Schneider Sepam Series 20 Protection Relays

Schneider Sepam Series 20 Protection Relays: Complete Guide to S20, S24, M20 and T20 Applications, Protection Functions, Settings and Testing

1. Introduction to Sepam Series 20

The Schneider Electric Sepam Series 20 is a family of numerical protection relays designed primarily for medium-voltage electrical distribution applications.

These relays provide protection, measurement and monitoring functions for electrical equipment such as:

  • Medium-voltage incoming feeders.
  • Outgoing distribution feeders.
  • Distribution transformers.
  • Induction motors.
  • Industrial electrical networks.

Sepam Series 20 was developed to provide reliable protection in conventional MV switchgear installations where straightforward protection functions, electrical measurements and basic monitoring are required.

The relay receives electrical signals from current transformers (CTs), and, depending on the model, voltage transformers (VTs). It processes these signals using numerical protection algorithms and operates its output contacts when configured protection conditions are satisfied.

Typical functions include phase overcurrent, earth fault, thermal overload and other application-dependent protection functions.

2. Sepam Series 20 Product Architecture

Sepam Series 20 relays combine several functional elements in a compact numerical protection device.

The main components include:

  1. Current measurement inputs.
  2. Voltage measurement inputs, depending on model.
  3. Numerical processing unit.
  4. Protection function algorithms.
  5. Binary input circuits.
  6. Binary output contacts.
  7. Local display and operator interface, depending on reference.
  8. Communication facilities, where supported.
  9. Auxiliary power supply.

3. Sepam Series 20 Models and Applications

Sepam Series 20 includes different relay references intended for different electrical applications.

The exact model and available functions must be verified using the corresponding Schneider Electric technical documentation.

3.1 Sepam S20 — Feeder Protection

Sepam S20 is intended for basic feeder protection applications.

Typical applications include:

  • MV outgoing feeders.
  • Distribution feeder protection.
  • Industrial power distribution.
  • Radial electrical networks.

The protection requirements can include phase overcurrent and earth fault protection, depending on the selected configuration.

3.2 Sepam S24 — Feeder Protection Applications

Sepam S24 belongs to the feeder protection family.

It is used in applicable MV distribution installations requiring feeder protection and associated monitoring functions.

When specifying S24, engineers should check its exact measurement, protection, input/output and communication capabilities rather than assuming all Series 20 models have identical functionality.

3.3 Sepam M20 — Motor Protection

Sepam M20 is associated with motor protection applications.

Typical protection requirements include:

  • Phase overcurrent.
  • Thermal overload.
  • Earth fault.
  • Starting supervision.
  • Abnormal current detection.

Motor protection settings must consider rated motor current, starting characteristics, acceleration time and thermal withstand capability.

3.4 Sepam T20 — Transformer Protection

Sepam T20 is intended for applicable transformer protection applications.

Typical requirements include:

  • Phase overcurrent protection.
  • Earth fault protection.
  • Transformer overload supervision.
  • Backup protection.
  • External transformer alarm and trip integration.

The protection scheme must also consider transformer rating, CT ratios, grounding arrangement and upstream/downstream coordination.

4. Sepam Series 20 Protection Functions

The available functions depend on the specific relay reference.

Important protection functions associated with Series 20 applications include:

ANSIProtection functionApplication
50/51Phase overcurrentFeeder protection
50N/51NEarth faultGround fault protection
49Thermal overloadEquipment protection
46Negative sequenceCurrent unbalance
37UndercurrentLoad supervision
27UndervoltageVoltage supervision
59OvervoltageVoltage supervision

This table is an application-oriented reference, not a claim that every function is available on every S20, S24, M20 or T20 reference.

5. Phase Overcurrent Protection (50/51)

Phase overcurrent protection is a fundamental function in MV distribution networks.

The relay continuously measures phase currents and compares them with configured pickup thresholds.

Two principal operating modes are used.

Instantaneous overcurrent (50)

The relay operates when the measured current exceeds the configured threshold, subject to the function’s operating characteristics.

Time overcurrent (51)

The relay operates according to a time-current characteristic.

Common characteristics include:

  • Definite time.
  • Standard inverse.
  • Very inverse.
  • Extremely inverse.

The selected characteristic must coordinate with other protection devices in the network.

5.1 Example of Overcurrent Setting Calculation

Consider an MV feeder with:

  • Rated load current: 250 A.
  • CT ratio: 300/1 A.
  • Proposed pickup setting: 1.2 times rated load current.

The primary pickup current is:

\[ I_{pickup}=250\times1.2=300A \]

The equivalent CT secondary current is:

\[ I_{secondary}=\frac{300}{300}=1A \]

The engineer must confirm that the proposed setting is suitable for the actual maximum load, minimum fault current, CT characteristics and protection coordination study.

6. Earth Fault Protection (50N/51N)

Earth fault protection detects current associated with phase-to-earth faults.

Depending on the relay and installation, residual current can be measured using:

  • Three-phase CT residual connection.
  • Dedicated core-balance CT.
  • Separate earth fault measurement arrangements.

The engineer must verify the supported measurement method and relay input requirements.

Important engineering considerations include:

  • Neutral grounding method.
  • Minimum earth fault current.
  • CT ratio and accuracy.
  • Earth fault pickup.
  • Operating time.
  • Coordination with upstream and downstream devices.

7. Sepam M20 Motor Protection Applications

Motor protection requires a coordinated combination of electrical and thermal protection functions.

Important motor parameters include:

  • Rated voltage.
  • Rated current.
  • Rated power.
  • Power factor.
  • Efficiency.
  • Starting current.
  • Starting time.
  • Permissible locked-rotor time.
  • Thermal withstand characteristics.

7.1 Thermal Overload Protection

Thermal overload protection monitors the motor’s estimated thermal condition.

It helps prevent excessive heating caused by prolonged overloading.

7.2 Starting Supervision

Motor starting supervision evaluates starting current and duration.

This helps identify abnormal starting conditions, such as excessive starting time or failure to accelerate.

7.3 Earth Fault Protection

Earth fault protection detects insulation-related faults and abnormal leakage current.

The sensitivity must be appropriate for the motor installation and earthing arrangement.

8. Sepam T20 Transformer Protection Applications

Transformer protection must consider both electrical fault conditions and equipment thermal limitations.

Sepam series 20 Transformer Type T20 – 50/51, 50N/51N, 50G/51G, 46,49RMS, 38/49T

Typical transformer protection functions include:

  • Phase overcurrent.
  • Earth fault.
  • Overload supervision.
  • External transformer trip integration.
  • Backup protection.

Transformer protection engineering should include:

  1. Transformer rated power.
  2. Primary and secondary voltages.
  3. Vector group.
  4. Impedance voltage.
  5. Neutral grounding arrangement.
  6. CT ratios.
  7. Maximum and minimum fault currents.
  8. Upstream and downstream coordination.

A conventional overcurrent protection relay should not automatically be considered a substitute for a dedicated transformer differential protection system.

9. Sepam Series 20 Engineering Software

Sepam Series 20 relays can be configured and monitored using Schneider Electric’s SFT2841 engineering software, subject to model and software-version compatibility.

Can Remote Control be enabled from the advanced UMI of the Sepam Series 20, 40 and 80 Relay? | Schneider Electric India

How to configure the “Logic Discrimination” in SEPAM series 40, hard wire connection (I/O)? | Schneider Electric Canada

Typical engineering activities include:

  • Relay identification.
  • Configuration retrieval.
  • Protection parameter configuration.
  • CT and VT parameter configuration.
  • Input/output assignment.
  • Protection setting management.
  • Measurement monitoring.
  • Event retrieval.
  • Diagnostic information review.

9.1 Creating a New Engineering Project

A typical workflow is:

  1. Install the compatible SFT2841 version.
  2. Identify the exact Sepam relay reference.
  3. Select the corresponding device in the software.
  4. Create a new configuration.
  5. Configure measurement parameters.
  6. Enter CT and VT ratios.
  7. Configure available protection functions.
  8. Enter protection settings.
  9. Configure binary inputs and outputs.
  10. Save and validate the configuration.

9.2 Online Configuration

Online engineering involves establishing communication between the engineering computer and the Sepam relay.

Typical activities include:

  • Reading existing settings.
  • Monitoring electrical measurements.
  • Reviewing relay status.
  • Retrieving events.
  • Performing supported configuration operations.

Always preserve the original relay configuration before making changes.

10. Sepam Series 20 Protection Settings

Protection settings must be calculated according to the electrical network and equipment characteristics.

The following parameters are particularly important.

ParameterEngineering consideration
CT ratioMatch installed CTs
Phase pickupMaximum load and minimum fault current
Earth fault pickupGrounding arrangement and fault sensitivity
Time delayProtection coordination
Curve selectionUpstream/downstream grading
Thermal parametersEquipment withstand capability
Binary logicCorrect trip and alarm operation

10.1 Protection Coordination

For an MV feeder, the Sepam relay should coordinate with:

  • Downstream feeder protection.
  • Upstream incomer protection.
  • Transformer protection.
  • Circuit breaker operating time.
  • Equipment thermal withstand limits.

The objective is to isolate the smallest possible faulty section while maintaining protection backup.

10.2 Setting Verification

Before applying settings:

  1. Check the approved protection study.
  2. Verify the relay model.
  3. Confirm CT and VT ratios.
  4. Check pickup values.
  5. Verify time-current characteristics.
  6. Review trip logic.
  7. Check output assignments.
  8. Save the approved configuration.

11. Sepam Series 20 Testing and Commissioning

Testing is essential before energizing a protected circuit.

The commissioning process should verify the complete protection chain, not simply the numerical relay’s internal operation.

11.1 Visual Inspection

Inspect:

  • Relay identification.
  • Auxiliary supply.
  • CT connections.
  • VT connections, where applicable.
  • Binary input wiring.
  • Binary output wiring.
  • Trip circuit.
  • Communication connections.

11.2 Secondary Injection Testing

Secondary injection testing verifies the relay’s protection functions using a suitable relay test system.

Typical tests include:

TestPurpose
Phase current injectionVerify current measurement
Overcurrent pickupVerify pickup threshold
Operating timeVerify relay timing
Earth fault injectionVerify earth fault operation
Thermal protectionVerify applicable thermal characteristics
Binary input testVerify external signal detection
Binary output testVerify output contact operation
Trip circuit testVerify circuit breaker trip chain

11.3 Binary Input and Output Testing

Binary inputs should be checked against the approved control and protection drawings.

Typical signals include:

  • Circuit breaker open.
  • Circuit breaker closed.
  • External trip.
  • Local/remote selection.
  • Protection blocking.
  • Interlocking signals.

Binary outputs should be checked for correct assignment and operation.

11.4 Circuit Breaker Trip Testing

A complete trip test should verify:

  1. Protection element operation.
  2. Relay trip logic.
  3. Output contact operation.
  4. Trip circuit continuity.
  5. Circuit breaker trip coil operation.
  6. Circuit breaker opening.
  7. Breaker auxiliary contact feedback.

11.5 Final Commissioning Report

The commissioning report should include:

  • Relay model and serial number.
  • Hardware and firmware information.
  • Approved settings.
  • CT and VT details.
  • Test equipment identification.
  • Protection test results.
  • Binary input/output results.
  • Trip circuit results.
  • Communication results.
  • Outstanding defects.
  • Final commissioning approval.

12. Common Sepam Series 20 Troubleshooting

ProblemPossible causeInvestigation
Relay does not startAuxiliary supply failureCheck supply and wiring
Incorrect current valuesCT ratio or wiring errorVerify CT configuration
Unexpected tripIncorrect settings or external signalReview event records
Earth fault indicationActual fault or measurement problemCheck network and CT circuits
SFT2841 communication failureIncorrect interface or compatibilityVerify connection and software
Binary input unavailableWiring or assignment issueCheck input configuration
Trip output not operatingLogic or output circuit problemVerify trip assignment and wiring
Incorrect protection timingCurve or setting errorReview settings and injection results

13. Practical Engineering Case Study: MV Feeder Protection

Consider an industrial MV distribution feeder supplying an auxiliary transformer.

System information

ParameterValue
System voltage11 kV
Transformer rating2.5 MVA
Transformer primary current131.2 A
Feeder CT ratio200/1 A
Protection relayApplicable Sepam Series 20 model
Main protectionPhase overcurrent and earth fault
Circuit breakerMV vacuum circuit breaker

Transformer primary rated current:

\[ I=\frac{S}{\sqrt{3}\times V} \]

\[ I=\frac{2500}{\sqrt{3}\times11} \]

\[ I\approx131.2A \]

Assuming a 200/1 A CT:

\[ I_s=\frac{131.2}{200}=0.656A \]

This represents the approximate secondary current at transformer rated load.

The protection engineer must then calculate suitable overcurrent and earth fault settings based on the network fault study, transformer characteristics, loading conditions and coordination requirements.

The final settings must be validated against the actual Sepam model’s supported ranges and characteristics.

14. Important Engineering Recommendations

When working with Sepam Series 20 installations, consider the following:

  • Always identify the complete relay reference before starting engineering.
  • Do not assume S20, S24, M20 and T20 have identical functions.
  • Verify the applicable SFT2841 software version.
  • Confirm CT and VT connection arrangements.
  • Check the actual relay configuration before modifying settings.
  • Preserve existing configuration files.
  • Perform secondary injection tests.
  • Verify the complete circuit breaker trip chain.
  • Review event records after testing.
  • Check Schneider Electric documentation for product lifecycle and replacement information.

15. Sepam Protection Relay Training by Elec-Engg

Practical Protection Relay Engineering Training

Elec-Engg provides professional training and technical resources for engineers involved in power system protection, substation automation, relay testing and commissioning.

Relevant training subjects include:

  • Schneider Sepam protection relay architecture.
  • Sepam Series 20, 40, 60 and 80.
  • SFT2841 engineering software.
  • Feeder protection settings.
  • Transformer protection.
  • Motor protection.
  • CT and VT engineering.
  • Protection coordination and grading.
  • Omicron CMC secondary injection testing.
  • Binary input/output testing.
  • Relay troubleshooting.
  • SCADA and IEC 61850 integration.

Practical courses by Dr Saeed Roostaee / Elec-Engg

Our training approach focuses on practical engineering applications, real protection problems and the skills required by protection, commissioning, operation and maintenance engineers.

Explore available courses:

  • Elec-Engg Training Platform
  • Training Courses
  • Substation Automation Courses

16. Conclusion

Schneider Sepam Series 20 provides numerical protection solutions for conventional medium-voltage feeder, motor and transformer applications.

Understanding the differences between relay models, their protection functions, engineering software, settings and testing procedures is essential for successful implementation.

For protection engineers, practical knowledge of CT and VT circuits, overcurrent coordination, earth fault protection, secondary injection testing and circuit breaker trip verification is particularly important.

Sepam Series 20 remains relevant when maintaining and engineering existing installations, making knowledge of its configuration and troubleshooting procedures valuable for electrical engineers.