Schneider Sepam Series 40 Protection Relays: Complete Guide to S40, S41, S42, M41, T40 and G40 Applications, Protection Functions, Settings and Testing
- 1. Introduction to Sepam Series 40
- 2. Sepam Series 40 Architecture
- 3. Sepam Series 40 Models and Applications
- 4. Sepam Series 40 Protection Functions
- 5. Feeder Protection Using Sepam S40/S41/S42
- 6. Motor Protection Using Sepam M41
- 7. Transformer Protection Using Sepam T40
- 8. Generator-Related Protection Applications
- 9. Sepam Series 40 Engineering Using SFT2841
- 10. Sepam Series 40 Settings Engineering
- 11. Sepam Series 40 Testing and Commissioning
- 12. Sepam Series 40 Troubleshooting
- 13. Practical Engineering Case Study — Industrial MV Feeder
- 14. Engineering Recommendations
- 15. Schneider Sepam Training by Elec-Engg
- 16. Conclusion
1. Introduction to Sepam Series 40
Schneider Electric Sepam Series 40 is a family of numerical protection relays designed for medium-voltage electrical distribution and industrial power system applications.
Compared with basic protection arrangements, Series 40 provides more advanced protection, measurement and monitoring capabilities for different electrical equipment.
Typical applications include:
- MV incoming and outgoing feeders.
- Industrial distribution networks.
- Power transformers.
- Induction motors.
- Generator-related applications.
- Electrical equipment requiring advanced protection functions.
Sepam Series 40 combines numerical protection algorithms, electrical measurements, programmable logic and communication capabilities according to the selected relay reference.
It is particularly relevant in industrial substations where reliable protection, equipment monitoring and integration with supervisory systems are required.
2. Sepam Series 40 Architecture
A typical Sepam Series 40 installation includes the following functional elements:
- Current transformer measurement inputs.
- Voltage transformer measurement inputs, where applicable.
- Numerical processing unit.
- Protection function algorithms.
- Binary input circuits.
- Binary output contacts.
- Local operator interface.
- Communication interfaces and optional modules.
- Auxiliary power supply.
- Engineering and configuration software.
The exact hardware arrangement depends on the relay reference and installed options.
3. Sepam Series 40 Models and Applications
Sepam Series 40 includes several references intended for different protection applications.
| Model | Typical application |
|---|---|
| Sepam S40 | Feeder protection |
| Sepam S41 | Advanced feeder protection |
| Sepam S42 | Feeder protection applications |
| Sepam M41 | Motor protection |
| Sepam T40 | Transformer protection |
| Sepam G40 | Generator-related protection applications |
Model-specific functions and availability must be verified against the original Schneider Electric technical documentation.
3.1 Sepam S40 — Feeder Protection
Sepam S40 is designed for medium-voltage feeder protection.
Typical applications include:
- Incoming feeder protection.
- Outgoing feeder protection.
- Industrial distribution systems.
- Radial network protection.
- Electrical distribution panels.
Depending on the reference and configuration, the protection scheme can include phase overcurrent, earth fault and other supported protection functions.
3.2 Sepam S41 — Advanced Feeder Protection
Sepam S41 is used in feeder applications requiring a more comprehensive protection arrangement.
Engineering considerations include:
- Phase overcurrent protection.
- Earth fault protection.
- Directional protection, where supported.
- Voltage supervision.
- Protection coordination.
- Communication and monitoring.
The engineer must verify the available functions for the exact product reference.
3.3 Sepam S42 — Feeder Protection Applications
Sepam S42 belongs to the feeder protection family.
It can be applied in suitable MV installations where the protection requirements match its capabilities.
Before selecting S42, check:
- Current measurement configuration.
- Voltage measurement requirements.
- Protection functions.
- Binary inputs and outputs.
- Communication interfaces.
- Firmware compatibility.
3.4 Sepam M41 — Motor Protection
Sepam M41 is intended for motor protection applications.
Typical applications include industrial induction motors, pumps, compressors, fans and other rotating equipment.
Important protection requirements include:
- Thermal overload.
- Phase overcurrent.
- Earth fault.
- Negative sequence.
- Starting supervision.
- Locked rotor protection.
- Undercurrent protection, where supported.
3.5 Sepam T40 — Transformer Protection
Sepam T40 is used in applicable transformer protection schemes.
Typical functions and requirements include:
- Phase overcurrent protection.
- Earth fault protection.
- Thermal supervision.
- Transformer backup protection.
- External alarm and trip integration.
The actual protection arrangement must be selected according to transformer rating, grounding method and fault study.
3.6 Sepam G40 — Generator Applications
Generator-related applications require special consideration of operating conditions and machine protection requirements.
Potential protection requirements include:
- Overcurrent protection.
- Earth fault protection.
- Negative sequence protection.
- Voltage supervision.
- Frequency supervision.
- Reverse power protection, where supported.
Do not assume that every generator protection function is available on every G40 configuration. Verify the actual protection function list before designing the scheme.
4. Sepam Series 40 Protection Functions
The following table summarizes important protection functions encountered in Series 40 engineering.
| ANSI code | Function | Engineering application |
|---|---|---|
| 50 | Instantaneous overcurrent | Short-circuit protection |
| 51 | Time overcurrent | Feeder protection |
| 50N/51N | Earth fault | Ground fault protection |
| 67 | Directional overcurrent | Network direction discrimination |
| 67N | Directional earth fault | Directional ground fault |
| 46 | Negative sequence | Current unbalance |
| 49 | Thermal overload | Motor and equipment protection |
| 27 | Undervoltage | Voltage supervision |
| 59 | Overvoltage | Voltage supervision |
| 81 | Frequency | Frequency supervision |
| 32 | Directional power | Applicable generator schemes |
| 37 | Undercurrent | Motor/load supervision |
| 48 | Incomplete starting | Motor protection |
The availability of individual functions depends on the selected Sepam reference and configuration.
5. Feeder Protection Using Sepam S40/S41/S42
Feeder protection is one of the most common applications of Sepam Series 40.
A typical MV feeder arrangement consists of:
- Current transformers.
- Voltage transformers, if required.
- Sepam protection relay.
- Vacuum circuit breaker.
- Trip and close circuits.
- Auxiliary DC supply.
- Communication interface.
5.1 Phase Overcurrent Protection
Phase overcurrent protection detects abnormal current levels.
Two principal operating functions are used:
ANSI 50 — Instantaneous Overcurrent
Operates when the measured current exceeds a configured threshold, subject to the function’s characteristics.
ANSI 51 — Time Overcurrent
Operates according to a configured time-current characteristic.
Typical characteristics include:
- Definite time.
- Standard inverse.
- Very inverse.
- Extremely inverse.
5.2 Directional Overcurrent Protection
Directional protection is particularly useful in interconnected electrical networks.
The relay evaluates current and an appropriate voltage reference to determine the direction of the fault.
Typical applications include:
- Parallel feeders.
- Ring distribution networks.
- Networks with multiple sources.
- Industrial networks with distributed generation.
5.3 Earth Fault Protection
Earth fault protection detects ground faults using the supported current measurement arrangement.
The engineer must consider:
- System grounding method.
- Residual current measurement.
- Core-balance CT requirements.
- Minimum fault current.
- Pickup sensitivity.
- Protection coordination.
6. Motor Protection Using Sepam M41
Motor protection requires coordination between electrical protection functions and the motor’s thermal limits.
6.1 Motor Thermal Overload Protection (49)
Thermal overload protection estimates the motor’s heating condition.
Important engineering parameters include:
- Rated motor current.
- Starting current.
- Starting duration.
- Thermal time constant.
- Permissible locked-rotor time.
- Cooling conditions.
- Restart limitations.
6.2 Locked Rotor and Starting Supervision
Abnormal motor starting can result in excessive heating.
The protection engineer should evaluate:
- Starting current.
- Acceleration time.
- Motor thermal withstand.
- Starting frequency.
- Stall conditions.
6.3 Negative Sequence Protection (46)
Negative sequence current is associated with unbalanced three-phase current conditions.
It can produce additional heating in motor windings and should be considered in motor protection engineering.
6.4 Earth Fault Protection
Earth fault protection helps identify insulation failures and ground fault conditions.
Its settings must account for the grounding arrangement and measurement method.
7. Transformer Protection Using Sepam T40
Transformer protection must address electrical faults, overload conditions and abnormal operating conditions.
Typical transformer protection requirements include:
- Phase overcurrent.
- Earth fault.
- Thermal overload.
- Backup protection.
- External Buchholz alarm/trip integration.
- External transformer temperature alarms.
7.1 Transformer CT Selection
Consider a transformer with:
- Rated power: 5 MVA.
- Primary voltage: 11 kV.
- CT ratio: 300/1 A.
The transformer primary rated current is:
\[ I=\frac{S}{\sqrt{3}\times V} \]
\[ I=\frac{5000}{\sqrt{3}\times11} \]
\[ I\approx262.4A \]
The CT secondary current at rated load is:
\[ I_s=\frac{262.4}{300} \]
\[ I_s\approx0.875A \]
This calculation provides a reference for configuring the relay’s current measurement. Final settings require a complete protection study.
8. Generator-Related Protection Applications
Generator protection requires careful consideration of the machine operating characteristics and network configuration.
Potential protection requirements include:
| ANSI | Protection function |
|---|---|
| 32 | Reverse power |
| 40 | Loss of excitation |
| 46 | Negative sequence |
| 27 | Undervoltage |
| 59 | Overvoltage |
| 81 | Frequency |
| 50/51 | Overcurrent |
| 50N/51N | Earth fault |
| 49 | Thermal protection |
The selected relay must be checked against the complete generator protection philosophy. Dedicated generator protection relays may be required for comprehensive schemes.
9. Sepam Series 40 Engineering Using SFT2841
SFT2841 is the engineering software historically associated with supported Sepam devices.
Typical engineering tasks include:
- Relay identification.
- Device selection.
- Configuration creation.
- CT and VT parameter entry.
- Protection function configuration.
- Protection setting entry.
- Binary input assignment.
- Binary output assignment.
- Communication configuration.
- Configuration validation.
- Reading and downloading supported settings.
- Event and diagnostic retrieval.
9.1 Online and Offline Engineering
Offline engineering allows preparation and review of the relay configuration without an active relay connection.
Online engineering allows communication with the installed relay for supported operations such as monitoring, configuration retrieval and parameter management.
Always verify software compatibility before connecting to an installed relay.
9.2 Configuration Backup
Before making any modifications:
- Retrieve the existing configuration.
- Save a backup.
- Record the original settings.
- Compare approved settings with existing values.
- Document all changes.
- Obtain the required operational authorization.
10. Sepam Series 40 Settings Engineering
Correct settings are essential for protection reliability.
The engineer should consider:
- Maximum operating load.
- Minimum and maximum fault current.
- CT characteristics.
- Equipment thermal limits.
- Circuit breaker operating time.
- Upstream/downstream coordination.
- Network grounding.
- Protection selectivity.
10.1 Overcurrent Coordination
A typical protection coordination study includes:
- Calculation of maximum load current.
- Calculation of minimum fault current.
- Calculation of maximum fault current.
- CT ratio verification.
- Selection of pickup current.
- Selection of operating curve.
- Time grading.
- Verification of circuit breaker clearing time.
10.2 Earth Fault Settings
Earth fault settings depend on the network grounding arrangement.
For example:
- Solidly grounded systems.
- Resistance-grounded systems.
- Isolated neutral systems.
- Compensated networks.
The protection engineer must select a measurement method and pickup threshold suitable for the actual system.
11. Sepam Series 40 Testing and Commissioning
Commissioning must verify both the relay’s protection functions and the complete electrical protection chain.
11.1 Secondary Injection Testing
Typical tests include:
| Test | Objective |
|---|---|
| Current measurement | Verify CT input measurement |
| Overcurrent pickup | Verify pickup accuracy |
| Operating time | Verify timing characteristics |
| Earth fault | Verify ground fault protection |
| Directional protection | Verify operating direction, where supported |
| Thermal protection | Verify applicable thermal characteristics |
| Binary inputs | Verify external status signals |
| Binary outputs | Verify relay output operation |
| Trip circuit | Verify complete trip chain |
11.2 Practical Omicron Testing
A suitable Omicron CMC test system can be used for protection function verification.
The testing engineer should prepare test cases based on the approved relay settings.
Testing may include:
- Pickup tests.
- Drop-off tests.
- Definite-time tests.
- Inverse-time tests.
- Directional characteristic tests.
- Binary logic tests.
- Trip timing tests.
11.3 Final Commissioning
The final commissioning procedure should include:
- Visual inspection.
- CT and VT circuit checks.
- Auxiliary supply verification.
- Relay configuration verification.
- Protection function testing.
- Binary input/output testing.
- Circuit breaker trip testing.
- SCADA communication testing.
- Event record verification.
- Final documentation.
12. Sepam Series 40 Troubleshooting
| Problem | Possible cause | Investigation |
|---|---|---|
| Incorrect current measurement | CT wiring or configuration | Check CT connections and ratios |
| Incorrect voltage measurement | VT wiring or settings | Verify phase connections |
| Unexpected trip | Protection setting or external signal | Review event records |
| Directional element malfunction | Incorrect polarity or voltage reference | Verify CT/VT circuits |
| Motor thermal alarm | Actual overload or incorrect parameters | Review motor loading and settings |
| Communication failure | Interface or parameter mismatch | Check communication configuration |
| Binary input problem | Wiring or configuration error | Verify input circuit |
| Trip output failure | Output logic or external circuit | Check output assignment and trip wiring |
13. Practical Engineering Case Study — Industrial MV Feeder
Consider an industrial 11 kV feeder supplying a 4 MVA distribution transformer.
System parameters
| Parameter | Value |
|---|---|
| System voltage | 11 kV |
| Transformer rating | 4 MVA |
| Primary rated current | 209.9 A |
| CT ratio | 250/1 A |
| Relay family | Sepam Series 40 |
| Main protection | Overcurrent and earth fault |
Transformer primary current:
\[ I=\frac{4000}{\sqrt{3}\times11} \]
\[ I\approx209.9A \]
CT secondary current at rated load:
\[ I_s=\frac{209.9}{250} \]
\[ I_s\approx0.84A \]
This gives the expected secondary current at rated transformer loading.
The protection engineer must complete the fault study and coordination calculations before selecting final relay settings.
14. Engineering Recommendations
When working with Sepam Series 40:
- Verify the complete relay reference.
- Check model-specific protection functions.
- Confirm CT and VT wiring.
- Use compatible SFT2841 software.
- Back up existing settings.
- Review protection coordination.
- Test protection functions using secondary injection.
- Verify binary input and output assignments.
- Check the complete trip circuit.
- Verify communication and SCADA signals.
- Follow applicable Schneider Electric documentation.
15. Schneider Sepam Training by Elec-Engg
Practical Power System Protection & Relay Engineering Training
Elec-Engg provides technical training for engineers working in protection, control, commissioning, maintenance and substation automation.
Relevant training subjects include:
- Sepam Series 20, 40, 60 and 80.
- SFT2841 software engineering.
- Feeder protection.
- Transformer protection.
- Motor protection.
- Generator protection fundamentals.
- Protection settings and coordination.
- CT and VT engineering.
- Omicron CMC testing.
- Secondary injection testing.
- Relay troubleshooting.
- SCADA and IEC 61850 integration.
Practical courses by Dr Saeed Roostaee / Elec-Engg
Our approach focuses on practical engineering applications, protection system analysis and real commissioning requirements.
Explore:
- Elec-Engg Training Platform
- Available Training Courses
- Substation Automation Training
16. Conclusion
Schneider Sepam Series 40 provides protection and monitoring capabilities for different medium-voltage electrical applications.
Understanding the differences between feeder, motor, transformer and generator-related relay references is essential for correct relay selection and engineering.
Practical knowledge of SFT2841, protection settings, CT/VT circuits, coordination, secondary injection testing and commissioning helps engineers maintain reliable electrical protection systems.