Sepam Feeder, Motor & Equipment Protection: Complete Guide to Applications, Overcurrent, Directional Overcurrent, Earth Fault, Motor Protection, Settings, Configuration and Practical MV Projects
- 1. Introduction to Sepam Feeder, Motor and Equipment Protection
- 2. Sepam Protection Relay Families and Applications
- 3. Sepam Feeder Protection Applications
- 4. Sepam Overcurrent Protection (ANSI 50/51)
- 5. Sepam Directional Overcurrent Protection (ANSI 67)
- 6. Sepam Earth Fault Protection (ANSI 50N/51N)
- 7. Sepam Sensitive Earth Fault Protection
- 8. Sepam Negative Sequence Protection (ANSI 46)
- 9. Sepam Thermal Overload Protection (ANSI 49)
- 10. Sepam Undervoltage and Overvoltage Protection (ANSI 27/59)
- 11. Sepam Motor Starting and Stall Protection
- 12. Sepam Motor Differential Protection (ANSI 87M)
- 13. Sepam Capacitor Bank Protection
- 14. Practical MV Feeder Protection Projects
- 15. Sepam Relay Configuration and Engineering Software
- 16. Sepam Protection Testing and Commissioning
- 17. Common Sepam Protection Problems and Troubleshooting
- 18. Recommended Standards and Engineering References
- 19. Practical Sepam Protection Engineering: What Engineers Should Be Able to Do
- 20. Sepam Protection Relay Training by Dr. Saeed Roostaee – Elec-Engg
- 21. Conclusion
1. Introduction to Sepam Feeder, Motor and Equipment Protection
Medium-voltage (MV) distribution systems require reliable protection to detect abnormal operating conditions, isolate faulty equipment, and maintain continuity of electrical supply.
Protection functions for MV feeders, motors, transformers, capacitor banks, and other electrical equipment are commonly implemented using numerical protection relays.
The Schneider Electric Sepam family of protection relays provides protection, measurement, monitoring, control, and communication capabilities for different MV applications.
Depending on the Sepam model and hardware configuration, these relays can provide:
- Phase overcurrent protection (50/51).
- Directional overcurrent protection (67).
- Earth fault protection (50N/51N).
- Sensitive earth fault protection.
- Negative sequence protection (46).
- Thermal overload protection (49).
- Undervoltage protection (27).
- Overvoltage protection (59).
- Motor starting supervision.
- Motor stall protection.
- Motor differential protection (87M), where supported by the selected protection architecture.
- Capacitor bank protection.
- Circuit breaker monitoring and control.
- Event recording and disturbance analysis.
This article provides a comprehensive engineering guide to Sepam feeder, motor, and equipment protection, including protection principles, ANSI functions, relay settings, CT connections, coordination, testing, commissioning, and practical MV protection projects.
The objective is to connect theoretical protection principles with actual engineering applications and relay configuration.
2. Sepam Protection Relay Families and Applications
Sepam relays are available in different families designed for particular protection applications.
The main families include:
| Sepam family | Typical applications |
|---|---|
| Sepam Series 20 | Basic feeder, transformer, and motor protection |
| Sepam Series 40 | Advanced feeder, motor, transformer, and equipment protection |
| Sepam Series 60 | More advanced protection and control applications |
| Sepam Series 80 | Comprehensive protection for complex MV applications |
The exact functions depend on the model, firmware, hardware options, and application configuration.
Examples of commonly encountered models include:
- Sepam S20, S24 and S26.
- Sepam S40, S41, S42 and S43.
- Sepam S50, S51 and S52.
- Sepam S60 and S62.
- Sepam S80, S81, S82 and S84.
- Sepam M20, M41 and M87.
- Sepam T40, T42, T81, T82 and T87.
It is important to check the model-specific documentation before preparing a protection scheme. Not every protection function is available in every Sepam relay.
3. Sepam Feeder Protection Applications
3.1 What Is MV Feeder Protection?
An MV feeder supplies electrical energy from a distribution busbar to downstream loads, distribution transformers, motors, or other substations.
A typical MV feeder protection arrangement includes:
- Incoming or outgoing circuit breaker.
- Current transformers (CTs).
- Voltage transformers (VTs), when required.
- Sepam protection relay.
- Circuit breaker trip and close circuits.
- Auxiliary DC supply.
- Protection and control wiring.
- Communication interfaces.
The protection relay continuously monitors electrical quantities and detects abnormal conditions.
When a fault occurs, the relay evaluates the measured quantities against its configured protection characteristics and issues a trip command when the relevant operating conditions are satisfied.
3.2 Typical Feeder Protection Functions
| Protection function | ANSI code | Purpose |
|---|---|---|
| Phase overcurrent | 50/51 | Detect phase faults |
| Directional overcurrent | 67 | Detect faults in a defined direction |
| Earth fault | 50N/51N | Detect ground faults |
| Sensitive earth fault | 50N/51N or model-specific function | Detect low-magnitude earth faults |
| Negative sequence | 46 | Detect current unbalance |
| Undervoltage | 27 | Detect low voltage |
| Overvoltage | 59 | Detect excessive voltage |
| Thermal overload | 49 | Detect thermal overload conditions |
| Breaker failure | 50BF | Detect failure of the circuit breaker to interrupt current, where supported |
3.3 CT Selection and Connections
CT selection is one of the most important stages in feeder protection engineering.
The following parameters must be considered:
- Primary rated current.
- Secondary rated current, commonly 1 A or 5 A.
- CT accuracy class.
- CT rated burden.
- Short-time thermal withstand.
- Dynamic current withstand.
- Protection accuracy and saturation performance.
- Required residual current measurement arrangement.
For example, consider an MV feeder with a maximum operating current of 400 A.
A possible CT ratio is:
\[ CT = 400/1\ A \]
If the primary current is 320 A, the secondary current is:
\[ I_s = \frac{320}{400}\times 1 \]
\[ I_s=0.8\ A \]
The relay uses this secondary measurement to calculate the primary current according to its CT configuration.
3.4 Feeder Protection Engineering Considerations
A complete feeder protection study should consider:
- Maximum load current.
- Maximum and minimum short-circuit currents.
- Earth fault current.
- Upstream and downstream protection characteristics.
- CT saturation during high-current faults.
- Cable thermal withstand.
- Circuit breaker interrupting capacity.
- Fault clearance time.
- Protection selectivity.
The protection settings should be based on an approved short-circuit and coordination study rather than arbitrary default values.
4. Sepam Overcurrent Protection (ANSI 50/51)
Overcurrent protection is one of the fundamental protection functions in MV distribution systems.
It detects current exceeding a configured threshold and initiates an alarm or trip depending on the selected protection stage.
Two main operating principles are used.
4.1 Instantaneous Overcurrent Protection (50)
ANSI 50 protection operates without an intentional inverse-time delay when the measured current exceeds its pickup threshold.
The operating principle is:
\[ I > I_{50} \]
Where:
- \(I\) = measured phase current.
- \(I_{50}\) = configured instantaneous pickup current.
For example, if the instantaneous pickup is 2,000 A and the measured fault current is 2,500 A, the protection function may operate after its configured operating and output delays.
Applications include:
- High-current phase faults.
- Close-in feeder faults.
- Busbar-related faults within the protection zone.
- Backup protection, where appropriate.
The pickup must be selected carefully to avoid unwanted operation during downstream faults or transformer inrush conditions.
4.2 Time Overcurrent Protection (51)
Time overcurrent protection operates when current exceeds a configured threshold for a specified time or according to an inverse-time characteristic.
The main characteristics include:
- Definite Time (DT).
- Standard Inverse (SI).
- Very Inverse (VI).
- Extremely Inverse (EI).
- Other characteristics supported by the selected relay.
For an IEC inverse-time characteristic:
\[ t = TMS \times \frac{k}{(I/I_s)^\alpha-1} \]
Where:
- \(t\) = operating time.
- \(TMS\) = time multiplier setting.
- \(I\) = measured current.
- \(I_s\) = pickup current.
- \(k,\alpha\) = curve constants.
Common IEC curve constants include:
| Curve | k | α |
|---|---|---|
| Standard Inverse | 0.14 | 0.02 |
| Very Inverse | 13.5 | 1 |
| Extremely Inverse | 80 | 2 |
| Long-Time Inverse | 120 | 1 |
4.3 Practical Overcurrent Setting Example
Consider an MV feeder with:
- CT ratio: 400/1 A.
- Maximum load current: 320 A.
- Relay pickup: 360 A primary.
- Maximum three-phase fault current: 5,000 A.
The secondary pickup is:
\[ I_{pickup,sec}=\frac{360}{400}=0.9 A \]
The relay pickup should be checked against:
- Maximum operating current.
- Emergency loading.
- Cable ampacity.
- Downstream protection settings.
- Minimum fault current.
4.4 Overcurrent Protection Coordination
Protection coordination ensures that the protection device nearest to the fault operates first, while upstream devices remain as backup.
For example:
- Downstream feeder relay: primary protection.
- Upstream incomer relay: backup protection.
- Transformer upstream protection: additional backup.
The coordination interval must account for relay operating time, breaker opening time, relay overshoot, and engineering margins.
5. Sepam Directional Overcurrent Protection (ANSI 67)
5.1 Why Is Directional Protection Required?
Conventional overcurrent protection responds to current magnitude.
However, in interconnected distribution networks, fault current may flow in either direction.
This is particularly important in:
- Ring distribution networks.
- Parallel feeders.
- Networks with distributed generation.
- Networks with multiple supply sources.
- Industrial networks with generators.
Directional overcurrent protection evaluates both current magnitude and the phase relationship between current and a reference voltage.
5.2 Operating Principle
ANSI 67 protection generally requires:
- Current measurement.
- Voltage measurement or an appropriate directional reference.
- Directional characteristic.
- Current pickup.
- Time delay or inverse-time characteristic.
The relay determines whether the fault current is flowing in the forward or reverse direction relative to the configured reference.
5.3 Forward and Reverse Direction
A directional protection scheme may be configured as:
- Forward: protection operates for faults in the selected forward direction.
- Reverse: protection operates for faults in the opposite direction.
The exact forward and reverse definitions depend on the relay connection and configuration.
5.4 Directional Protection Settings
Important settings include:
- Phase current pickup.
- Directional operating angle.
- Polarizing voltage selection.
- Maximum torque angle or characteristic angle.
- Directional mode.
- Operating delay.
- Inverse-time characteristic, if available.
Incorrect CT or VT polarity can cause directional protection to operate incorrectly.
5.5 Practical Application
Consider a ring network supplied from two substations.
A fault occurs on one feeder section.
Without directional discrimination, multiple overcurrent relays may detect the fault and operate.
With directional protection, each relay determines whether the fault is in its forward or reverse direction, allowing selective isolation.
6. Sepam Earth Fault Protection (ANSI 50N/51N)
6.1 What Is Earth Fault Protection?
An earth fault occurs when an energized conductor makes an unintended connection to earth or an earthed structure.
Common causes include:
- Cable insulation failure.
- Moisture ingress.
- Cable termination damage.
- Equipment insulation deterioration.
- Contamination.
- Mechanical damage.
- Internal equipment faults.
Earth fault protection detects residual current or current measured through a dedicated earth-fault CT.
6.2 Residual Current Measurement
For a three-phase system:
\[ I_a+I_b+I_c=3I_0 \]
Where:
- \(I_a\) = phase A current.
- \(I_b\) = phase B current.
- \(I_c\) = phase C current.
- \(I_0\) = zero-sequence current.
The residual current is:
\[ I_{res}=I_a+I_b+I_c \]
In a balanced system under normal operating conditions:
\[ I_{res}\approx 0 \]
During an earth fault, the residual current may become significant.
6.3 Earth Fault Detection Methods
Two common methods are:
1. Residual connection of three phase CTs
The relay calculates the residual current from the three phase current measurements.
2. Core balance current transformer (CBCT)
All three phase conductors pass through a common CT.
Under normal conditions, the magnetic flux contributions cancel each other.
During an earth fault, the residual current produces an output signal.
6.4 Earth Fault Settings
Typical settings include:
- Earth fault pickup current.
- Operating delay.
- Definite-time or inverse-time characteristic.
- Alarm threshold.
- Trip threshold.
- Directional supervision, if required.
The pickup must be coordinated with the system earthing arrangement.
An effectively earthed system, resistance-earthed system, and isolated-neutral system may have very different earth fault current levels.
7. Sepam Sensitive Earth Fault Protection
Sensitive earth fault protection is designed to detect relatively low earth fault currents that may not be detected reliably by conventional phase protection or higher-set earth fault stages.
7.1 Applications
Sensitive earth fault protection is particularly useful in:
- Resistance-earthed systems.
- Isolated-neutral systems.
- Networks with low earth fault current.
- Long MV cable networks.
- Systems where earth fault current is limited by grounding impedance.
7.2 Operating Principle
The relay measures a small residual current and compares it with a configured threshold.
For example:
\[ I_{res}>I_{SEF} \]
Where \(I_{SEF}\) is the sensitive earth fault pickup.
The function may use:
- Residual current.
- Neutral current.
- Residual voltage.
- Directional earth fault supervision, depending on the relay model.
7.3 Engineering Challenges
Sensitive earth fault protection requires careful attention to:
- CT accuracy.
- CT wiring.
- Residual current measurement errors.
- Cable charging currents.
- System capacitance.
- Neutral grounding method.
- External earth fault conditions.
The sensitivity should not be increased without checking the possibility of unwanted operation during normal system conditions.
8. Sepam Negative Sequence Protection (ANSI 46)
8.1 What Is Negative Sequence Protection?
Negative sequence protection detects current unbalance in a three-phase electrical system.
A balanced three-phase system contains positive sequence current but ideally no negative sequence current.
Unbalanced conditions create negative sequence components.
Typical causes include:
- Single-phase faults.
- Phase-to-phase faults.
- Unequal phase loading.
- Open-phase conditions.
- Incorrect connections.
- Unbalanced supply voltage.
8.2 Negative Sequence Current
The negative sequence current can be calculated using symmetrical components.
\[ I_2=\frac{1}{3}(I_a+a^2I_b+aI_c) \]
Where:
\[ a=1\angle120^\circ \]
The negative sequence component is important because it can produce additional heating in rotating electrical machines.
8.3 Applications
Negative sequence protection can be used for:
- Motor protection.
- Generator protection.
- Feeder unbalance detection.
- Phase failure detection.
- Equipment protection.
8.4 Setting Considerations
Important parameters include:
- Negative sequence pickup.
- Operating time.
- Time characteristic.
- Thermal withstand limitations.
- Alarm and trip thresholds.
For motor applications, the allowable negative sequence current and duration should be checked against the motor manufacturer’s specifications.
9. Sepam Thermal Overload Protection (ANSI 49)
9.1 Why Is Thermal Protection Necessary?
Electrical equipment can be damaged by excessive temperature even when the current is not high enough to cause instantaneous overcurrent operation.
Thermal overload protection estimates the thermal condition of the protected equipment.
The protection function generally uses a thermal model based on measured current and configured thermal parameters.
9.2 Thermal Model
The thermal state can be represented conceptually by:
\[ \frac{d\theta}{dt}= \frac{I^2}{I_{ref}^2}-\frac{\theta}{\tau} \]
Where:
- \(\theta\) = normalized thermal state.
- \(I\) = measured current.
- \(I_{ref}\) = reference current.
- \(\tau\) = thermal time constant.
Actual Sepam thermal algorithms may include separate heating and cooling characteristics and other model-specific parameters.
9.3 Thermal Overload Applications
- MV induction motors.
- Transformers.
- Feeders.
- Cables.
- Other electrical equipment, depending on the application.
9.4 Important Settings
Typical parameters may include:
- Rated current.
- Thermal overload pickup.
- Thermal time constant.
- Heating characteristic.
- Cooling characteristic.
- Alarm threshold.
- Trip threshold.
- Thermal restart inhibition.
For motor protection, the motor’s rated current, service factor, starting duty, permissible stall time, and thermal withstand data must be considered.
10. Sepam Undervoltage and Overvoltage Protection (ANSI 27/59)
10.1 Undervoltage Protection (27)
Undervoltage protection detects when the measured voltage falls below a configured threshold.
Possible causes include:
- Network disturbances.
- Short circuits.
- Transformer problems.
- Supply interruptions.
- Excessive loading.
- Generator instability.
The operating principle is:
\[ V<V_{27} \]
Applications include:
- Motor protection.
- Feeder protection.
- Load shedding.
- Supply supervision.
- Automatic transfer schemes.
10.2 Overvoltage Protection (59)
Overvoltage protection detects when voltage exceeds the configured threshold.
\[ V>V_{59} \]
Potential causes include:
- Load rejection.
- Incorrect voltage regulation.
- Generator operating problems.
- Neutral displacement.
- Switching operations.
- Network disturbances.
10.3 Important Settings
- Phase-to-phase or phase-to-neutral voltage selection.
- Pickup threshold.
- Operating delay.
- Reset threshold.
- Number of phases required for operation.
- VT supervision.
- Alarm or trip assignment.
Voltage protection settings must consider the system’s nominal voltage, VT ratio, voltage operating range, and equipment withstand levels.
11. Sepam Motor Starting and Stall Protection
Motor protection requires more than conventional overcurrent protection because an induction motor draws high current during starting.
11.1 Motor Starting Current
When an induction motor starts, its current can be several times its rated current.
The starting current depends on:
- Motor design.
- Motor power rating.
- Starting method.
- Supply voltage.
- Mechanical load.
- Starting conditions.
A protection relay must distinguish between a normal starting condition and an abnormal motor condition.
11.2 Motor Starting Supervision
Motor starting supervision monitors the starting process and checks whether the motor accelerates within the permitted time.
Important parameters include:
- Motor rated current.
- Starting current.
- Maximum starting time.
- Starting current threshold.
- Number of starts.
- Starting interval.
- Thermal state before starting.
11.3 Motor Stall Protection
A motor stall occurs when the motor fails to accelerate or stops rotating while energized.
Possible causes include:
- Mechanical jamming.
- Excessive load torque.
- Low supply voltage.
- Mechanical failure.
- Starting under excessive load.
Stall protection identifies abnormal current and operating conditions and initiates a trip before the motor is damaged.
11.4 Motor Protection Settings
A typical motor protection study should include:
| Parameter | Required information |
|---|---|
| Rated current | Motor nameplate |
| Starting current | Manufacturer data |
| Starting time | Actual application |
| Locked rotor withstand | Manufacturer data |
| Thermal time constant | Motor data |
| Number of starts | Process requirements |
| Cooling time | Motor manufacturer |
| Stall protection | Motor operating characteristics |
Motor starting and stall functions must be coordinated with thermal overload protection to prevent conflicting operation.
12. Sepam Motor Differential Protection (ANSI 87M)
12.1 What Is Motor Differential Protection?
Motor differential protection detects internal faults within the stator winding protection zone.
It compares currents entering and leaving the protected motor winding.
Under normal conditions:
\[ I_{diff}\approx 0 \]
During an internal fault, the current difference increases.
12.2 Operating Principle
A differential protection scheme generally uses CTs installed at both ends of the protected winding.
The relay compares the measured currents after considering CT ratios, polarity, and compensation.
A simplified differential current expression is:
\[ I_{diff}=|I_1-I_2| \]
Actual percentage differential schemes use restraint current and a biased operating characteristic.
12.3 Types of Motor Internal Faults
- Phase-to-phase faults.
- Three-phase stator faults.
- Phase-to-earth faults, depending on winding and grounding arrangements.
12.4 Important Engineering Considerations
- CT ratio matching.
- CT polarity.
- CT accuracy and saturation.
- Differential stability.
- Minimum pickup.
- Percentage bias.
- Protected zone definition.
- Motor terminal arrangement.
Important model limitation: Motor differential protection is not a universal function of every Sepam motor relay. It must be implemented using a Sepam model and protection arrangement specifically supporting the required differential scheme. Do not assume that Sepam M20, M41 or M87 provides identical functions or that all support 87M. Verify the exact model documentation and hardware configuration.
13. Sepam Capacitor Bank Protection
13.1 Why Do Capacitor Banks Require Protection?
Capacitor banks are commonly installed in MV distribution systems to improve power factor and provide reactive power compensation.
However, capacitor banks can experience abnormal conditions that require dedicated protection.
Common problems include:
- Capacitor unit failure.
- Internal element breakdown.
- Overcurrent.
- Overvoltage.
- Unbalanced capacitor current.
- Harmonic overloading.
- Switching transients.
- Excessive temperature.
13.2 Main Protection Functions
| Protection function | ANSI code |
|---|---|
| Phase overcurrent | 50/51 |
| Earth fault | 50N/51N |
| Overvoltage | 59 |
| Undervoltage | 27 |
| Unbalance protection | Application-specific |
| Thermal overload | 49 |
| Switching supervision | Application-specific |
13.3 Capacitor Bank Unbalance Protection
Capacitor bank failures can change the capacitance distribution between phases or sections.
This may produce an unbalanced current or voltage condition.
Depending on the capacitor bank design, unbalance protection may use:
- Neutral current.
- Neutral voltage.
- Residual current.
- Phase current comparison.
- Voltage comparison.
The correct protection method depends on whether the bank is connected in grounded star, ungrounded star, double star, or delta configuration.
13.4 Capacitor Bank Engineering Considerations
- Capacitor rated voltage.
- Rated reactive power.
- Switching frequency.
- Inrush current.
- Discharge time.
- Harmonic conditions.
- Fuse coordination.
- Reactor configuration.
- Bank grounding arrangement.
- Circuit breaker switching duty.
Capacitor bank protection must be designed according to the manufacturer’s recommendations and applicable standards.
14. Practical MV Feeder Protection Projects
Theoretical knowledge becomes valuable when engineers can apply it to actual protection schemes.
This section introduces practical engineering projects that can be developed using Sepam relays.
Project 1: MV Feeder Overcurrent Protection
Objective: Configure a Sepam relay for an outgoing MV feeder.
Scope:
- Study the single-line diagram.
- Identify CT ratios.
- Calculate maximum load current.
- Obtain maximum and minimum fault levels.
- Calculate phase overcurrent pickup.
- Select the appropriate time characteristic.
- Configure instantaneous protection.
- Coordinate with downstream protection.
- Perform secondary injection testing.
- Verify circuit breaker trip operation.
Project 2: Directional Overcurrent Protection
Objective: Implement directional protection for a ring-connected MV distribution system.
Scope:
- Review the network topology.
- Identify forward and reverse fault directions.
- Check CT and VT connections.
- Configure directional characteristics.
- Calculate pickup values.
- Coordinate the operating times.
- Test forward and reverse operation.
- Verify directional stability.
Project 3: Earth Fault Protection
Objective: Configure earth fault protection for a resistance-earthed MV network.
Scope:
- Study the neutral grounding arrangement.
- Calculate expected earth fault current.
- Select the earth fault measurement method.
- Configure the residual current input.
- Calculate pickup and time delay.
- Coordinate with upstream protection.
- Test earth fault pickup and trip.
- Verify correct alarm and trip signals.
Project 4: Sensitive Earth Fault Protection
Objective: Detect low-current earth faults in an MV network.
Scope:
- Identify the network earthing method.
- Calculate the capacitive earth fault current.
- Select a suitable CBCT.
- Verify CT accuracy and wiring.
- Calculate the sensitive pickup.
- Configure the operating delay.
- Test low-current injection.
- Verify security during normal operation.
Project 5: MV Motor Protection
Objective: Develop a complete motor protection scheme.
Scope:
- Collect motor nameplate information.
- Review motor starting characteristics.
- Calculate CT ratio.
- Configure phase overcurrent protection.
- Configure thermal overload protection.
- Configure negative sequence protection.
- Configure starting supervision.
- Configure stall protection.
- Configure undervoltage protection.
- Test motor trip and alarm logic.
Project 6: Motor Differential Protection
Objective: Develop a differential protection scheme for an MV motor.
Scope:
- Identify motor winding configuration.
- Define the differential protection zone.
- Select CTs at both ends.
- Verify CT polarity.
- Configure differential pickup.
- Configure restraint characteristics.
- Perform stability tests.
- Perform differential operating tests.
- Verify trip circuit operation.
The project must use a compatible differential relay arrangement.
Project 7: Capacitor Bank Protection
Objective: Develop a protection scheme for an MV capacitor bank.
Scope:
- Review capacitor bank configuration.
- Calculate rated current.
- Select CT ratios.
- Configure overcurrent protection.
- Configure earth fault protection.
- Configure overvoltage protection.
- Develop unbalance protection.
- Review inrush and switching conditions.
- Perform secondary injection tests.
- Verify trip and alarm functions.
15. Sepam Relay Configuration and Engineering Software
Sepam relays are configured and managed using Schneider Electric engineering tools, with the exact software depending on the relay generation and model.
One of the important engineering tools is SFT2841.
15.1 Main Engineering Activities
Typical engineering activities include:
- Relay model identification.
- Protection function configuration.
- CT and VT ratio configuration.
- Protection setting entry.
- Logic configuration.
- Input and output assignment.
- Communication configuration.
- Measurement verification.
- Event retrieval.
- Fault record analysis.
15.2 Offline Configuration
Offline configuration allows engineers to prepare relay parameters without connecting directly to the relay.
A typical workflow includes:
- Create or open a relay configuration.
- Select the correct Sepam model.
- Configure measurement inputs.
- Enable the required protection functions.
- Enter protection settings.
- Configure logic and outputs.
- Save the configuration.
- Review the settings before downloading.
15.3 Online Configuration
Online engineering involves connecting to the physical relay.
Typical activities include:
- Reading existing settings.
- Comparing actual and approved settings.
- Uploading configuration.
- Downloading approved changes.
- Monitoring measurements.
- Checking protection status.
- Retrieving events and fault records.
Always maintain a backup of the original relay configuration before making changes.
16. Sepam Protection Testing and Commissioning
Protection testing is essential to verify that the configured protection functions operate correctly.
A complete commissioning procedure should include the following.
16.1 Visual Inspection
- Verify relay model.
- Check auxiliary power supply.
- Check CT wiring.
- Check VT wiring.
- Verify grounding.
- Check trip circuit wiring.
- Check terminal connections.
16.2 Secondary Injection Testing
A relay test set, such as an OMICRON CMC system, can be used to inject controlled current and voltage signals.
Typical tests include:
- Phase overcurrent pickup.
- Instantaneous overcurrent operation.
- Inverse-time characteristics.
- Directional operation.
- Earth fault pickup.
- Sensitive earth fault pickup.
- Negative sequence operation.
- Thermal overload operation.
- Undervoltage operation.
- Overvoltage operation.
16.3 Timing Tests
For time-dependent protection functions, measure the actual operating time and compare it with the expected relay characteristic.
For example, an inverse-time protection test should verify multiple current injection points.
16.4 Functional Testing
Functional tests should verify:
- Relay trip output.
- Alarm output.
- Circuit breaker trip.
- Circuit breaker status feedback.
- Protection indications.
- Event recording.
- Communication signals.
16.5 End-to-End System Verification
Where applicable, verify the complete protection chain:
CT/VT → Protection relay → Trip output → Trip circuit → Circuit breaker.
A successful relay injection test alone does not prove that the complete protection system is operational.
17. Common Sepam Protection Problems and Troubleshooting
| Problem | Possible cause | Recommended investigation |
|---|---|---|
| Unwanted overcurrent trip | Incorrect pickup or coordination | Review load and fault calculations |
| Earth fault alarm during normal operation | CT wiring or measurement errors | Check residual current measurement |
| Directional protection operates incorrectly | CT/VT polarity error | Verify phase sequence and polarity |
| Motor trips during starting | Incorrect thermal or starting settings | Review motor starting characteristics |
| Thermal overload alarm | Excessive loading or incorrect model | Check thermal parameters and load |
| Undervoltage trip | Incorrect VT ratio or threshold | Verify voltage measurement |
| Capacitor bank unbalance alarm | Failed capacitor elements or wiring | Inspect bank configuration |
| Relay communication failure | Incorrect settings or interface problems | Check communication configuration |
| Circuit breaker fails to trip | Trip circuit problem | Check DC supply, trip coil and wiring |
18. Recommended Standards and Engineering References
Sepam protection engineering should be based on applicable IEC and IEEE standards, manufacturer documentation, and the project’s protection philosophy.
Useful references include:
- IEC 60255 series — Measuring relays and protection equipment.
- IEC 60909 — Short-circuit currents in three-phase AC systems.
- IEC 60034 — Rotating electrical machines.
- IEC 62271 series — High-voltage switchgear and controlgear.
- IEC 61869 series — Instrument transformers.
- IEC 60269 — Low-voltage fuses, where relevant to auxiliary and associated circuits.
- IEEE C37 series — Power switchgear and protection-related standards.
- Schneider Electric Sepam model-specific user manuals.
- Schneider Electric Sepam application and setting guides.
The applicable editions and project requirements should always be checked.
19. Practical Sepam Protection Engineering: What Engineers Should Be Able to Do
After studying the topics covered in this article, protection engineers should be able to:
- Identify suitable Sepam relay families for MV feeder and motor applications.
- Understand the main Sepam protection functions.
- Calculate phase overcurrent pickup values.
- Select inverse-time and definite-time characteristics.
- Understand directional overcurrent protection.
- Design earth fault protection schemes.
- Apply sensitive earth fault protection.
- Understand negative sequence protection.
- Configure thermal overload protection.
- Apply undervoltage and overvoltage protection.
- Develop motor starting and stall protection schemes.
- Understand motor differential protection arrangements.
- Develop capacitor bank protection schemes.
- Configure protection settings using appropriate Sepam engineering software.
- Perform secondary injection testing.
- Troubleshoot common relay and protection system problems.
- Verify the complete CT-to-circuit-breaker protection chain.
20. Sepam Protection Relay Training by Dr. Saeed Roostaee – Elec-Engg
Elec-Engg provides practical power system protection and substation automation training by Dr. Saeed Roostaee / Elec-Engg.
Our training approach focuses on real engineering applications rather than only explaining theoretical protection principles.
Sepam-related training can cover:
- Sepam relay families and applications.
- Feeder protection engineering.
- Overcurrent and directional overcurrent protection.
- Earth fault and sensitive earth fault protection.
- Motor protection.
- Transformer and equipment protection.
- Protection coordination and grading.
- CT and VT selection and connections.
- Protection relay configuration.
- Relay testing and commissioning.
- Practical protection troubleshooting.
Related Training Areas
Engineers interested in Sepam protection can also benefit from our training in:
- Power System Protection, Grading and Coordination.
- Protection Relay Testing and Commissioning.
- Motor Protection.
- Transformer Differential Protection.
- MV Feeder Protection.
- Schneider Electric Protection Relays.
- IEC 61850 and Substation Automation.
Explore training courses: https://elec-engg.com/
Training philosophy: Practical courses by Dr Saeed Roostaee / Elec-Engg, focused on helping engineers understand, configure, test, and troubleshoot real protection systems.
21. Conclusion
Sepam protection relays provide a range of protection and monitoring functions for medium-voltage distribution systems, industrial feeders, motors, and other electrical equipment.
A reliable protection scheme requires more than enabling individual protection functions. Engineers must understand the complete system, including CT and VT connections, fault levels, equipment characteristics, protection coordination, relay logic, circuit breaker operation, and commissioning requirements.
The most important protection functions covered in this article include:
- Phase overcurrent (50/51).
- Directional overcurrent (67).
- Earth fault (50N/51N).
- Sensitive earth fault.
- Negative sequence (46).
- Thermal overload (49).
- Undervoltage and overvoltage (27/59).
- Motor starting and stall protection.
- Motor differential protection (87M).
- Capacitor bank protection.
Combining these functions with proper engineering calculations, configuration, testing, and commissioning helps engineers develop reliable and selective MV protection systems.