Schneider Sepam Series 80

Schneider Sepam Series 80 Protection Relays: Complete Engineering Guide to Feeder, Line, Motor, Transformer, Generator and Busbar Protection, Advanced Logic, Settings and Configuration

Table Of Contents
  1. 1. Introduction to Schneider Sepam Series 80
  2. 2. Sepam Series 80 Architecture and Hardware
  3. 3. Sepam Series 80 Model Selection and Applications
  4. 4. Sepam S80 — Feeder and Incomer Protection
  5. 5. Sepam S81 and S82 — Line Protection Applications
  6. 6. Sepam S84 — Advanced Feeder and Substation Protection
  7. 7. Sepam M87 — Motor Protection
  8. 8. Sepam T81 and T82 — Transformer Protection
  9. 9. Sepam T87 — Transformer Differential Protection
  10. 10. Sepam G82 — Generator Protection
  11. 11. Sepam G87 — Generator Differential Protection
  12. 12. Sepam B83 — Busbar Protection
  13. 13. Sepam Series 80 Advanced Logic and Control
  14. 14. Sepam Series 80 Settings and Configuration
  15. 15. Sepam Series 80 Testing and Commissioning
  16. 16. Common Engineering Problems and Troubleshooting
  17. 17. Sepam Series 80 Compared with Other Sepam Families
  18. 18. Practical Engineering Case Studies
  19. 19. Engineering Best Practices for Sepam Series 80
  20. 20. Conclusion
  21. 21. Schneider Electric Documentation and Further Reading
  22. 22. Sepam Series 80 Article Series

1. Introduction to Schneider Sepam Series 80

The Schneider Electric Sepam Series 80 is a family of advanced numerical protection relays designed for medium-voltage electrical distribution systems, industrial power networks, substations, and electrical installations requiring comprehensive protection, monitoring, control, and automation.

Sepam 80 relays provide extensive protection functions, measurement capabilities, programmable logic, disturbance recording, communication facilities, and circuit-breaker control. They are designed for applications where conventional overcurrent protection alone is insufficient and more advanced protection schemes are required.

The Sepam 80 family covers several important electrical applications, including:

  • Feeder and incomer protection.
  • Overhead line and cable protection.
  • Motor protection.
  • Transformer protection.
  • Transformer differential protection.
  • Generator protection.
  • Generator differential protection.
  • Busbar protection.
  • Advanced protection and control automation.

The Sepam 80 family is particularly relevant to protection engineers, electrical commissioning engineers, substation automation specialists, and maintenance personnel working with medium-voltage switchgear.

This engineering guide explains the Sepam Series 80 architecture, individual relay applications, protection functions, engineering configuration, programmable logic, and practical commissioning considerations.

2. Sepam Series 80 Architecture and Hardware

Sepam Series 80 is based on a modular numerical protection architecture. Depending on the selected model and ordered configuration, the relay can include analogue measurement inputs, digital inputs and outputs, communication interfaces, temperature measurement modules, and programmable logic capabilities.

2.1 Main Hardware Components

The principal hardware components include:

  1. Base unit: Performs protection calculations, measurements, logic processing, and communication.
  2. Current input circuits: Receive phase and residual current signals from CTs.
  3. Voltage input circuits: Receive voltage signals from VTs or voltage transformers.
  4. Digital input modules: Receive circuit-breaker status, isolator position, protection interlocks, and external signals.
  5. Digital output modules: Operate circuit-breaker trip and close circuits, alarms, and control functions.
  6. Temperature measurement modules: Support RTD temperature monitoring for motors, transformers, and other equipment.
  7. Communication interfaces: Provide connectivity to substation automation and supervisory systems.
  8. Memory cartridge: Stores application information, parameters, and settings to facilitate replacement and restoration.
  9. Operator interface (UMI): Provides local measurements, protection status, alarms, and control operations.

The published Series 80 architecture supports configurations with up to 12 analogue inputs, 42 logic inputs, 23 relay outputs, two Modbus communication ports, and 16 temperature sensor inputs, depending on the selected configuration. Schneider Electric Ireland+1

2.2 Operator Machine Interface (UMI)

Sepam Series 80 offers different operator interface arrangements.

The operator interface is used for:

  • Reading phase currents and voltages.
  • Checking frequency and power measurements.
  • Viewing active protection functions.
  • Reviewing alarms and trip indications.
  • Reading fault and disturbance records.
  • Accessing protection settings.
  • Operating circuit breakers where configured.
  • Checking relay health and diagnostic information.

A remote advanced UMI can also be installed where the relay itself is mounted inside a switchgear compartment and operators require access from the front of the panel.

2.3 Analogue Measurement Inputs

Correct analogue input configuration is fundamental to protection performance.

Typical measurements include:

MeasurementSourceApplication
Phase currentsCTsOvercurrent and differential protection
Residual currentResidual CT arrangementEarth-fault protection
Phase voltagesVTsVoltage and frequency protection
Residual voltageVT residual connectionEarth-fault detection
TemperatureRTD sensorsMotor and transformer thermal monitoring

The selected input arrangement must be compatible with the relay model, CT secondary rating, VT secondary voltage, and application configuration.

2.4 Communication Architecture

Sepam Series 80 supports communication with supervisory and substation automation systems.

Typical applications include:

  • SCADA measurement acquisition.
  • Remote reading of protection settings.
  • Alarm and event reporting.
  • Circuit-breaker status monitoring.
  • Remote control, where configured.
  • Disturbance record retrieval.
  • Engineering and maintenance access.

Communication options depend on the ordered hardware and firmware. Modbus is part of the Series 80 communication architecture, while certain configurations support IEC 61850 and GOOSE.

Engineers must distinguish between the communication capabilities of a particular relay configuration and those of the Series 80 family as a whole.

3. Sepam Series 80 Model Selection and Applications

Sepam Series 80 contains dedicated relay models for different protection applications.

The following table summarizes the models covered in this engineering guide.

Relay modelMain application
S80Substation incomer and feeder protection
S81Feeder and line protection with directional earth-fault applications
S82Feeder and line protection with directional overcurrent applications
S84Advanced substation protection
M87Motor differential and advanced motor protection
T81Transformer protection
T82Transformer protection with advanced directional functions
T87Transformer differential protection
G82Generator protection
G87Generator differential protection
B83Busbar protection and busbar voltage supervision

Important model-selection note: The Sepam 80 catalogue includes other models, including M81, M88, G88, B80, and C86. They are not covered individually in this particular series. The exact protection functions depend on the selected model and configuration. Schneider Electric Ireland+1

4. Sepam S80 — Feeder and Incomer Protection

4.1 Application Overview

Sepam S80 is designed for substation incomers and outgoing feeder applications.

It can be used in:

  • Medium-voltage distribution substations.
  • Industrial power distribution systems.
  • Utility distribution networks.
  • Transformer secondary incomers.
  • Feeder circuit-breaker protection.
  • Industrial switchgear.

Its principal purpose is to detect abnormal electrical conditions and initiate circuit-breaker tripping according to the configured protection scheme.

4.2 Main Protection Functions

Depending on the configuration, the protection scheme may include:

ANSIProtection function
50/51Instantaneous and time-delayed phase overcurrent
50N/51NEarth-fault overcurrent
50G/51GGround overcurrent
27Undervoltage
59Overvoltage
46Negative-sequence overcurrent
49Thermal overload
50BFCircuit-breaker failure
79Automatic reclosing, where supported and configured
86Lockout logic, where implemented
67NDirectional earth-fault protection, according to model

The actual available functions must be verified against the model-specific protection function table.

4.3 Phase Overcurrent Protection

Phase overcurrent protection is one of the most important functions in feeder protection.

The relay measures the three phase currents and compares them against configured pickup thresholds.

Two main operating characteristics are commonly used:

Definite-time overcurrent

The relay operates after a fixed time delay when the measured current exceeds the pickup setting.

Inverse-time overcurrent

The operating time decreases as the fault current increases.

Common inverse-time characteristics include:

  • Standard inverse.
  • Very inverse.
  • Extremely inverse.
  • Long-time inverse.

The selection depends on the network fault level, downstream protection, upstream protection, and coordination requirements.

4.4 Earth-Fault Protection

Earth-fault protection detects current flowing through an unintended earth-return path.

The residual current can be calculated from the three phase currents:

\[ I_0=\frac{I_A+I_B+I_C}{3} \]

The residual current is:

\[ I_N=3I_0 \]

Earth-fault protection can use:

  • Residual current derived from phase CTs.
  • A dedicated core-balance CT.
  • A suitable neutral CT arrangement.

The CT arrangement must be selected according to the network earthing system and the required sensitivity.

4.5 Practical S80 Engineering Considerations

When engineering an S80 feeder relay, the protection engineer should:

  1. Determine the maximum continuous feeder current.
  2. Calculate the minimum and maximum short-circuit currents.
  3. Select suitable CT ratios.
  4. Determine phase overcurrent pickup settings.
  5. Calculate earth-fault pickup settings.
  6. Coordinate the relay with downstream protection.
  7. Check upstream grading.
  8. Configure breaker-failure protection.
  9. Configure trip circuit and alarm outputs.
  10. Verify the complete protection scheme through secondary injection testing.

5. Sepam S81 and S82 — Line Protection Applications

5.1 Introduction

Sepam S81 and S82 are dedicated members of the Series 80 substation protection family.

They are intended for feeder and line protection applications where additional directional protection capabilities may be required.

Their application depends on network topology, grounding arrangement, and the required protection philosophy.

Typical installations include:

  • Medium-voltage overhead lines.
  • Industrial distribution feeders.
  • Radial distribution networks.
  • Ring-main distribution systems.
  • Networks with parallel feeders.
  • Networks supplied from multiple sources.

5.2 Directional Protection

In a simple radial network, overcurrent protection can often distinguish between normal and fault conditions using current magnitude and operating time.

However, in interconnected networks, fault current may flow in different directions.

Directional protection uses both current and a suitable polarizing voltage or reference quantity to determine the direction of the fault.

The relay evaluates the relationship between current and voltage phase angles.

A simplified directional operating principle is:

\[ T=|V||I|\cos(\theta-\tau) \]

Where:

  • \(V\) = Polarizing voltage.
  • \(I\) = Operating current.
  • \(\theta\) = Current-to-voltage phase angle.
  • \(\tau\) = Relay maximum torque angle.

The actual directional characteristic depends on the relay protection element and its configured polarizing method.

5.3 Directional Earth-Fault Protection

Directional earth-fault protection is particularly important in networks with multiple feeding sources or interconnected feeders.

It can distinguish between an earth fault located in the protected direction and one located behind the relay.

The protection may use residual current and residual voltage quantities.

Typical applications include:

  • Compensated networks.
  • Isolated-neutral networks.
  • Impedance-earthed networks.
  • Parallel feeder arrangements.
  • Networks with multiple transformer incomers.

The correct selection of polarizing quantities and directional characteristics is essential.

5.4 S81 and S82 Application Differences

The precise distinction between S81 and S82 should be established from the model-specific Schneider Electric protection function tables and ordering documentation.

Both belong to the substation feeder protection group, but their dedicated application functions are not interchangeable merely because they have similar hardware architecture.

Engineers should check:

  • Directional earth-fault availability.
  • Phase directional overcurrent availability.
  • Voltage measurement requirements.
  • Residual voltage measurement arrangements.
  • CT and VT input requirements.
  • Required communication and I/O modules.

5.5 Practical Line Protection Engineering

A typical engineering study should include:

  1. Single-line diagram analysis.
  2. Network grounding study.
  3. Maximum and minimum fault current calculations.
  4. CT and VT selection.
  5. Directional element selection.
  6. Pickup current calculation.
  7. Time-current coordination.
  8. Directional characteristic verification.
  9. Circuit-breaker trip logic.
  10. Secondary injection testing under forward and reverse fault conditions.

A particularly important commissioning test is to verify that the relay operates correctly for forward faults and remains stable for reverse faults.

6. Sepam S84 — Advanced Feeder and Substation Protection

6.1 Application Overview

Sepam S84 is a dedicated substation protection relay intended for advanced feeder and incomer applications.

It is suitable for installations requiring more comprehensive protection and control functionality than a basic feeder relay.

Typical applications include:

  • Main incomer protection.
  • Bus-section circuit-breaker protection.
  • Industrial substation protection.
  • Critical distribution feeders.
  • Complex power distribution arrangements.

6.2 Rate-of-Change-of-Frequency Protection

One of the important application-specific functions associated with S84 is rate-of-change-of-frequency protection.

The rate of change of frequency is expressed as:

\[ ROCOF=\frac{df}{dt} \]

Where:

  • \(f\) = System frequency.
  • \(t\) = Time.

ROCOF protection monitors how quickly system frequency changes.

It may be used in:

  • Distributed generation applications.
  • Islanding detection schemes.
  • Generator-grid separation schemes.
  • Load-shedding and system stability applications.

ROCOF settings must be selected carefully because frequency disturbances, switching events, and measurement transients can cause unwanted operation.

6.3 Advanced Feeder Protection Scheme

An S84 protection scheme may combine:

  • Phase overcurrent.
  • Earth-fault protection.
  • Voltage protection.
  • Frequency protection.
  • ROCOF protection.
  • Breaker-failure protection.
  • Synchronism-check functions, where equipped.
  • Programmable logic.
  • Circuit-breaker control.

6.4 Synchronism Check

Synchronism-check protection verifies whether two electrical systems are suitable for connection.

The principal quantities are:

  • Voltage difference.
  • Frequency difference.
  • Phase-angle difference.

The synchronism-check function prevents circuit-breaker closing when the two sides are outside the permitted synchronizing limits.

This is particularly important for bus-section breakers, generator incomers, and network interconnections.

7. Sepam M87 — Motor Protection

7.1 Introduction to M87

Sepam M87 is designed for advanced motor protection applications, particularly where motor differential protection and comprehensive electrical supervision are required.

Typical applications include:

  • Large industrial induction motors.
  • Critical process motors.
  • Pumps and compressors.
  • Fans and blowers.
  • Industrial drives.
  • Motors requiring differential protection.

Motor protection must consider both electrical and thermal operating conditions.

An effective motor protection scheme must protect against stator winding faults, phase faults, earth faults, overloads, abnormal voltage conditions, and mechanical operating problems that produce abnormal electrical characteristics.

7.2 Main Motor Protection Functions

Typical motor protection functions include:

ANSIFunctionPurpose
50/51Phase overcurrentShort-circuit and overcurrent protection
50N/51NEarth-fault protectionStator and cable earth faults
49Thermal overloadMotor thermal protection
46Negative-sequence protectionUnbalanced current protection
48Incomplete sequence/start-up supervisionAbnormal starting conditions
50LRLocked-rotor protectionDetects stalled motor conditions
27UndervoltageAbnormal supply voltage
59OvervoltageExcessive supply voltage
37UndercurrentLoss-of-load detection
66Starts-per-hour supervisionLimits excessive starting
87MMotor differentialInternal stator phase-fault protection

The available functions and their exact ANSI implementation should be verified in the model-specific documentation.

7.3 Motor Differential Protection (87M)

Motor differential protection is an important function for large and critical motors.

The principle is based on comparing the currents entering and leaving the protected motor stator winding.

Under normal operating conditions:

\[ I_{\text{diff}}\approx 0 \]

For an internal fault:

\[ I_{\text{diff}}=|I_1-I_2| \]

Where:

  • \(I_1\) = Current measured at one side of the protected zone.
  • \(I_2\) = Corresponding current at the opposite side.

The actual differential algorithm includes appropriate compensation and stabilization.

A differential protection scheme normally requires CTs at both ends of the protected motor winding.

The protection engineer must verify:

  • CT ratio compatibility.
  • CT polarity.
  • Phase correspondence.
  • CT secondary wiring.
  • Differential operating characteristic.
  • Restraint or stabilization behavior.
  • Trip output assignment.

7.4 Motor Thermal Protection (49)

Motor thermal protection estimates the thermal condition of the motor using electrical loading and configured thermal characteristics.

The thermal model considers:

  • Motor rated current.
  • Thermal capacity.
  • Heating time constant.
  • Cooling time constant.
  • Starting current.
  • Starting duration.
  • Motor operating conditions.

The thermal state can be represented conceptually as:

\[ \frac{d\theta}{dt} = \frac{P_{\text{loss}}}{C_{\text{th}}} – \frac{\theta}{\tau_{\text{th}}} \]

Where:

  • \(\theta\) = Thermal state.
  • \(P_{\text{loss}}\) = Heating power.
  • \(C_{\text{th}}\) = Equivalent thermal capacity.
  • \(\tau_{\text{th}}\) = Thermal time constant.

The relay should be configured according to the motor manufacturer’s thermal data and starting characteristics.

7.5 Negative-Sequence Protection (46)

Negative-sequence current is produced by unbalanced phase currents.

It can result from:

  • Phase-to-phase faults.
  • Unbalanced supply voltages.
  • Open-phase conditions.
  • Unequal phase loading.
  • Supply system abnormalities.

Negative-sequence current produces additional heating in motor windings and rotor components.

The protection settings must consider the motor’s allowable negative-sequence withstand capability.

7.6 Motor Starting and Locked-Rotor Protection

Motor starting current can be several times higher than rated current.

Consequently, protection settings must allow normal motor starting without compromising short-circuit protection.

The engineer should consider:

  • Starting current magnitude.
  • Starting time.
  • Acceleration time.
  • Hot and cold starting conditions.
  • Permitted number of starts.
  • Motor thermal withstand.
  • Locked-rotor withstand time.

7.7 Practical M87 Commissioning

Important commissioning tests include:

  1. CT ratio and polarity verification.
  2. Differential current measurement.
  3. Differential stability testing.
  4. Differential operating tests.
  5. Thermal model verification.
  6. Negative-sequence injection.
  7. Start-up supervision testing.
  8. Locked-rotor protection testing.
  9. RTD input verification, where fitted.
  10. Trip circuit and breaker operation testing.

8. Sepam T81 and T82 — Transformer Protection

transformer – T87 – Sepam series 80 – Schneider Electric Gulf

8.1 Introduction

Sepam T81 and T82 are designed for transformer protection applications.

They are intended for transformer installations where several protection functions must be integrated into a single numerical relay.

Typical applications include:

  • Distribution transformers.
  • Industrial power transformers.
  • Medium-voltage transformer feeders.
  • Transformer incomers.
  • Transformers supplying industrial processes.
  • Transformer protection in substations.

Transformer protection must account for faults inside the transformer, external network faults, overloads, abnormal voltage conditions, and abnormal operating conditions such as magnetizing inrush.

8.2 Transformer Protection Functions

A typical transformer protection scheme may include:

ANSIProtectionPurpose
50/51Phase overcurrentPhase fault backup
50N/51NEarth-fault overcurrentEarth-fault protection
67NDirectional earth faultDirectional ground-fault protection
49Thermal overloadTransformer thermal protection
46Negative-sequence protectionUnbalanced current protection
27UndervoltageVoltage supervision
59OvervoltageExcessive voltage protection
24Volts-per-hertzOverfluxing protection
50BFBreaker failureFailure of circuit-breaker interruption

Actual availability varies with relay model and application.

8.3 Transformer Overcurrent Protection

Transformer overcurrent protection provides protection against:

  • External phase faults.
  • Internal phase faults, within the sensitivity of the scheme.
  • Excessive loading.
  • Downstream fault backup conditions.

The pickup current must be selected based on:

  • Transformer rated current.
  • Transformer impedance.
  • Maximum loading.
  • Inrush current.
  • Downstream protection coordination.
  • Maximum and minimum fault currents.

Transformer rated current is calculated using:

\[ I_n=\frac{S_n}{\sqrt{3}V_n} \]

Where:

  • \(S_n\) = Transformer rated apparent power.
  • \(V_n\) = Rated line-to-line voltage.
  • \(I_n\) = Rated line current.

8.4 Transformer Earth-Fault Protection

Earth-fault protection must consider the transformer winding connection and neutral grounding arrangement.

Different transformer connections create different zero-sequence current paths.

The engineer should evaluate:

  • Star-connected windings.
  • Delta-connected windings.
  • Grounded star neutral.
  • Resistance-grounded neutral.
  • Isolated-neutral arrangements.
  • Grounding transformer arrangements.

A relay setting suitable for a solidly grounded system may not be suitable for a resistance-grounded or isolated-neutral system.

8.5 Transformer Thermal Protection

Transformer thermal protection supervises loading and thermal stress.

Important parameters include:

  • Rated transformer current.
  • Permissible overload.
  • Cooling arrangement.
  • Ambient temperature.
  • Winding temperature limits.
  • Transformer thermal time constants.

Where temperature sensors are available, RTD measurements can supplement current-based thermal protection.

8.6 Volts-per-Hertz Protection (24)

Transformer overfluxing occurs when the magnetic flux exceeds the permissible design limit.

The approximate relationship is:

\[ \Phi\propto\frac{V}{f} \]

Where:

  • \(\Phi\) = Magnetic flux.
  • \(V\) = Applied voltage.
  • \(f\) = Frequency.

Excessive V/Hz can produce magnetic saturation, increased magnetizing current, and transformer overheating.

The protection engineer must consider the transformer manufacturer’s permissible overfluxing curve.

8.7 T81 and T82 Engineering Considerations

When selecting T81 or T82, engineers should evaluate the required application-specific directional and voltage-related functions, as well as the standard transformer protection functions.

The selection must be based on the official model function matrix rather than assuming that both models provide identical protection capabilities.

9. Sepam T87 — Transformer Differential Protection

9.1 Introduction

Sepam T87 is dedicated to transformer differential protection.

Transformer differential protection is one of the most important protection schemes for medium-sized and large power transformers.

It provides selective protection for faults occurring within the transformer protection zone.

The differential protection zone is generally defined by the CT locations on the transformer primary and secondary sides.

9.2 Operating Principle

The relay compares the currents entering and leaving the protected transformer.

Under normal conditions, after appropriate ratio and phase compensation, the differential current should be close to zero.

For an internal fault, the difference between the compensated currents increases.

A simplified differential current equation is:

\[ I_{\text{diff}}=|I_1′-I_2’| \]

Where:

  • \(I_1’\) = Compensated primary-side current.
  • \(I_2’\) = Compensated secondary-side current.

Deep Learning-Based Algorithm for Internal Fault Detection of Power Transformers during Inrush Current at Distribution Substations

9.3 Transformer Ratio Compensation

The current values on the transformer primary and secondary sides are normally different because of the transformer turns ratio.

For example, consider a transformer rated:

  • 20 MVA.
  • 33 kV / 11 kV.

The rated primary current is:

\[ I_{HV}=\frac{20\times10^6}{\sqrt{3}\times33000} \]

\[ I_{HV}\approx349.9\ A \]

The rated secondary current is:

\[ I_{LV}=\frac{20\times10^6}{\sqrt{3}\times11000} \]

\[ I_{LV}\approx1049.7\ A \]

The differential protection system must compensate for the different current magnitudes.

9.4 Vector Group Compensation

Transformer vector groups introduce phase displacement between primary and secondary currents.

For example, a Dyn11 transformer introduces a 30-degree phase displacement.

The differential relay must account for this phase shift to prevent unwanted operation during normal load and external faults.

9.5 Differential Restraint

Differential protection must remain stable during external faults, even when CT saturation produces differential current.

A percentage differential characteristic typically includes:

  • Minimum differential pickup.
  • Restraint current.
  • One or more bias slopes.
  • High-set differential operation, where provided.

A simplified operating characteristic is:

\[ I_{\text{diff}}>I_{\text{pickup}}+kI_{\text{restraint}} \]

The actual characteristic depends on the relay algorithm and selected settings.

9.6 Magnetizing Inrush Restraint

Transformer energization produces magnetizing inrush current.

This current can be significantly higher than normal magnetizing current and may contain substantial second-harmonic components.

The differential relay must distinguish between:

  • Internal transformer faults.
  • External faults.
  • Normal load current.
  • Magnetizing inrush.

Inrush restraint or blocking functions help prevent unwanted differential tripping during transformer energization.

9.7 Transformer Differential Protection Testing

Testing should include:

  1. CT ratio verification.
  2. CT polarity verification.
  3. Transformer vector group confirmation.
  4. Phase compensation verification.
  5. Differential stability testing.
  6. Differential pickup testing.
  7. Bias characteristic testing.
  8. External fault stability testing.
  9. Inrush restraint verification, where supported.
  10. Trip circuit verification.

A complete differential test should reproduce the actual current relationships expected during normal load, external faults, and internal faults.

10. Sepam G82 — Generator Protection

10.1 Introduction

Sepam G82 is designed for generator protection applications.

It can be used in industrial power plants, captive generation installations, and distribution systems with embedded generators.

Generator protection must address both electrical faults and abnormal operating conditions.

Important generator protection requirements include:

  • Stator winding fault protection.
  • Earth-fault protection.
  • Overcurrent protection.
  • Negative-sequence protection.
  • Reverse-power protection.
  • Loss-of-excitation protection.
  • Overvoltage protection.
  • Underfrequency and overfrequency protection.
  • Overfluxing protection.

10.2 Main Generator Protection Functions

ANSIProtectionPurpose
50/51Phase overcurrentBackup and fault protection
50N/51NEarth faultGround-fault protection
46Negative sequenceUnbalanced current protection
32Reverse powerMotoring protection
40Loss of excitationExcitation failure protection
27UndervoltageLow voltage protection
59OvervoltageHigh voltage protection
81UUnderfrequencyLow frequency protection
81OOverfrequencyHigh frequency protection
24V/HzOverfluxing protection
25Synchronism checkSynchronization supervision
50BFBreaker failureGenerator breaker failure protection

The exact function availability must be verified against the G82 model documentation.

10.3 Reverse Power Protection (32)

Reverse-power protection detects when a generator begins absorbing active power from the electrical system.

This condition can occur when the prime mover loses its driving torque while the generator remains connected to the network.

For a synchronous generator, this may result in motoring operation.

The relay measures active power and operates when reverse power exceeds the configured threshold for the specified time.

The protection engineer must consider:

  • Minimum reverse-power threshold.
  • Operating time delay.
  • Generator prime mover characteristics.
  • Auxiliary power requirements.
  • Normal operating conditions.

10.4 Loss-of-Excitation Protection (40)

Loss of excitation occurs when the generator excitation system fails or becomes insufficient.

This can cause:

  • Excessive reactive power absorption.
  • Loss of synchronizing capability.
  • Rotor heating.
  • Voltage instability.
  • Potential loss of synchronism.

Loss-of-excitation protection can use impedance-based or other suitable detection principles, depending on the available relay function.

The setting must be coordinated with generator capability curves and the excitation system.

10.5 Negative-Sequence Protection (46)

Unbalanced phase currents produce negative-sequence components.

These components induce double-frequency currents in the rotor, causing additional heating.

Generator negative-sequence protection must be coordinated with the manufacturer’s permissible negative-sequence withstand capability.

10.6 Generator Earth-Fault Protection

Generator earth-fault protection depends on the generator neutral grounding arrangement.

Typical arrangements include:

  • Solidly grounded neutral.
  • Resistance grounding.
  • Distribution-transformer grounding.
  • Isolated neutral.

The protection scheme must be selected according to the generator stator grounding method and required earth-fault sensitivity.

10.7 Generator Synchronization

Synchronism-check protection verifies that voltage, frequency, and phase angle are within acceptable limits before closing the generator circuit breaker.

The function is particularly important for generators connected to an existing power network.

11. Sepam G87 — Generator Differential Protection

11.1 Introduction

Sepam G87 is dedicated to generator differential protection.

It protects the generator stator winding against internal phase faults within the differential protection zone.

The protection scheme uses CTs installed at the generator terminal and neutral sides.

11.2 Generator Differential Operating Principle

Under normal operating conditions, the current entering and leaving the protected stator winding should be equal after accounting for CT polarity and measurement direction.

For an internal fault, the difference between the two currents increases.

\[ I_{\text{diff}}=|I_{\text{terminal}}-I_{\text{neutral}}| \]

The relay detects the differential current and initiates tripping when the operating characteristic is satisfied.

11.3 Generator Differential Protection Zone

The differential protection zone is determined by the locations of the CTs.

Differential (87) Current Protection | Electric Power Measurement and Control Systems

The protection engineer should verify:

  • CT location.
  • CT ratio.
  • CT polarity.
  • Phase identification.
  • Secondary circuit continuity.
  • Differential pickup.
  • Restraint characteristics.
  • Stability during external faults.

11.4 Differential Protection Limitations

Generator differential protection is highly effective for internal phase-to-phase and phase faults within the protected zone.

However, it does not automatically provide complete protection against every stator earth fault.

Additional protection may be required depending on the neutral grounding arrangement, including dedicated stator earth-fault protection.

11.5 G87 Commissioning

Recommended tests include:

  1. CT secondary injection.
  2. CT polarity verification.
  3. Differential current measurement.
  4. Differential pickup test.
  5. Restraint characteristic test.
  6. External fault stability test.
  7. Internal fault simulation.
  8. Trip output verification.
  9. Alarm and event verification.
  10. Disturbance recording verification.

12. Sepam B83 — Busbar Protection

12.1 Introduction

Sepam B83 is a dedicated busbar protection relay.

Busbars are critical components in electrical substations because they connect multiple incoming and outgoing circuits.

A busbar fault can affect several feeders simultaneously and may cause widespread interruption.

Busbar protection must therefore operate selectively and rapidly.

12.2 Busbar Protection Requirements

Typical busbar protection requirements include:

  • Fast internal fault detection.
  • Stability during external feeder faults.
  • Selective tripping.
  • Correct circuit-breaker identification.
  • Busbar section supervision.
  • Protection zone discrimination.

12.3 Busbar Voltage Supervision

An important feature associated with B83 is the supervision of three-phase voltages on two busbar systems.

This is particularly relevant to substations with two busbar arrangements.

The relay can support voltage supervision and related control functions according to its configuration.

12.4 Busbar Differential Protection

The fundamental principle of busbar differential protection is to compare the sum of currents entering and leaving the protected busbar zone.

For a healthy busbar:

\[ \sum I_{\text{in}}-\sum I_{\text{out}}\approx0 \]

For an internal busbar fault:

\[ \left|\sum I\right|>I_{\text{pickup}} \]

The protection scheme must remain stable for external faults, even when CT saturation occurs.

Engineering distinction: B83 is a dedicated busbar application relay, but the exact protection scheme and CT arrangement must be checked against the relevant application documentation. Do not assume that every B83 installation implements a conventional centralized high-speed busbar differential scheme.

12.5 Double-Busbar Applications

In substations with two busbar systems, circuit breakers and disconnectors can connect feeders to different bus sections.

The protection and control system must identify the actual switching arrangement.

Important signals include:

  • Busbar isolator position.
  • Bus-section breaker status.
  • Feeder breaker status.
  • Busbar voltage.
  • Protection trip signals.
  • Interlocking signals.

12.6 Practical B83 Engineering

Important commissioning activities include:

  1. Verification of voltage transformer connections.
  2. Verification of phase sequence.
  3. Busbar voltage measurement tests.
  4. Verification of switching position inputs.
  5. Synchronism-check testing, where configured.
  6. Busbar protection logic verification.
  7. Trip matrix verification.
  8. Circuit-breaker control testing.
  9. Communication verification.
  10. Complete functional testing of the busbar scheme.

13. Sepam Series 80 Advanced Logic and Control

One of the important advantages of Sepam Series 80 is its ability to integrate protection, control, monitoring, and automation functions.

The relay can do more than detect faults and issue trip commands.

It can also implement application-specific logic for circuit-breaker control, alarms, interlocking, and other electrical control functions.

13.1 Programmable Logic

Sepam Series 80 supports programmable logic through the optional Logipam functionality.

Logipam allows engineers to develop customized control and automation functions.

Typical applications include:

  • Circuit-breaker control.
  • Interlocking.
  • Alarm processing.
  • Protection blocking.
  • Trip logic.
  • Load shedding.
  • Switching sequence supervision.
  • External protection signal processing.

The availability of Logipam functionality depends on the ordered firmware and configuration. Schneider Electric Ireland+1

13.2 Circuit-Breaker Control

A typical breaker control scheme includes:

  • Local and remote control selection.
  • Open command.
  • Close command.
  • Breaker position feedback.
  • Spring-charged status.
  • Trip circuit supervision.
  • Electrical interlocking.
  • Protection trip priority.

A simplified breaker closing permissive can be represented as:

\[ Close=RemoteEnable \land InterlockOK \land NoTripLockout \]

This is a conceptual example. Actual logic must include the switchgear manufacturer’s requirements and all applicable electrical and mechanical interlocks.

13.3 Protection Trip Logic

Protection trip logic combines protection function outputs and other conditions to generate the correct trip command.

For example:

\[ Trip=OC\lor EF\lor BF\lor Differential \]

Where:

  • OC = Overcurrent protection.
  • EF = Earth-fault protection.
  • BF = Breaker-failure-related trip logic.
  • Differential = Differential protection.

The final trip matrix depends on the application and must be coordinated with the switchgear protection design.

13.4 Interlocking

Electrical interlocking prevents unsafe switching operations.

Examples include:

  • Preventing breaker closing when an isolator is in an incorrect position.
  • Preventing earthing-switch closing when the circuit is energized.
  • Preventing simultaneous closing of incompatible switching devices.
  • Restricting remote operation during local control.

Interlocking logic must be designed as part of the complete substation control system.

13.5 Communication and SCADA Integration

Sepam Series 80 can provide information to SCADA systems through supported communication interfaces.

Typical data points include:

SignalSCADA application
Phase currentsElectrical measurements
Phase voltagesVoltage monitoring
Active powerEnergy management
Reactive powerPower-factor supervision
FrequencyNetwork monitoring
Breaker statusSwitching supervision
Protection pickupAlarm indication
Protection tripTrip event
Relay healthEquipment supervision
Fault recordsDisturbance analysis

Communication mapping should include proper signal naming, scaling, quality indication, and time synchronization arrangements.

14. Sepam Series 80 Settings and Configuration

Correct protection settings are essential for reliable operation.

An incorrectly configured relay may fail to detect a fault, operate unnecessarily, or cause unwanted interruption of healthy equipment.

14.1 Engineering Software

Sepam Series 80 engineering is performed using Schneider Electric’s Sepam configuration and setting tools.

The engineering environment is used for:

  • Selecting the relay application.
  • Configuring hardware.
  • Defining CT and VT ratios.
  • Configuring protection functions.
  • Adjusting protection thresholds.
  • Setting operating delays.
  • Configuring logic.
  • Assigning inputs and outputs.
  • Configuring communication.
  • Reading measurements and event records.

The exact software version and compatibility must be checked against the relay firmware and hardware generation.

14.2 Typical Configuration Workflow

A practical configuration procedure consists of the following steps.

Step 1 — Create a new project

Create a project for the electrical installation and identify the relevant substation or switchgear panel.

Step 2 — Select the relay model

Select the correct model, such as S80, S84, T87, G87, or B83.

Step 3 — Configure hardware

Define the installed:

  • Current input modules.
  • Voltage input modules.
  • Digital input modules.
  • Output modules.
  • Temperature measurement modules.
  • Communication interfaces.
  • Operator interface.

Step 4 — Configure CT and VT parameters

Enter the primary and secondary ratings and verify the measurement arrangement.

Step 5 — Configure protection functions

Enable the required protection elements and enter their settings.

Step 6 — Configure protection coordination

Verify the pickup thresholds, time delays, and operating characteristics against the protection coordination study.

Step 7 — Configure logic

Assign the required protection outputs, alarm signals, breaker control functions, and interlocks.

Step 8 — Configure communication

Define the required communication protocol, address, network parameters, and SCADA data mapping.

Step 9 — Transfer settings

Transfer the configuration to the relay using the approved engineering procedure.

Step 10 — Verify configuration

Read back the relay settings and compare them with the approved engineering file.

14.3 Important Protection Setting Parameters

ParameterEngineering consideration
CT primary ratingMatch the installed CT ratio
CT secondary ratingConfirm 1 A or 5 A compatibility
VT ratioMatch the installed voltage transformer
Phase sequenceConfirm correct phase identification
Overcurrent pickupBased on load and fault calculations
Earth-fault pickupBased on grounding arrangement
Operating timeBased on protection coordination
Directional angleBased on network configuration
Thermal settingsBased on equipment characteristics
Differential settingsBased on CTs and protected equipment
Breaker failure timeBased on breaker interruption time
Trip matrixBased on the protection philosophy

14.4 Protection Coordination

Protection coordination ensures that the protection device closest to the fault operates first, while upstream protection provides backup.

For example, in a radial distribution system:

  • The outgoing feeder relay should clear a feeder fault.
  • The transformer incomer relay should provide backup.
  • The upstream source relay should provide additional backup.

Time-current coordination should be checked using the actual relay characteristics and system fault levels.

14.5 Settings Management

A professional engineering practice should maintain:

  • Approved relay setting files.
  • Original as-found settings.
  • Final as-left settings.
  • Configuration backups.
  • Firmware information.
  • CT and VT information.
  • Test reports.
  • Commissioning records.
  • Revision history.

The removable memory cartridge is particularly useful when a relay replacement is required, but the replacement procedure must still include verification of hardware compatibility and settings.

15. Sepam Series 80 Testing and Commissioning

Commissioning verifies that the relay has been correctly installed, configured, and connected to the electrical protection system.

Testing should be performed using an appropriate secondary injection test set, suitable test procedures, and approved commissioning documents.

15.1 Visual and Mechanical Inspection

Check:

  • Relay model and ordering code.
  • Hardware configuration.
  • Auxiliary supply voltage.
  • Earthing connections.
  • Terminal tightness.
  • CT and VT wiring.
  • Communication cables.
  • Digital input and output wiring.
  • Memory cartridge installation.

15.2 CT Circuit Testing

Verify:

  • CT ratios.
  • CT polarity.
  • Phase identification.
  • Secondary circuit continuity.
  • Correct earthing of CT secondary circuits.
  • Absence of unintended open circuits.

Never open-circuit an energized CT secondary circuit.

15.3 VT Circuit Testing

Verify:

  • VT ratio.
  • Phase sequence.
  • Phase-to-phase voltage.
  • Phase-to-neutral voltage, where applicable.
  • Fuse and miniature circuit-breaker arrangements.
  • Voltage input configuration.

15.4 Protection Function Testing

Typical protection tests include:

ProtectionTest method
50/51Current injection and operating-time test
50N/51NResidual current injection
46Negative-sequence current injection
27Voltage reduction test
59Voltage increase test
49Thermal model or approved simulation test
32Active power directional test
40Loss-of-excitation simulation
24V/Hz test
87TTransformer differential simulation
87GGenerator differential simulation
87MMotor differential simulation
50BFBreaker-failure logic test
25Synchronism-check test

Only the functions available in the selected relay model should be included in the test plan.

15.5 Binary Input and Output Testing

Every configured input and output should be verified.

Examples:

  • Circuit-breaker open indication.
  • Circuit-breaker closed indication.
  • Protection trip output.
  • Protection alarm output.
  • Remote trip input.
  • External interlocking signal.
  • Local/remote selection.
  • Breaker failure initiation.

15.6 Communication Testing

Verify:

  • Communication link status.
  • Protocol configuration.
  • Device address.
  • Data mapping.
  • Measurement scaling.
  • Alarm reporting.
  • Event reporting.
  • Remote control permissions.
  • Time synchronization.

15.7 Final Commissioning Documentation

A complete commissioning report should include:

  1. Relay identification.
  2. Hardware configuration.
  3. Firmware version.
  4. Approved settings.
  5. CT and VT test results.
  6. Protection function test results.
  7. Input/output test results.
  8. Communication test results.
  9. Trip circuit verification.
  10. Final configuration backup.
  11. Outstanding issues.
  12. Engineer approval.

16. Common Engineering Problems and Troubleshooting

During installation, commissioning, and operation, protection engineers may encounter several problems with Sepam Series 80 relays.

16.1 Incorrect Current Measurements

Possible causes:

  • Incorrect CT ratio.
  • Reversed CT polarity.
  • Incorrect phase connections.
  • Open CT secondary circuit.
  • Incorrect analogue input configuration.

Recommended checks:

  • Verify CT nameplate information.
  • Check phase current measurements.
  • Verify polarity and phase sequence.
  • Compare relay measurements with an independent instrument.

16.2 Unwanted Protection Operation

Possible causes include:

  • Incorrect pickup settings.
  • Incorrect time delays.
  • CT saturation.
  • Incorrect directional polarization.
  • Incorrect logic configuration.
  • Improper coordination with downstream protection.

Review the event records, disturbance records, and protection measurements before modifying settings.

16.3 Differential Protection Instability

For T87, G87, and M87 applications, investigate:

  • CT polarity.
  • CT ratio mismatch.
  • Incorrect phase compensation.
  • Secondary wiring errors.
  • CT saturation.
  • Incorrect differential settings.

16.4 Communication Failure

Possible causes include:

  • Incorrect communication address.
  • Incorrect baud rate or network parameters.
  • Communication cable problems.
  • Incorrect protocol selection.
  • Incompatible firmware or communication modules.
  • SCADA configuration errors.

16.5 Circuit-Breaker Control Problems

Check:

  • Digital input assignments.
  • Digital output assignments.
  • Local/remote control selection.
  • Breaker position feedback.
  • Interlocking conditions.
  • Trip and close circuit wiring.
  • Lockout conditions.

17. Sepam Series 80 Compared with Other Sepam Families

Sepam Series 80 is positioned as an advanced protection family for applications requiring dedicated equipment protection and extensive programmable functions.

FeatureSepam Series 20Sepam Series 40Sepam Series 80
Protection complexityBasicIntermediateAdvanced
Feeder protectionYesYesYes
Transformer applicationsSelected applicationsSelected applicationsDedicated models
Motor protectionSelected applicationsDedicated applicationsAdvanced dedicated models
Generator protectionLimited applicationsSelected applicationsDedicated models
Differential protectionLimitedSelected applicationsDedicated models
Programmable logicLimitedApplication dependentLogipam option
Advanced controlLimitedAvailableExtensive
CommunicationModel dependentModel dependentAdvanced options

The actual capabilities depend on the individual relay model, firmware, and ordered hardware.

18. Practical Engineering Case Studies

Case Study 1 — Industrial Feeder Protection Using S80

System information:

  • System voltage: 11 kV.
  • Feeder rated current: 250 A.
  • CT ratio: 300/1 A.
  • Application: Industrial outgoing feeder.

Engineering activities:

  1. Calculate the feeder operating current.
  2. Select the CT ratio.
  3. Calculate phase overcurrent pickup.
  4. Determine earth-fault sensitivity.
  5. Coordinate with downstream protection.
  6. Configure circuit-breaker trip logic.
  7. Perform secondary injection tests.

Case Study 2 — Transformer Differential Protection Using T87

System information:

  • Transformer rating: 20 MVA.
  • HV voltage: 33 kV.
  • LV voltage: 11 kV.
  • Vector group: Dyn11.

Engineering activities:

  1. Calculate rated currents on both sides.
  2. Select appropriate CT ratios.
  3. Verify CT polarity.
  4. Configure transformer vector group compensation.
  5. Configure differential protection.
  6. Verify restraint characteristics.
  7. Test external fault stability.
  8. Perform internal fault simulation.

Case Study 3 — Generator Differential Protection Using G87

System information:

  • Generator rating: 10 MVA.
  • Generator voltage: 6.6 kV.
  • CTs installed at terminal and neutral sides.

Engineering activities:

  1. Calculate generator rated current.
  2. Verify CT ratios.
  3. Verify CT polarity.
  4. Configure differential protection.
  5. Test differential pickup.
  6. Test differential restraint.
  7. Verify trip logic.
  8. Perform complete commissioning tests.

Case Study 4 — Motor Protection Using M87

System information:

  • Motor rating: 2 MW.
  • Voltage: 6.6 kV.
  • Application: Critical industrial pump.

Engineering activities:

  1. Collect motor nameplate information.
  2. Calculate rated current.
  3. Review motor starting current.
  4. Configure thermal overload protection.
  5. Configure negative-sequence protection.
  6. Configure motor differential protection where applicable.
  7. Verify RTD measurements where fitted.
  8. Perform secondary injection tests.

19. Engineering Best Practices for Sepam Series 80

For reliable protection system operation, the following practices are recommended.

Protection design

  • Use an approved protection coordination study.
  • Select the correct relay model for the application.
  • Verify all CT and VT requirements.
  • Consider minimum and maximum fault levels.
  • Check equipment thermal and short-circuit withstand limits.

Configuration

  • Maintain approved configuration files.
  • Verify all enabled protection functions.
  • Use appropriate protection logic.
  • Document all changes.
  • Verify settings after transferring them to the relay.

Testing

  • Perform CT and VT checks.
  • Test all configured protection functions.
  • Verify breaker trip and close circuits.
  • Test interlocking logic.
  • Check communication with SCADA.
  • Save complete commissioning reports.

Maintenance

  • Review protection event records.
  • Investigate unexpected trips.
  • Maintain backup configuration files.
  • Check communication and relay diagnostics.
  • Review settings following network modifications.

20. Conclusion

Schneider Electric Sepam Series 80 is an advanced family of numerical protection relays designed for medium-voltage distribution systems, industrial substations, and specialized equipment protection applications.

Its dedicated relay models provide solutions for feeder, line, motor, transformer, generator, and busbar protection.

The most important engineering capabilities covered in this guide include:

  • S80 feeder and incomer protection.
  • S81 and S82 directional line protection applications.
  • S84 advanced feeder and substation protection.
  • M87 motor differential and motor protection.
  • T81 and T82 transformer protection.
  • T87 transformer differential protection.
  • G82 generator protection.
  • G87 generator differential protection.
  • B83 busbar protection.
  • Advanced logic and circuit-breaker control.
  • Protection settings and configuration.
  • Testing, commissioning, and troubleshooting.

For protection engineers, understanding the individual relay models, their dedicated functions, and their practical applications is essential for selecting, configuring, testing, and maintaining a reliable protection system.

Important product documentation note: Sepam Series 80 is an established product family, and some models and configurations may be discontinued or subject to regional availability. Always consult the applicable Schneider Electric documentation, firmware compatibility information, and product lifecycle notices before specifying equipment for a new project.

21. Schneider Electric Documentation and Further Reading

The following resources are useful for detailed engineering and product verification:

  1. Schneider Electric — Sepam Series 80 Official Product Range.
  2. Sepam Series 80 — Technical Documentation and Selection Guide.
  3. Sepam Series 60 and 80 Product Catalogue.
  4. Schneider Electric — Sepam 80 Ordering Configurations.
  5. Schneider Electric — Sepam Protection Configurations.

22. Sepam Series 80 Article Series

This article is part of the Elec-Engg Schneider Sepam Protection Relays knowledge series.

No.Article
1Sepam Series 80 Overview
2Sepam S80 Feeder Protection
3Sepam S81 and S82 Line Protection Applications
4Sepam S84 Advanced Feeder Protection
5Sepam M87 Motor Protection
6Sepam T81 and T82 Transformer Protection
7Sepam T87 Transformer Differential Protection
8Sepam G82 Generator Protection
9Sepam G87 Generator Differential Protection
10Sepam B83 Busbar Protection
11Sepam 80 Advanced Logic and Control
12Sepam 80 Settings and Configuration

Explore more technical resources: Elec-Engg — Power System Protection and Substation Automation

Practical engineering knowledge for protection, control, commissioning, and substation automation professionals.

Leave a Comment