use the actual order codes and manufacturer documentation.

23. Training on GE Multilin Feeder Protection Relays by Elec-Engg

Practical feeder protection engineering requires knowledge of network fault calculations, CT and VT configuration, protection settings, time-current coordination, communication and commissioning.

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for engineers working in power system protection, commissioning, operation, maintenance and substation automation.

Relevant training subjects include:

  • GE Multilin 350 and 850 feeder protection
  • GE Multilin F650 protection and control
  • ANSI 50/51 phase overcurrent protection
  • Earth-fault protection
  • Directional overcurrent protection
  • CT and VT configuration
  • Protection coordination
  • Breaker failure protection
  • Autoreclosing principles
  • EnerVista configuration
  • IEC 61850 MMS and GOOSE
  • IEDScout and Wireshark
  • Secondary injection testing
  • Troubleshooting and commissioning

Training delivery options include:

  • Pre-recorded video courses
  • Structured self-paced training
  • Live online training
  • Face-to-face technical training
  • Customized in-house training for companies and utilities

The training focuses on practical engineering applications, helping engineers understand how to configure, test and troubleshoot protection systems used in real industrial and utility installations.

Explore the training resources:

Elec-Engg website: https://elec-engg.com/

Contact and training enquiries: https://elec-engg.com/contact/

24. Conclusion

The GE Multilin 850 is a feeder protection relay platform intended for industrial and utility distribution applications.

Reliable application requires accurate CT and VT configuration, suitable protection settings and careful coordination with other protection devices.

The engineer must evaluate phase overcurrent, earth fault and directional protection requirements based on the network topology and neutral-earthing arrangement.

Additional functions such as voltage, frequency, breaker failure and autoreclosing should only be included after confirming their availability and suitability for the installed configuration.

Communication and IEC 61850 integration must be engineered and tested carefully, particularly when GOOSE signals are used for interlocking or protection-related functions.

Finally, commissioning should verify the complete protection chain, including measurements, logic, outputs, circuit-breaker operation and SCADA communication.

25. Frequently Asked Questions

1. What is the GE Multilin 850 used for?

The GE Multilin 850 is used in feeder protection applications in utility and industrial distribution systems. Its available functions depend on the exact configuration.

2. What is the difference between GE Multilin 350 and 850?

Both belong to the feeder protection family, but their available functions, hardware and application capabilities should be compared using the exact product documentation and order codes.

3. What is ANSI 50/51 protection?

ANSI 50 is instantaneous overcurrent protection, while ANSI 51 is time overcurrent protection.

4. When is ANSI 67 directional protection required?

Directional overcurrent protection is useful in ring networks, parallel feeders and multiple-source systems where fault-current direction is important for selectivity.

5. What is the purpose of earth-fault protection?

Earth-fault protection detects current associated with insulation failure or an unintended connection between a phase conductor and earth.

6. Does the GE Multilin 850 support IEC 61850?

The available IEC 61850 services depend on the installed relay version and communication options. Verify the exact supported services from the product documentation.

7. What is GOOSE used for?

GOOSE provides fast event-based communication between compatible IEDs. It can be used for applications such as interlocking, blocking and signal exchange.

8. How is the GE Multilin 850 tested?

Testing generally includes current and voltage measurement checks, protection pickup and timing, binary I/O, directional tests where applicable, communication tests and complete trip circuit verification.

9. What software is used to configure the GE Multilin 850?

Use the manufacturer engineering software compatible with the installed relay model and firmware. Confirm the correct software version and procedure in the applicable documentation.

10. Where can engineers receive GE Multilin feeder protection training?

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering). Visit https://elec-engg.com/ or contact https://elec-engg.com/contact/.


Complete GE Multilin 850 guide covering feeder protection, ANSI 50/51, earth fault, directional protection, autoreclosing, IEC 61850, configuration and commissioning.

GE Multilin 850, GE 850 Relay, GE Feeder Protection Relay, Feeder Protection, Advanced Feeder Protection, ANSI 50, ANSI 51, ANSI 50N, ANSI 51N, ANSI 67, Directional Overcurrent, Earth Fault Protection, CT Configuration, VT Configuration, Protection Coordination, Autoreclosing, Breaker Failure Protection, IEC 61850, MMS, GOOSE, EnerVista, Relay Testing, Power System Protection