GE Multilin GOOSE Communication: Publisher and Subscriber Configuration, Protection Interlocking, Blocking Schemes, Testing and Troubleshooting

Table Of Contents
  1. 1. Introduction
  2. 2. What Is GOOSE Communication?
  3. 3. GOOSE Publisher and Subscriber Architecture
  4. 4. GOOSE Communication Compared with MMS
  5. 5. GOOSE Data Model and Dataset Engineering
  6. 6. GOOSE Control Block
  7. 7. GOOSE Multicast MAC Address
  8. 8. GOOSE APPID, VLAN and Priority
  9. 9. GOOSE Retransmission and State Changes
  10. 10. Practical Application 1: Feeder-to-Feeder Protection Blocking
  11. 11. Practical Application 2: Busbar Trip Distribution
  12. 12. Practical Application 3: Breaker Failure Signal Exchange
  13. 13. GE Multilin GOOSE Configuration Workflow
  14. 14. SCL Engineering for GOOSE
  15. 15. GOOSE Testing with IEDScout
  16. 16. GOOSE Testing with Wireshark
  17. 17. GOOSE Communication Failure Supervision
  18. 18. GOOSE Redundancy and Network Architecture
  19. 19. GOOSE Commissioning and End-to-End Testing
  20. 20. GOOSE Test Matrix
  21. 21. Common GOOSE Engineering Mistakes
  22. 22. Practical GOOSE Commissioning Checklist
  23. 23. Training on GE Multilin GOOSE Communication by Elec-Engg
  24. 24. Conclusion
  25. 25. Frequently Asked Questions

1. Introduction

Generic Object-Oriented Substation Event (GOOSE) communication is one of the most important services in IEC 61850-based substation automation. It enables intelligent electronic devices (IEDs) to exchange event information over Ethernet without requiring a separate hardwired connection for every signal.

For protection engineers working with GE Multilin relays, GOOSE communication can support applications such as:

  • Protection blocking between feeder relays
  • Breaker failure initiation and coordination
  • Busbar protection trip distribution
  • Transformer and feeder interlocking
  • Transfer trip signals
  • Circuit-breaker status exchange
  • Trip permissive schemes
  • Alarm and protection status exchange

However, successful GOOSE engineering requires more than enabling IEC 61850 communication. Engineers must understand publisher and subscriber configuration, datasets, GOOSE control blocks, multicast addressing, VLANs, APPID, configuration revisions, communication supervision and application logic.

This article explains the practical engineering principles of GOOSE communication for GE Multilin protection relays, including configuration, system design, testing and troubleshooting.

Important: GOOSE functionality varies by GE Multilin relay model, firmware, hardware and IEC 61850 implementation. The examples in this article describe general engineering principles. Confirm the exact GOOSE publishing, subscription, dataset and logic capabilities of the installed relay before applying them to a project.

2. What Is GOOSE Communication?

GOOSE is an IEC 61850 communication service designed for fast exchange of event information between IEDs.

Unlike conventional client-server communication, GOOSE uses a publisher-subscriber model.

  • A publisher creates and transmits a GOOSE message.
  • One or more subscribers receive the message.
  • The subscriber processes the received information according to its configured logic.

GOOSE messages are transmitted using Ethernet multicast frames.

<AsyncImage query=”IEC 61850 GOOSE publisher subscriber communication architecture diagram with two protection relays and Ethernet switch” aspectRatio=”16:9″ width=”100%”/>

For example, a GE Multilin feeder relay detects a fault and publishes a protection-start signal. An upstream GE Multilin relay subscribes to this signal and uses it in a blocking or coordination scheme, if the required functions are supported.

2.1 Why Is GOOSE Used?

In a conventional substation, exchanging a protection signal between two relays may require:

  1. A binary output from the sending relay.
  2. A copper cable between panels.
  3. A binary input on the receiving relay.
  4. Input configuration and logic programming.

GOOSE can exchange the signal through the Ethernet network instead.

Potential advantages include:

  • Reduced inter-panel wiring
  • Flexible signal distribution
  • Easier integration of multiple IEDs
  • Standardized communication structures
  • Support for advanced protection and interlocking schemes
  • Improved access to communication diagnostics

GOOSE does not automatically replace all hardwired protection circuits. Critical trip circuits, safety-related circuits and project-specific functions may still require hardwired connections.

3. GOOSE Publisher and Subscriber Architecture

Understanding the publisher-subscriber architecture is fundamental to IEC 61850 engineering.

3.1 GOOSE Publisher

The publisher is the IED that transmits information.

For example, a GE Multilin feeder relay may publish:

  • Overcurrent protection start
  • Earth-fault protection operation
  • Circuit-breaker position
  • Breaker failure indication
  • Protection blocking status

The published information is selected through an IEC 61850 dataset associated with a GOOSE Control Block.

3.2 GOOSE Subscriber

The subscriber receives the published information.

For example, an upstream relay may subscribe to a downstream feeder’s protection-start signal.

The received information can be connected to an internal logic function, provided the relay supports the required subscription and application functionality.

3.3 One Publisher and Multiple Subscribers

A GOOSE publisher can distribute information to multiple subscribers.

For example, a busbar protection IED may publish a trip signal that is received by several feeder or transformer IEDs.

The engineering design must verify that every intended subscriber supports the required GOOSE configuration and that the Ethernet network distributes the multicast traffic correctly.

3.4 GOOSE Communication Is Not a Direct Trip Guarantee

Receiving a GOOSE frame does not automatically mean that the intended circuit breaker will trip.

The complete application includes:

  1. Correct publisher information.
  2. Correct dataset configuration.
  3. Correct GOOSE transmission.
  4. Correct subscriber mapping.
  5. Valid communication supervision.
  6. Correct internal logic.
  7. Correct output configuration.
  8. Correct circuit-breaker trip circuit.

Every stage must be tested.

4. GOOSE Communication Compared with MMS

GOOSE and MMS are both used in IEC 61850 systems, but they serve different communication purposes.

FeatureGOOSEMMS
Communication modelPublisher-subscriberClient-server
Main purposeEvent and status exchangeData access and reporting
TransportEthernet multicastCommonly TCP/IP
Typical applicationBlocking, interlocking, trip signalsSCADA measurements and status
Communication patternRepeated event messagesClient requests and server responses
Typical subscribers or clientsOther IEDsSCADA, gateway, engineering tools
Event handlingState-based retransmissionReports and data access services

A GE Multilin relay may support one or more IEC 61850 services depending on its implementation. Do not assume that GOOSE and MMS support are identical across all relay models.

5. GOOSE Data Model and Dataset Engineering

GOOSE communication depends on the IEC 61850 data model.

A GOOSE publisher does not simply transmit an arbitrary text signal. It publishes selected IEC 61850 data attributes through a configured dataset.

5.1 Logical Nodes

Logical nodes represent functions or information categories.

Examples relevant to protection and control include:

Logical nodeTypical information
PTOCTime overcurrent protection
PIOCInstantaneous overcurrent protection
PDIFDifferential protection
PDISDistance protection
PTRCProtection trip conditioning
XCBRCircuit-breaker information
XSWISwitch information
GGIOGeneric process input/output
RBRFBreaker failure protection

The actual nodes and data objects available depend on the specific relay.

5.2 Data Objects and Attributes

A logical node contains data objects, which in turn contain data attributes.

For example, protection information may include:

  • Start status
  • Operate status
  • Quality
  • Timestamp
  • Additional status or configuration information

The exact data reference must be taken from the actual IED data model.

5.3 What Is a Dataset?

A dataset is a collection of IEC 61850 data attributes.

For a feeder protection application, a dataset might contain:

  • Overcurrent start
  • Earth-fault start
  • Protection trip
  • Circuit-breaker position
  • Device health status

A dataset should contain only the information required for its intended application.

5.4 Dataset Engineering Recommendations

When creating a GOOSE dataset:

  1. Identify the required protection or control information.
  2. Locate the relevant logical node.
  3. Select the correct data object.
  4. Select the required data attribute.
  5. Include quality information where required.
  6. Confirm that the publisher supports the selected data.
  7. Confirm that subscribers can process the information.
  8. Verify the final dataset in the system configuration.

Avoid selecting large quantities of unnecessary information. A carefully designed dataset is easier to maintain and troubleshoot.

6. GOOSE Control Block

The GOOSE Control Block (GoCB) defines the publishing configuration associated with a dataset.

It contains information required to transmit GOOSE messages.

Typical parameters include:

  • GOOSE control block reference
  • Dataset reference
  • GOOSE identifier
  • Application identifier
  • Multicast destination address
  • VLAN configuration
  • Priority
  • Configuration revision
  • Minimum and maximum retransmission timing parameters, where applicable

The exact parameter availability and configuration method depend on the IED.

6.1 GOOSE Identifier

The GOOSE identifier is used to identify the GOOSE application or message.

It should be meaningful and managed consistently in the engineering project.

6.2 Dataset Reference

The dataset reference identifies the information being transmitted.

A mismatch between the publisher’s dataset and the subscriber’s expected data structure can result in incorrect or unsuccessful integration.

6.3 Configuration Revision

The configuration revision is important when a GOOSE publisher configuration changes.

When the dataset or GOOSE configuration is modified, the engineering team must ensure that subscribers have the corresponding updated configuration.

A configuration revision mismatch can result in communication or application problems.

7. GOOSE Multicast MAC Address

GOOSE uses Ethernet multicast communication.

The destination MAC address identifies the multicast group used by the GOOSE message.

The multicast address is part of the communication design and must be correctly configured in the system.

7.1 Why Is Multicast Used?

One publisher may need to transmit information to several subscribers.

Multicast allows the network to distribute a message to the intended group without requiring a separate unicast transmission for every subscriber.

7.2 Engineering Considerations

Check:

  • Correct multicast address
  • No unintended address duplication
  • Correct switch multicast handling
  • VLAN configuration
  • Subscriber connectivity
  • Network topology
  • Switch port configuration

Do not assume that a GOOSE message visible on one switch port will automatically be visible on every other port.

8. GOOSE APPID, VLAN and Priority

Three important communication parameters are APPID, VLAN ID and Ethernet priority.

8.1 APPID

APPID is the Application Identifier used to identify a GOOSE application within the Ethernet communication environment.

The publisher and subscriber engineering must be consistent with the intended APPID.

8.2 VLAN ID

A Virtual Local Area Network can be used to separate GOOSE traffic from other Ethernet traffic.

For example, an engineering project may define separate VLANs for:

  • GOOSE protection communication
  • Station-level MMS communication
  • Engineering access
  • Other operational network services

The actual VLAN architecture should follow the project network design.

8.3 Ethernet Priority

Ethernet priority can help give time-critical traffic preferential treatment.

It must be coordinated with the switch configuration and overall network engineering.

8.4 Common Configuration Mistakes

Typical mistakes include:

  • Different VLAN IDs on publisher and subscriber paths
  • Incorrect APPID
  • Incorrect multicast address
  • Switch ports assigned to the wrong VLAN
  • Inconsistent priority configuration
  • Multicast filtering blocking the message

These problems can make a correctly configured GOOSE publisher appear unavailable to a subscriber.

9. GOOSE Retransmission and State Changes

GOOSE messages are transmitted repeatedly to improve communication reliability.

When an event occurs, the publisher sends a message indicating the new state. It then retransmits the message according to its configured retransmission strategy.

The retransmission interval generally increases after a state change until the steady-state transmission interval is reached.

When another state change occurs, the transmission process accelerates again.

9.1 State Number

The state number identifies a change in the published GOOSE state.

It is useful when examining whether a new event has been transmitted.

9.2 Sequence Number

The sequence number is associated with the transmission sequence for a particular state.

It helps identify repeated transmissions and changes in the message sequence.

9.3 Why Retransmission Matters

Repeated transmission helps subscribers receive the latest state even if an individual Ethernet frame is lost.

However, retransmission does not eliminate the need for network supervision and communication-failure handling.

9.4 Timing Considerations

GOOSE performance depends on:

  • Publisher processing
  • Network switch performance
  • Network topology
  • Ethernet traffic
  • Subscriber processing
  • Application logic
  • Configuration of the communication services

For protection applications, verify the required end-to-end performance through appropriate testing. Do not assume a universal GOOSE operating time for every GE Multilin relay or network.

10. Practical Application 1: Feeder-to-Feeder Protection Blocking

Consider an 11 kV distribution system with two feeder relays.

The downstream feeder is protected by a GE Multilin relay. An upstream relay provides backup protection.

The objective is to use GOOSE communication to exchange a blocking signal.

10.1 System Operation

Under normal conditions:

  • Both feeders operate normally.
  • No blocking signal is active.
  • The upstream protection remains available as backup.

When a downstream fault occurs:

  1. The downstream relay detects the fault.
  2. The downstream relay publishes the required protection-start or blocking information.
  3. The upstream relay receives the GOOSE message.
  4. The upstream relay applies the configured blocking logic.
  5. The downstream relay trips its circuit breaker.
  6. The upstream relay remains restrained for the coordinated fault, provided all scheme conditions are satisfied.

10.2 Illustrative Logic

A simplified conceptual expression is:

[
Trip_{upstream}=OC_{upstream}\land \neg Blocking
]

Where:

  • (OC_{upstream}) is the upstream overcurrent operating condition.
  • (Blocking) is the valid received blocking signal.

This is a conceptual equation, not a universal GE Multilin logic implementation.

10.3 Important Engineering Considerations

The engineer must define:

  • Which protection element initiates the signal
  • Whether the signal represents start or operation
  • Blocking duration
  • Communication supervision
  • Behaviour during communication loss
  • Backup trip timing
  • Reset conditions
  • Fail-safe or fail-secure philosophy

The scheme must be tested for both normal communication and communication failure.

11. Practical Application 2: Busbar Trip Distribution

A busbar protection scheme may need to trip multiple circuit breakers.

In a conventional system, separate hardwired trip outputs and wiring may be used.

Where supported and approved by the protection design, GOOSE can distribute selected trip information to several IEDs.

11.1 Illustrative Architecture

A busbar protection IED publishes a trip indication.

The intended feeder and transformer IEDs subscribe to the signal and process it through their configured trip logic.

11.2 Engineering Requirements

The design must verify:

  • Correct bus-zone selection
  • Correct breaker association
  • Correct GOOSE dataset
  • Correct subscriber mapping
  • Correct trip logic
  • Communication supervision
  • Breaker failure coordination
  • Redundancy requirements
  • End-to-end operating performance

11.3 Important Safety Consideration

GOOSE-based trip distribution must only be used where the complete protection architecture, IED capabilities, network design and applicable project requirements support it.

A critical protection scheme must not rely on an unverified communication path.

12. Practical Application 3: Breaker Failure Signal Exchange

Breaker failure protection (ANSI 50BF) may require information to be exchanged between protection devices.

For example, a relay may publish breaker failure initiation or status information for another IED.

A GOOSE-based scheme may be used where the relevant relay functions and system design support it.

12.1 Typical Sequence

  1. A protection relay issues a trip command.
  2. The circuit breaker receives the trip command.
  3. Breaker auxiliary contacts and current supervision are monitored.
  4. If breaker failure is detected, the required signal is published.
  5. Other IEDs receive the information.
  6. The configured backup trip logic operates.

12.2 Engineering Checks

Verify:

  • Breaker failure initiation
  • Current supervision
  • Breaker auxiliary contacts
  • Breaker failure timer
  • GOOSE publisher logic
  • Subscriber logic
  • Backup trip matrix
  • Communication-loss response

The GOOSE signal must not replace the required local breaker failure detection unless the approved design explicitly provides for it.

13. GE Multilin GOOSE Configuration Workflow

The exact engineering software and configuration procedure depend on the GE Multilin relay family and firmware.

The following is a generic IEC 61850 engineering workflow.

Step 1 – Verify Relay Capability

Confirm:

  • Exact model
  • Hardware configuration
  • Firmware version
  • IEC 61850 edition
  • GOOSE publishing support
  • GOOSE subscription support
  • Supported datasets
  • Supported application logic

Step 2 – Obtain the Correct SCL File

Obtain the appropriate ICD or other applicable IED description file.

Check that it corresponds to the actual relay version.

Step 3 – Import the IED

Import the IED into the system configuration tool.

Review the available logical devices, logical nodes and data objects.

Step 4 – Define the Publisher Dataset

Select the data attributes required for the GOOSE application.

For example, select the relevant protection-start or breaker-status information.

Step 5 – Configure the GOOSE Control Block

Configure the required parameters, including:

  • GOOSE control block
  • Dataset reference
  • GOOSE identifier
  • APPID
  • Multicast destination
  • VLAN
  • Priority
  • Configuration revision

Use the actual parameter names and limits supported by the IED.

Step 6 – Configure Subscribers

Configure the receiving IEDs to subscribe to the required GOOSE information.

Map the received data to the appropriate internal logic.

Step 7 – Configure the Ethernet Switches

Check VLAN membership, multicast handling, priority and network topology.

Step 8 – Download Configuration

Transfer the configuration using the supported manufacturer procedure.

Verify that the configuration is accepted by the IED.

Step 9 – Verify Communication

Use suitable IEC 61850 tools and network analysis to confirm that messages are transmitted and received.

Step 10 – Test the Protection Application

Simulate the required signals and verify the complete protection or control response.

14. SCL Engineering for GOOSE

Substation Configuration Language is central to IEC 61850 system engineering.

GOOSE publisher and subscriber relationships are represented in the system configuration.

14.1 ICD File

The IED Capability Description file describes the IED’s supported data model and capabilities.

14.2 SCD File

The Substation Configuration Description file represents the system-level engineering configuration.

It can contain information about:

  • IEDs
  • Communication networks
  • GOOSE control blocks
  • Datasets
  • Subscriber relationships
  • Substation structure

14.3 CID File

The Configured IED Description file represents the configuration intended for an individual IED.

14.4 Engineering Process

A typical GOOSE engineering process is:

  1. Import the IED description files.
  2. Add the IEDs to the substation project.
  3. Define the required GOOSE datasets.
  4. Configure publisher control blocks.
  5. Define subscriber relationships.
  6. Configure network addressing.
  7. Generate the system configuration.
  8. Export the appropriate IED configuration.
  9. Load the configuration into the devices.
  10. Verify the resulting communication.

The final SCL files should be archived with the relay settings and commissioning records.

15. GOOSE Testing with IEDScout

IEDScout can be useful for inspecting IEC 61850 communication and IED data models.

Depending on the software version and available functionality, it can help engineers examine:

  • IED data models
  • Logical nodes
  • Data objects
  • Data attributes
  • Communication services
  • GOOSE-related information

15.1 Testing Procedure

  1. Connect the engineering computer to the substation Ethernet network.
  2. Configure the computer’s network interface.
  3. Verify network connectivity.
  4. Open IEDScout.
  5. Connect to the supported IEC 61850 server.
  6. Browse the data model.
  7. Inspect the required protection information.
  8. Check the configured GOOSE information using the available tools.
  9. Compare the observed information with the engineering configuration.

15.2 Important Limitation

IEDScout is an engineering and diagnostic tool, not a substitute for complete protection testing.

A visible GOOSE message does not prove that the subscriber’s internal logic or circuit-breaker trip circuit operates correctly.

16. GOOSE Testing with Wireshark

Wireshark is particularly useful for analysing GOOSE Ethernet frames.

It helps identify whether the publisher is transmitting the expected messages and whether the network is carrying them correctly.

<AsyncImage query=”Wireshark IEC 61850 GOOSE packet analysis Ethernet frame screenshot” aspectRatio=”16:9″ width=”100%”/>

16.1 Capture Preparation

Before starting a capture:

  1. Identify the publisher and subscriber IP or MAC addresses where applicable.
  2. Identify the relevant Ethernet switch ports.
  3. Configure a suitable mirror or monitoring port if necessary.
  4. Connect the engineering PC.
  5. Start the capture.
  6. Generate a controlled protection or test signal.

A capture point that does not receive the relevant multicast traffic may not show the messages.

16.2 GOOSE Packet Analysis

Inspect:

  • Ethernet source MAC address
  • Ethernet destination MAC address
  • VLAN information
  • APPID
  • GOOSE control block reference
  • Dataset reference
  • State number
  • Sequence number
  • Configuration revision
  • Test and simulation indicators, where applicable
  • Time-related information

16.3 What to Look For

When a protection signal changes state:

  • A new GOOSE state should be published.
  • The message should contain the expected information.
  • Retransmissions should follow the configured behaviour.
  • The subscriber should receive the relevant message.
  • The application logic should respond correctly.

16.4 Common GOOSE Packet Problems

ObservationPossible explanation
No GOOSE frames visiblePublisher disabled, incorrect capture point or network issue
Wrong destination MACIncorrect publisher configuration
Wrong VLANNetwork or publisher configuration mismatch
Unexpected APPIDIncorrect communication engineering
Dataset differs from designWrong or outdated SCL configuration
State does not changePublisher input or logic not operating
Subscriber reports invalid dataConfiguration or communication mismatch
Frames visible but no operationSubscriber mapping or application logic problem

17. GOOSE Communication Failure Supervision

Protection engineers must consider what happens when GOOSE communication is interrupted.

Potential causes include:

  • Ethernet cable failure
  • Switch failure
  • Publisher power failure
  • Subscriber communication failure
  • Incorrect VLAN configuration
  • Network congestion
  • Configuration mismatch
  • Firmware or configuration problems

17.1 Communication Supervision

A subscriber should be engineered to recognize invalid or stale communication according to the supported IEC 61850 implementation.

The system must define how the subscriber behaves when the expected GOOSE information is no longer valid.

17.2 Fail-Safe and Fail-Secure Design

The appropriate response depends on the protection application.

For example:

  • A blocking signal may require a carefully designed backup time delay if communication fails.
  • A trip signal may require a different failure response.
  • An interlocking application may need to prevent unsafe operation when status information is unavailable.

There is no universal failure response suitable for every GOOSE application.

17.3 Required Tests

Test at least:

  1. Normal GOOSE communication.
  2. Publisher power loss.
  3. Ethernet cable disconnection.
  4. Switch communication failure, where practical.
  5. Incorrect or invalid subscriber configuration.
  6. Communication restoration.
  7. Recovery of application logic.
  8. Alarm and event recording.

18. GOOSE Redundancy and Network Architecture

Protection communication networks should be designed according to the required availability and performance.

Possible network arrangements include:

  • Single Ethernet network
  • Redundant Ethernet networks
  • PRP
  • HSR

18.1 PRP

Parallel Redundancy Protocol provides two independent network paths.

Compatible devices can transmit duplicate frames over the two networks.

The receiving device accepts the first valid frame, allowing communication to continue during certain network failures.

18.2 HSR

High-availability Seamless Redundancy is a ring-based redundancy approach.

Frames are transmitted through the ring in both directions.

The devices and network components must support the required HSR architecture.

18.3 GE Multilin Compatibility

Do not assume every GE Multilin relay supports PRP or HSR.

Verify:

  • Relay communication hardware
  • Firmware
  • Supported redundancy protocol
  • Switch compatibility
  • System architecture
  • Required network performance

Redundancy must be tested as part of commissioning.

19. GOOSE Commissioning and End-to-End Testing

A successful GOOSE commissioning test must verify the complete signal path.

19.1 Publisher Testing

Verify:

  • Correct source signal
  • Correct dataset
  • Correct GOOSE control block
  • Correct APPID
  • Correct multicast address
  • Correct VLAN
  • Correct state change
  • Correct retransmission behaviour

19.2 Subscriber Testing

Verify:

  • Correct publisher reference
  • Correct dataset mapping
  • Correct data interpretation
  • Correct quality handling
  • Correct communication supervision
  • Correct internal logic
  • Correct output operation

19.3 End-to-End Testing

An end-to-end test should confirm:

  1. The source relay receives the test condition.
  2. The protection or control signal changes state.
  3. The publisher transmits the GOOSE message.
  4. The network delivers the message.
  5. The subscriber receives the information.
  6. The subscriber logic operates correctly.
  7. The intended output or control action occurs.
  8. The event records and timestamps are correct.

19.4 Testing Safety

Before testing any trip or blocking application:

  • Obtain the required work permit.
  • Review the approved test procedure.
  • Isolate unintended trip paths where necessary.
  • Confirm the protection system’s operational status.
  • Coordinate with the control room.
  • Restore all trip and blocking circuits after testing.
  • Independently verify the final system condition.

Never conduct uncontrolled GOOSE trip testing on an energized substation.

20. GOOSE Test Matrix

The following matrix provides an example of a commissioning test structure.

TestTest conditionExpected result
Publisher normal stateNo protection operationCorrect normal-state message
Publisher eventProtection signal activatedNew GOOSE state transmitted
Subscriber receptionValid message receivedCorrect data indication
Logic operationRequired input condition appliedIntended logic response
Trip outputApproved trip test conditionCorrect output response
Communication lossPublisher or network disconnectedDefined failure response
Communication recoveryNetwork restoredValid communication re-established
Configuration mismatchControlled mismatch testAppropriate supervision or failure indication
Event recordingSignal changes stateCorrect event and timestamp
RedundancyOne approved network path interruptedRequired communication continuity, where supported

21. Common GOOSE Engineering Mistakes

Mistake 1: Assuming All Relays Support GOOSE

IEC 61850 support does not automatically mean that every GOOSE service is supported.

Recommendation: Verify the exact relay implementation and firmware.

Mistake 2: Incorrect Dataset Selection

The publisher may transmit information that does not correspond to the subscriber’s expected application.

Recommendation: Review the dataset and its data references.

Mistake 3: Incorrect APPID or Multicast Address

The subscriber may not identify the intended GOOSE application.

Recommendation: Compare publisher and subscriber configuration with the approved SCL project.

Mistake 4: VLAN Mismatch

The message may be blocked or isolated by the Ethernet network.

Recommendation: Verify VLAN configuration at all relevant switch ports.

Mistake 5: Incorrect Subscriber Mapping

The GOOSE message may arrive, but the wrong internal signal may be used.

Recommendation: Perform point-to-point signal verification.

Mistake 6: Ignoring Communication Failure

A protection scheme may operate incorrectly if the GOOSE signal becomes unavailable.

Recommendation: Define and test the communication-failure response.

Mistake 7: Testing Only the Ethernet Message

A visible packet does not prove that the protection application works.

Recommendation: Complete end-to-end functional testing.

Mistake 8: Failing to Update Configuration Revisions

The publisher and subscriber may use inconsistent configuration information.

Recommendation: Manage SCL revisions and configuration downloads under a controlled procedure.

22. Practical GOOSE Commissioning Checklist

Relay verification

  • GE Multilin model confirmed
  • Firmware version recorded
  • IEC 61850 support confirmed
  • GOOSE publisher capability verified
  • GOOSE subscriber capability verified
  • Required data objects available

Publisher configuration

  • Dataset created
  • Required data attributes selected
  • GOOSE Control Block configured
  • GOOSE identifier checked
  • APPID checked
  • Multicast MAC checked
  • VLAN and priority checked
  • Configuration revision recorded

Subscriber configuration

  • Correct publisher identified
  • Dataset mapping verified
  • Data quality checked
  • Communication supervision configured
  • Internal logic verified
  • Output mapping verified

Network verification

  • Ethernet connectivity checked
  • Switch port configuration checked
  • VLAN configuration checked
  • Multicast handling checked
  • Network loading reviewed
  • Redundancy tested, where installed

Functional testing

  • Normal-state message verified
  • State-change message verified
  • Subscriber reception verified
  • Internal logic tested
  • Trip or blocking operation tested
  • Communication failure tested
  • Communication recovery tested
  • Event recording checked

Documentation

  • Final SCL files archived
  • GOOSE matrix updated
  • Relay configurations backed up
  • Network configuration archived
  • Test reports completed
  • As-built documentation updated

23. Training on GE Multilin GOOSE Communication by Elec-Engg

GOOSE communication is a practical engineering subject that requires an understanding of protection functions, IEC 61850 data modelling, Ethernet communication and system commissioning.

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for engineers working in power system protection, commissioning, operation, maintenance and substation automation.

Relevant training subjects include:

  • IEC 61850 fundamentals
  • GE Multilin IEC 61850 communication
  • GOOSE publisher and subscriber configuration
  • GOOSE datasets and control blocks
  • Logical nodes and data objects
  • APPID, multicast MAC and VLAN engineering
  • Protection blocking schemes
  • GOOSE-based interlocking
  • Breaker failure signal exchange
  • Busbar trip distribution
  • SCL file engineering
  • ICD, CID, IID and SCD files
  • Integration with Siemens SICAM PAS
  • IEDScout practical exercises
  • Wireshark GOOSE packet analysis
  • Communication failure supervision
  • GOOSE commissioning and end-to-end testing

Training delivery options include:

  • Pre-recorded video courses
  • Structured self-paced training
  • Live online technical training
  • Face-to-face training
  • Customized in-house training for utilities and industrial companies

The objective is to help engineers understand not only how GOOSE messages are configured, but also how they are applied in practical protection and substation automation schemes.

Visit Elec-Engg for technical training resources:

https://elec-engg.com

For customized training and technical enquiries:

https://elec-engg.com/contact

24. Conclusion

GOOSE communication is a key technology in IEC 61850-based substation automation. It enables protection and control IEDs to exchange event information over Ethernet and supports applications such as protection blocking, interlocking, breaker failure coordination and trip distribution.

For GE Multilin relays, successful GOOSE engineering requires verification of the exact relay capabilities, correct dataset and control-block configuration, subscriber mapping, multicast communication, VLAN settings and application logic.

The most important commissioning principle is to test the complete communication and protection chain. Engineers must verify the publisher, Ethernet network, subscriber, internal logic and final output response.

A properly engineered and tested GOOSE application can improve substation integration and reduce wiring complexity while maintaining the required protection performance and system reliability.

25. Frequently Asked Questions

1. What is GOOSE communication in GE Multilin relays?

GOOSE is an IEC 61850 communication service that allows supported GE Multilin relays to exchange event information with other IEDs over Ethernet.

2. What is the difference between a GOOSE publisher and subscriber?

The publisher transmits the configured information. The subscriber receives that information and uses it in its configured application logic.

3. Can GE Multilin relays exchange trip signals using GOOSE?

Some supported relay configurations can exchange protection-related information using GOOSE. Whether a particular trip application is supported depends on the relay model, firmware, communication capabilities and approved protection design.

4. What is a GOOSE dataset?

A dataset is a collection of IEC 61850 data attributes selected for transmission through a GOOSE Control Block.

5. What is a GOOSE Control Block?

A GOOSE Control Block defines the publishing configuration associated with a dataset, including relevant communication parameters.

6. What are APPID and VLAN in GOOSE communication?

APPID identifies the GOOSE application, while VLAN configuration helps organize and separate Ethernet traffic.

7. Why are GOOSE messages retransmitted?

Repeated transmission improves the probability that subscribers receive the latest published state, even if individual Ethernet frames are lost.

8. Can GOOSE replace all hardwired signals?

No. GOOSE can replace selected signal connections where the protection design and project requirements permit it. Some hardwired circuits remain necessary.

9. How can GOOSE communication be tested?

Use suitable IEC 61850 engineering tools, network packet analysis and end-to-end functional tests to verify publisher transmission, subscriber reception and application operation.

10. Can Wireshark analyse GOOSE messages?

Yes. Wireshark can capture and inspect GOOSE Ethernet frames, including communication parameters and published information.

11. What happens if GOOSE communication fails?

The response depends on the subscriber implementation and protection design. Communication failure supervision and the resulting protection behaviour must be explicitly engineered and tested.

12. Where can I receive practical GE Multilin GOOSE training?

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering). Visit https://elec-engg.com/ or contact https://elec-engg.com/contact/.


Learn GE Multilin GOOSE communication, including publisher and subscriber configuration, datasets, APPID, VLAN, protection blocking, SCL engineering and commissioning tests.

GE Multilin GOOSE, GE GOOSE Communication, IEC 61850 GOOSE, GOOSE Publisher, GOOSE Subscriber, GOOSE Control Block, GOOSE Dataset, GOOSE Configuration, GOOSE Testing, GOOSE Troubleshooting, GOOSE Interlocking, Protection Blocking, Breaker Failure Protection, Busbar Protection, APPID, VLAN, Multicast MAC Address, IEC 61850 SCL, GE Multilin Relay, Substation Automation, IEDScout, Wireshark, SICAM PAS, Protection Relay Communication, Relay Testing and Commissioning

Leave a Comment

Your email address will not be published. Required fields are marked *

Scroll to Top