Sepam Transformer Protection

Sepam Transformer Protection: Complete Guide to Transformer Differential Protection, REF, Overcurrent, Earth Fault, Thermal Protection, Overfluxing, Inrush Restraint, CT Selection, Settings and Testing

Practical Power Transformer Protection Engineering Using Schneider Electric Sepam Relays

Table Of Contents
  1. 1. Sepam Transformer Protection Overview
  2. 2. Transformer Differential Protection (ANSI 87T)
  3. 3. Restricted Earth Fault Protection (ANSI 64REF)
  4. 4. Transformer Overcurrent Protection (ANSI 50/51)
  5. 5. Transformer Earth Fault Protection (ANSI 50N/51N)
  6. 6. Transformer Thermal Protection (ANSI 49)
  7. 7. Transformer Overfluxing Protection (ANSI 24)
  8. 8. Transformer Inrush Current and Harmonic Restraint
  9. 9. Transformer CT Selection and Compensation
  10. 10. Transformer Protection Settings and Practical Engineering
  11. 11. Sepam Transformer Protection Configuration and Engineering Software
  12. 12. Transformer Protection Testing and Commissioning
  13. 13. Common Transformer Protection Problems and Troubleshooting
  14. 14. Practical Transformer Protection Engineering Case Study
  15. 15. Transformer Protection Engineering: Important Standards
  16. 16. Practical Sepam Transformer Protection Training by Elec-Engg
  17. 17. Frequently Asked Questions (FAQ)

Transformer protection is one of the most important functions in electrical power systems. Power transformers are critical and expensive assets in substations, industrial plants, power stations and distribution networks. Internal transformer faults, winding insulation failures, earth faults, overloading, overfluxing and abnormal operating conditions can cause severe equipment damage, extended outages and significant financial losses.

A properly engineered transformer protection system must detect internal faults rapidly, distinguish between internal and external faults, remain stable during transformer energization and external short circuits, and provide appropriate backup protection when primary protection fails.

Schneider Electric Sepam protection relays provide several protection functions for transformer applications, depending on the relay model, hardware configuration and application requirements.

This comprehensive technical guide covers Sepam transformer protection, including transformer differential protection (87T), restricted earth fault protection (64REF), overcurrent protection, earth fault protection, thermal protection, overfluxing protection, inrush current restraint, CT selection and compensation, protection settings, commissioning and practical testing.

The article is intended for protection engineers, electrical engineers, commissioning engineers, maintenance engineers and substation automation professionals.

1. Sepam Transformer Protection Overview

1.1 What Is Transformer Protection?

Transformer protection is the coordinated application of protective devices and schemes designed to identify abnormal operating conditions and isolate a faulty transformer before serious damage occurs.

Transformer faults can be classified into several categories:

  • Phase-to-phase winding faults.
  • Phase-to-earth winding faults.
  • Inter-turn winding faults.
  • Transformer bushing faults.
  • Internal insulation failures.
  • Core insulation faults.
  • Overloading and overheating.
  • Overfluxing caused by excessive voltage or low frequency.
  • External short circuits.
  • Abnormal operating conditions during energization.

The protection system must provide fast and selective fault detection while maintaining stability during normal operating conditions.

1.2 Main Transformer Protection Functions

The following ANSI protection functions are commonly used in transformer protection schemes.

ANSIProtection functionPurpose
87TTransformer differentialDetect internal phase faults
64REFRestricted earth faultDetect sensitive winding earth faults
50/51Phase overcurrentShort-circuit and backup protection
50N/51NEarth fault overcurrentDetect earth faults
49Thermal overloadProtect against overheating
24OverfluxingProtect against excessive V/Hz
27UndervoltageDetect low voltage
59OvervoltageDetect excessive voltage
46Negative sequenceDetect phase unbalance
50BFBreaker failureDetect failure of circuit breaker operation
86LockoutMaintain trip isolation following serious faults

Not every Sepam model supports every function. The available functions must be verified against the specific Sepam series, application and firmware.

1.3 Sepam Relay Selection for Transformer Applications

Schneider Electric Sepam protection relays are available in different series and application configurations.

Transformer protection engineering requires selecting a relay that supports the required protection functions, CT inputs, voltage measurements, communication facilities and trip logic.

Important selection considerations include:

  • Transformer rated power and voltage.
  • Number of transformer windings.
  • Transformer vector group.
  • Required differential protection.
  • REF protection requirements.
  • Phase and earth fault protection.
  • Thermal and overfluxing protection.
  • CT ratios and secondary ratings.
  • Number of current and voltage inputs.
  • Binary inputs and outputs.
  • Communication and SCADA requirements.

Engineering note: Sepam S20, S40, S80 and other variants have different capabilities. Do not assume that every Sepam relay supports transformer differential or REF protection. Confirm the applicable model documentation before designing the protection scheme.

2. Transformer Differential Protection (ANSI 87T)

2.1 Operating Principle

Transformer differential protection is the primary protection against internal phase faults in power transformers.

The principle is based on comparing the currents entering and leaving the protected transformer zone.

Under normal operating conditions, the currents are balanced after compensation for:

  • Transformer turns ratio.
  • Transformer vector group.
  • CT ratios.
  • Phase displacement.
  • Transformer tap changer position.
  • Zero-sequence current effects where applicable.

If an internal fault occurs, the difference between the compensated currents increases and the differential relay operates.

The basic differential current equation is:

\[ I_{diff}=|I_1-I_2| \]

Where:

  • \(I_1\): Compensated current from transformer side 1.
  • \(I_2\): Compensated current from transformer side 2.

The actual differential protection algorithm may use multiple winding currents and a specific bias calculation.

2.2 Transformer Differential Protection Characteristics

A percentage-biased differential characteristic is used to maintain stability during external faults and CT saturation.

A simplified operating criterion is:

\[ I_{diff}>I_{pickup}+S\times I_{bias} \]

Where:

  • \(I_{pickup}\): Minimum differential pickup.
  • \(S\): Bias or slope setting.
  • \(I_{bias}\): Restraint current.

The relay trips when the differential operating quantity exceeds the configured characteristic.

2.3 Differential Protection During Internal Faults

For an internal transformer fault, current flows into the fault from one or more transformer sides.

The differential currents no longer balance, producing an operating quantity that exceeds the differential characteristic.

Typical faults include:

  • Phase-to-phase winding faults.
  • Three-phase winding faults.
  • Phase-to-earth faults within the protected zone.
  • Internal bushing faults.
  • Severe inter-turn faults, depending on fault magnitude and sensitivity.

2.4 Differential Protection During External Faults

Consider a short circuit outside the transformer protection zone.

Current enters the transformer from one side and leaves through the other side.

After correct compensation, the differential relay should remain stable.

However, CT saturation during high external fault currents can produce a false differential current.

The percentage bias characteristic helps prevent unwanted operation.

2.5 Differential Protection Settings

Typical engineering parameters include:

ParameterEngineering consideration
Minimum differential pickupSensitivity to internal faults
Bias slope 1Stability at lower through currents
Bias slope 2Stability during high through currents
High-set differentialFast operation for severe internal faults
Inrush restraintStability during energization
Overexcitation restraintStability during abnormal V/Hz conditions
Vector group compensationCorrect phase displacement
CT ratio compensationMatching transformer-side currents

Actual values must be calculated for the transformer, CTs and relay application. There is no universally correct differential pickup or slope.

2.6 Transformer Differential Protection Testing

Testing should include:

  1. Verify CT ratios and polarity.
  2. Confirm transformer vector group.
  3. Verify phase compensation.
  4. Inject balanced through-current conditions.
  5. Verify differential stability.
  6. Inject differential operating current.
  7. Test bias characteristic points.
  8. Test high-set differential operation.
  9. Verify inrush restraint.
  10. Confirm trip output and event recording.

A secondary injection test set such as Omicron CMC can be used to simulate transformer-side currents and verify differential operating characteristics, provided the relay configuration supports the test method.

3. Restricted Earth Fault Protection (ANSI 64REF)

3.1 What Is REF Protection?

Restricted Earth Fault protection is a sensitive protection scheme used to detect earth faults within a defined transformer winding zone.

It is particularly useful for detecting winding-to-earth faults close to the transformer neutral point, where the fault current may be relatively low.

Transformer differential protection may have limited sensitivity to certain earth faults, particularly near the neutral end of a star-connected winding.

REF protection provides additional sensitivity within its restricted zone.

3.2 Operating Principle

A conventional REF scheme compares the residual current obtained from the three phase CTs with the current measured by the neutral CT.

The residual current is:

\[ I_{res}=I_A+I_B+I_C \]

The operating principle compares the phase CT residual current with the neutral CT current.

For a simplified scheme:

\[ I_{REF}=|I_{res}-I_N| \]

The exact polarity and operating equation depend on CT connection and relay implementation.

Under normal load and external earth fault conditions, the currents should balance.

For an internal earth fault within the protected zone, the balance is disturbed and the relay operates.

3.3 High-Impedance and Low-Impedance REF

Two common REF arrangements are:

High-impedance REF

  • Uses matched CT characteristics.
  • Requires careful CT selection.
  • Uses a stabilizing resistor.
  • May require a voltage-limiting device.
  • Requires stability calculations for external faults.

Low-impedance REF

  • Uses numerical relay measurement and operating algorithms.
  • Provides greater flexibility in CT matching.
  • Can use numerical bias or stabilization characteristics.
  • Requires correct CT polarity, ratio and relay configuration.

The actual REF implementation available in a Sepam installation must be confirmed from the relay model and application documentation.

3.4 REF Protection Applications

REF is commonly applied to:

  • Star-connected transformer windings with accessible neutral CTs.
  • Generator step-up transformer star windings.
  • Distribution transformer grounded star windings.
  • Power transformer windings requiring sensitive earth fault protection.

REF applicability depends on the grounding arrangement and the protection zone.

3.5 REF Settings

Important parameters include:

  • REF pickup current.
  • Neutral CT ratio.
  • Phase CT ratio.
  • CT polarity.
  • Stabilization or bias characteristic.
  • Operating delay.
  • Trip logic.

Settings should be determined from the transformer grounding system, fault current calculations, CT performance and relay application.

3.6 REF Testing

The testing procedure should include:

  1. Verify phase CT connections.
  2. Verify neutral CT polarity.
  3. Confirm CT ratios.
  4. Inject balanced current to verify stability.
  5. Simulate an external earth fault.
  6. Verify no unwanted operation.
  7. Simulate an internal earth fault.
  8. Verify REF pickup and trip.
  9. Check operating time.
  10. Verify trip matrix and disturbance records.

4. Transformer Overcurrent Protection (ANSI 50/51)

4.1 Purpose of Overcurrent Protection

Transformer overcurrent protection provides backup protection against excessive phase current.

It may also provide primary protection for smaller transformers where differential protection is not economically justified.

The two main functions are:

ANSI 50 — Instantaneous Overcurrent

Operates when the measured current exceeds a predefined high-set threshold.

ANSI 51 — Time-Delayed Overcurrent

Operates according to an inverse-time or definite-time characteristic.

4.2 Overcurrent Protection Characteristics

Common inverse-time characteristics include:

  • Standard inverse.
  • Very inverse.
  • Extremely inverse.
  • Definite time.

The IEC standard inverse characteristic can be expressed as:

\[ t=TMS\times\frac{0.14}{(I/I_s)^{0.02}-1} \]

Where:

  • \(t\): Operating time.
  • \(TMS\): Time multiplier setting.
  • \(I\): Measured current.
  • \(I_s\): Pickup current.

The exact available curves depend on the relay.

4.3 Transformer Overcurrent Setting Considerations

The pickup must be higher than the maximum expected operating current while remaining sufficiently sensitive to detect faults.

The engineer must consider:

  • Transformer rated current.
  • Maximum permissible loading.
  • Transformer impedance.
  • Downstream protection coordination.
  • Transformer inrush current.
  • Maximum and minimum fault levels.
  • CT ratio.
  • Breaker operating time.

Transformer rated current is calculated using:

\[ I_n=\frac{S_n}{\sqrt{3}\times V_n} \]

Where:

  • \(S_n\): Transformer rated apparent power.
  • \(V_n\): Rated line-to-line voltage.
  • \(I_n\): Rated line current.

4.4 Overcurrent Coordination

Transformer overcurrent protection must coordinate with:

  • Downstream feeder relays.
  • Upstream incomer protection.
  • Busbar protection.
  • Transformer differential protection.
  • Circuit breaker clearing times.

Time-current characteristic curves should be reviewed to avoid unnecessary simultaneous tripping.

5. Transformer Earth Fault Protection (ANSI 50N/51N)

5.1 Earth Fault Protection Principle

Earth fault protection detects current flowing through the earth return path during phase-to-earth faults.

The residual current is calculated as:

\[ I_0=I_A+I_B+I_C \]

The earth fault current is related to zero-sequence current:

\[ I_E=3I_0 \]

Depending on the relay convention, measured residual current may be expressed as \(3I_0\).

5.2 Types of Earth Fault Protection

Residual earth fault protection

Uses the residual sum of the three phase CT currents.

Neutral earth fault protection

Measures current through the transformer neutral grounding connection.

Sensitive earth fault protection

Uses a lower pickup setting to detect relatively low-magnitude earth faults.

Directional earth fault protection

Uses current and voltage quantities to determine the direction of the earth fault.

5.3 Transformer Neutral Grounding

Earth fault current depends strongly on the transformer neutral grounding arrangement.

Common arrangements include:

  • Solid grounding.
  • Resistance grounding.
  • Reactance grounding.
  • Resonant grounding.
  • Isolated neutral.

The grounding method determines the available earth fault current and therefore affects protection sensitivity and coordination.

5.4 Earth Fault Settings

Important parameters include:

  • Pickup current.
  • Time delay.
  • Operating curve.
  • Neutral CT ratio.
  • Residual current measurement.
  • Directional characteristics, if applicable.
  • Coordination with downstream earth fault protection.

The setting must be above normal residual measurement errors but below the minimum earth fault current that must be detected.

6. Transformer Thermal Protection (ANSI 49)

6.1 Why Thermal Protection Is Important

Transformer insulation life depends strongly on operating temperature.

Excessive temperature accelerates insulation ageing and can lead to premature transformer failure.

Thermal protection helps prevent damage caused by:

  • Prolonged overload.
  • High ambient temperature.
  • Cooling system failure.
  • Reduced cooling efficiency.
  • Excessive winding temperature.
  • Abnormal operating conditions.

6.2 Thermal Model

Numerical thermal protection can use current measurements and a thermal model to estimate the thermal state of the protected equipment.

A simplified first-order thermal model is:

\[ \frac{d\theta}{dt} = \frac{\theta_{\infty}-\theta}{\tau} \]

Where:

  • \(\theta\): Estimated thermal state.
  • \(\theta_{\infty}\): Final thermal state at the present load.
  • \(\tau\): Thermal time constant.

The actual transformer thermal model is more complex and may consider oil and winding temperature separately.

6.3 Thermal Protection Functions

Typical protection actions include:

  • Thermal alarm.
  • Overload warning.
  • Load reduction.
  • Cooling system activation.
  • Transformer trip.

Temperature monitoring may use separate transformer temperature instruments and supervisory systems.

Important: A Sepam current-based thermal overload function is not automatically equivalent to direct winding hot-spot temperature measurement. Confirm the available sensor inputs and thermal modeling capabilities of the selected relay.

6.4 Thermal Protection Settings

Important parameters include:

  • Rated current.
  • Thermal time constant.
  • Thermal alarm threshold.
  • Thermal trip threshold.
  • Cooling assumptions.
  • Maximum permissible loading.
  • Thermal reset characteristics.

Settings must be based on transformer manufacturer data and the applicable relay functionality.

7. Transformer Overfluxing Protection (ANSI 24)

7.1 What Is Overfluxing?

Overfluxing occurs when the magnetic flux in a transformer core exceeds its designed operating level.

It can result from:

  • Excessive applied voltage.
  • Reduced system frequency.
  • Incorrect generator voltage control.
  • Abnormal operating conditions.
  • Transformer operation outside its rated V/Hz range.

Excessive magnetic flux causes core saturation, increased magnetizing current, overheating and potentially severe insulation damage.

7.2 V/Hz Principle

Transformer magnetic flux is approximately proportional to the ratio of voltage to frequency:

\[ \Phi\propto\frac{V}{f} \]

The overfluxing quantity is commonly expressed as:

\[ V/Hz=\frac{V_{measured}/V_{rated}} {f_{measured}/f_{rated}} \]

When the V/Hz ratio exceeds the permitted limit, overfluxing protection operates.

7.3 Protection Characteristics

ANSI 24 protection may use:

  • Definite-time characteristics.
  • Inverse-time characteristics.
  • Alarm thresholds.
  • Trip thresholds.

The time characteristic should coordinate with the transformer manufacturer’s overexcitation withstand curve.

7.4 Overfluxing Settings

The engineer should consider:

  • Transformer rated voltage.
  • Rated frequency.
  • Maximum permissible V/Hz.
  • Transformer core design.
  • Manufacturer withstand data.
  • Operating voltage variations.
  • Frequency variations.
  • Alarm and trip coordination.

A generic V/Hz setting should not be applied without checking transformer manufacturer recommendations.

8. Transformer Inrush Current and Harmonic Restraint

8.1 What Is Transformer Inrush Current?

When a transformer is energized, a high transient magnetizing current may flow.

This current can be significantly greater than the normal rated current and may cause unwanted operation of differential protection if inrush restraint is not properly implemented.

Inrush current depends on:

  • Switching instant.
  • Residual magnetic flux.
  • Transformer core characteristics.
  • Source impedance.
  • Transformer connection.
  • Energization conditions.

8.2 Characteristics of Inrush Current

Typical inrush current characteristics include:

  • High initial magnitude.
  • Asymmetrical waveform.
  • Significant DC offset.
  • Harmonic components.
  • High second-harmonic content in many conventional cases.

8.3 Second-Harmonic Restraint

Differential protection may use second-harmonic content to distinguish magnetizing inrush current from internal fault current.

The harmonic ratio is commonly expressed as:

\[ H_2(\%)= \frac{I_2}{I_1}\times100 \]

Where:

  • \(I_2\): Second-harmonic current component.
  • \(I_1\): Fundamental-frequency current component.

If the harmonic content exceeds the configured restraint threshold, differential operation may be blocked or restrained according to the relay algorithm.

8.4 Other Restraint Methods

Modern transformer differential relays may also use:

  • Waveform recognition.
  • Current waveform analysis.
  • Cross-phase blocking.
  • Second-harmonic restraint.
  • Fifth-harmonic restraint for overexcitation discrimination.

The actual functions available depend on the Sepam relay model.

8.5 Inrush Protection Testing

Testing should verify:

  1. Differential stability during simulated inrush.
  2. Harmonic restraint operation.
  3. Differential operation for internal fault conditions.
  4. Security during transformer energization.
  5. Correct alarm and event indications.

Testing must verify that inrush restraint does not compromise dependable operation for genuine internal faults.

9. Transformer CT Selection and Compensation

9.1 Why CT Selection Is Critical

Current transformers provide the current signals required by transformer protection relays.

Incorrect CT selection, polarity, ratio or wiring can cause:

  • False differential current.
  • Unwanted tripping.
  • Reduced fault sensitivity.
  • Incorrect earth fault measurement.
  • CT saturation during external faults.
  • Protection instability.

9.2 CT Ratio Selection

The CT primary rating must be appropriate for the transformer rated current and expected operating conditions.

For example, consider a transformer rated:

  • Power: 40 MVA.
  • HV voltage: 110 kV.
  • LV voltage: 11 kV.

HV rated current:

\[ I_{HV}=\frac{40\times10^6} {\sqrt{3}\times110\times10^3} \]

\[ I_{HV}=209.95A \]

LV rated current:

\[ I_{LV}=\frac{40\times10^6} {\sqrt{3}\times11\times10^3} \]

\[ I_{LV}=2099.5A \]

Possible CT ratios for preliminary consideration could be:

  • HV: 250/1 A.
  • LV: 2500/1 A.

These are illustrative ratios only. Final selection requires checking burden, accuracy, protection class, fault current, saturation performance and relay input requirements.

9.3 CT Polarity

Correct CT polarity is essential for differential and REF protection.

The engineer must verify:

  • P1 and P2 primary markings.
  • S1 and S2 secondary markings.
  • Phase identification.
  • Relay current input polarity.
  • Neutral CT polarity.
  • Differential current direction.

Incorrect polarity can result in incorrect differential or residual current calculations.

9.4 Transformer Vector Group Compensation

Transformer vector groups introduce phase displacement between primary and secondary currents.

For example:

  • Dyn11.
  • Dyn1.
  • YNd11.
  • YNyn0.

The differential protection scheme must compensate for the transformer phase displacement.

Numerical relays may provide internal vector group compensation, depending on the model and application.

The engineer must verify the configured vector group against the transformer nameplate.

9.5 CT Saturation

CT saturation can occur during high short-circuit currents.

The following parameters should be considered:

  • CT accuracy class.
  • Knee-point voltage where applicable.
  • CT secondary resistance.
  • Lead resistance.
  • Relay burden.
  • Maximum symmetrical fault current.
  • DC offset and system X/R ratio.

CT performance must be evaluated to ensure stable protection during external faults.

10. Transformer Protection Settings and Practical Engineering

Transformer protection settings must be based on engineering calculations, system studies, transformer data and relay characteristics.

10.1 Required Transformer Data

Before preparing relay settings, collect:

ParameterRequired information
Transformer ratingMVA
HV rated voltagekV
LV rated voltagekV
FrequencyHz
Vector groupDyn11, YNd1, etc.
ImpedancePercentage
CoolingONAN, ONAF, OFAF, etc.
HV CT ratioPrimary/secondary
LV CT ratioPrimary/secondary
Neutral groundingSolid, resistance, reactance, etc.
Maximum fault levelkA
Minimum fault levelkA
Tap changer rangePercentage
Transformer temperature limitsManufacturer data

10.2 Main Protection Setting Parameters

ProtectionImportant settings
87TPickup, bias slopes, high-set
64REFPickup, stabilization, operating time
50/51Pickup, curve, time multiplier
50N/51NPickup, curve, time delay
49Thermal time constant, alarm, trip
24V/Hz pickup and time characteristic
46Negative-sequence pickup and delay
27/59Voltage thresholds and delay

The final settings should be checked against the actual relay configuration and the transformer protection philosophy.

10.3 Protection Coordination

The transformer protection scheme must coordinate with upstream and downstream protective devices.

Coordination studies should consider:

  • Transformer inrush current.
  • Transformer through-fault withstand.
  • Downstream feeder fault currents.
  • Upstream backup protection.
  • Transformer differential operating time.
  • Circuit breaker clearing time.
  • Earth fault protection sensitivity.
  • Thermal overload limits.

The objective is to isolate only the faulty section while preserving the availability of the remaining power system.

11. Sepam Transformer Protection Configuration and Engineering Software

11.1 Sepam Configuration

Sepam engineering requires correct selection and configuration of the relay model and application.

Typical engineering activities include:

  1. Identify the installed Sepam model.
  2. Verify hardware and firmware.
  3. Create or open the relay configuration.
  4. Configure CT and VT ratios.
  5. Configure protection functions.
  6. Enter calculated protection settings.
  7. Configure protection logic.
  8. Assign binary inputs and outputs.
  9. Configure trip circuits.
  10. Configure communication parameters.
  11. Transfer and verify settings.

11.2 SFT2841 Engineering Software

Schneider Electric SFT2841 is used for engineering and configuration of compatible Sepam protection relays.

Depending on the Sepam model and software version, engineering activities may include:

  • Relay configuration.
  • Protection setting adjustment.
  • Logic configuration.
  • Measurement monitoring.
  • Event retrieval.
  • Fault record analysis.
  • Communication configuration.

Software compatibility must be checked against the installed Sepam model and firmware.

11.3 Protection Logic

A transformer protection scheme should define the required actions for each protection function.

For example:

Protection functionTypical action
Differential 87TTransformer trip
REF 64REFTransformer trip
High-set overcurrent 50Trip
Time overcurrent 51Backup trip
Earth fault 50N/51NTrip or alarm according to scheme
Thermal 49Alarm and/or trip
Overfluxing 24Alarm and/or trip
Breaker failure 50BFTrip upstream breaker

The actual trip matrix depends on the protection philosophy and circuit breaker arrangement.

12. Transformer Protection Testing and Commissioning

Protection testing is necessary to verify that the complete protection system operates correctly under simulated fault conditions.

12.1 Pre-Commissioning Checks

Before testing:

  • Verify relay model and configuration.
  • Confirm transformer nameplate data.
  • Check CT ratios and polarity.
  • Verify CT wiring and earthing.
  • Check VT wiring.
  • Verify auxiliary DC supply.
  • Confirm binary input and output wiring.
  • Check trip circuit continuity.
  • Review protection settings.
  • Verify circuit breaker interfaces.

12.2 Secondary Injection Testing

Secondary injection testing verifies relay measurement and protection operation by injecting simulated current and voltage signals directly into the relay.

Common testing equipment includes:

  • Omicron CMC 356.
  • Omicron CMC 256plus.
  • Other compatible secondary injection test sets.

12.3 Differential Protection Test

The differential protection test should include:

  • Balanced current injection.
  • Differential current injection.
  • Bias characteristic testing.
  • High-set differential testing.
  • Inrush restraint testing.
  • Trip output verification.

12.4 Overcurrent Protection Test

Test the following:

  • Pickup current.
  • Reset current.
  • Operating time.
  • Inverse-time curve.
  • High-set operation.
  • Trip output.

12.5 Earth Fault and REF Testing

Test:

  • Residual current measurement.
  • Neutral current measurement.
  • Earth fault pickup.
  • Operating delay.
  • REF stability.
  • REF operating condition.
  • Trip matrix.

12.6 Thermal and Overfluxing Testing

Verify:

  • Thermal alarm threshold.
  • Thermal trip threshold.
  • Thermal reset behavior.
  • V/Hz measurement.
  • Overfluxing pickup.
  • Overfluxing time characteristic.

12.7 End-to-End Functional Testing

The final commissioning process should verify the entire protection chain:

  1. CT and VT secondary circuits.
  2. Protection relay measurement.
  3. Protection function operation.
  4. Internal relay logic.
  5. Binary output operation.
  6. Trip relay operation.
  7. Circuit breaker trip.
  8. Alarm and indication.
  9. SCADA signal transmission.
  10. Event and disturbance record generation.

12.8 Commissioning Documentation

The final test report should include:

  • Relay model and serial number.
  • Transformer technical data.
  • CT and VT information.
  • Approved protection settings.
  • Test equipment details.
  • Injection values.
  • Pickup and operating times.
  • Trip circuit verification.
  • Test results.
  • Deviations and corrective actions.
  • Commissioning approval.

13. Common Transformer Protection Problems and Troubleshooting

Transformer protection commissioning and maintenance engineers frequently encounter problems related to incorrect settings, CT wiring, relay configuration and protection coordination.

13.1 Unwanted Differential Protection Operation

Possible causes:

  • Incorrect CT polarity.
  • Incorrect CT ratio.
  • Incorrect transformer vector group.
  • Incorrect phase compensation.
  • CT saturation during external faults.
  • Incorrect differential bias settings.
  • Improper inrush restraint configuration.

Recommended checks:

  1. Review transformer nameplate information.
  2. Verify CT polarity and ratio.
  3. Check phase compensation.
  4. Review differential current measurements.
  5. Check restraint current.
  6. Review disturbance records.
  7. Perform secondary injection tests.

13.2 REF Protection Unwanted Operation

Possible causes:

  • Incorrect neutral CT polarity.
  • Incorrect phase CT connections.
  • Incorrect residual current calculation.
  • Incorrect CT ratio.
  • Wiring problems.
  • Incorrect stabilization settings.

13.3 Transformer Overcurrent Protection Nuisance Tripping

Possible causes:

  • Pickup setting too low.
  • Incorrect CT ratio.
  • Transformer overload.
  • Incorrect time multiplier.
  • Poor coordination with downstream feeders.
  • Transformer energization conditions.

13.4 Transformer Thermal Alarm

Possible causes:

  • Excessive transformer loading.
  • High ambient temperature.
  • Cooling fan failure.
  • Cooling pump failure.
  • Incorrect thermal settings.
  • Abnormal temperature measurement.

13.5 Overfluxing Alarm or Trip

Possible causes:

  • Excessive operating voltage.
  • Reduced system frequency.
  • Generator excitation problems.
  • Incorrect voltage measurement.
  • Incorrect frequency measurement.
  • Incorrect V/Hz settings.

13.6 Troubleshooting Using Relay Records

Sepam measurements, event records and available disturbance records can help engineers identify the cause of unwanted operation.

Important information to investigate includes:

  • Phase currents.
  • Residual current.
  • Differential current, where supported.
  • Voltage measurements.
  • Frequency.
  • Protection pickup indications.
  • Trip indications.
  • Binary input and output status.
  • Event timestamps.
  • Disturbance waveforms, where available.

A systematic investigation should distinguish between genuine transformer faults, protection configuration problems and secondary circuit failures.

14. Practical Transformer Protection Engineering Case Study

Consider a typical industrial power transformer.

14.1 Transformer Technical Data

ParameterExample
Transformer rating40 MVA
HV voltage110 kV
LV voltage11 kV
Frequency50 Hz
Vector groupDyn11
Impedance12.5%
HV CT250/1 A
LV CT2500/1 A
CoolingONAN/ONAF

These values represent an illustrative engineering case, not an approved relay setting schedule.

14.2 Protection Philosophy

The proposed protection scheme includes:

  • Transformer differential protection (87T).
  • Restricted earth fault protection (64REF).
  • HV phase overcurrent protection (50/51).
  • LV phase overcurrent protection (50/51).
  • Earth fault protection (50N/51N).
  • Thermal overload protection (49).
  • Overfluxing protection (24).
  • Breaker failure protection (50BF), where implemented in the protection system.

14.3 Engineering Activities

The protection engineer should complete the following activities:

  1. Calculate rated currents on both sides.
  2. Select suitable CT ratios and protection classes.
  3. Verify transformer vector group.
  4. Calculate differential compensation.
  5. Evaluate differential protection stability.
  6. Calculate REF protection requirements.
  7. Perform phase and earth fault coordination.
  8. Review transformer thermal limits.
  9. Obtain the manufacturer’s V/Hz withstand curve.
  10. Prepare the protection setting schedule.
  11. Configure the compatible Sepam relay.
  12. Perform secondary injection tests.
  13. Verify the complete trip circuit.
  14. Prepare commissioning documentation.

14.4 Expected Engineering Deliverables

The completed engineering package should contain:

  • Transformer protection single-line diagram.
  • CT connection drawings.
  • Protection function diagram.
  • Differential protection calculations.
  • REF protection calculations.
  • Overcurrent coordination curves.
  • Protection setting schedule.
  • Relay configuration files.
  • Secondary injection test reports.
  • Commissioning and functional test reports.

15. Transformer Protection Engineering: Important Standards

Transformer protection engineering should consider the applicable international standards and manufacturer recommendations.

StandardSubject
IEC 60076Power transformers
IEC 60255Measuring relays and protection equipment
IEC 61869Instrument transformers
IEC 60255-151Functional requirements for overcurrent protection
IEEE C37.91Guide for protecting power transformers
IEEE C57.91Loading guide for mineral-oil-immersed transformers
IEC 60076-7Loading guide for oil-immersed power transformers

The latest applicable editions and project specifications should be checked before engineering or commissioning work.

16. Practical Sepam Transformer Protection Training by Elec-Engg

Elec-Engg provides practical power system protection and substation automation training by Dr Saeed Roostaee.

Our training approach focuses on practical engineering, relay configuration, protection calculations, fault analysis and commissioning rather than theoretical explanations alone.

Relevant training subjects include:

  • Schneider Electric Sepam protection relays.
  • Sepam Series 80 transformer protection.
  • Sepam T87 transformer differential protection.
  • Transformer differential protection calculations.
  • Restricted earth fault protection.
  • Transformer phase and earth fault protection.
  • CT selection, polarity and compensation.
  • Transformer protection coordination.
  • SFT2841 engineering software.
  • Relay configuration and protection settings.
  • Omicron CMC secondary injection testing.
  • Practical relay troubleshooting and commissioning.

Training is available through:

  1. Pre-recorded technical courses.
  2. Structured self-paced training.
  3. Face-to-face technical training.
  4. Customized in-house training for companies and utilities.

Explore our technical training resources:

Website: Elec-Engg – Power System Protection and Substation Automation

Related training: Protection Relay Training Courses

17. Frequently Asked Questions (FAQ)

Q1. Which Sepam relay is used for transformer differential protection?

Sepam Series 80 T87 supports two-winding transformer differential protection (87T). The precise application and configuration must be checked against the relay documentation.

Q2. Does Sepam T87 support REF protection?

Yes. The T87 application supports restricted earth fault protection (64REF), subject to correct CT configuration and application requirements.

Q3. What is the difference between 87T and 64REF?

87T detects internal phase and other differential faults within the transformer protection zone. REF provides sensitive earth fault protection for a restricted winding zone.

Q4. Why is transformer vector group compensation necessary?

It compensates for phase displacement between transformer winding currents to prevent unwanted differential current during normal operation and external faults.

Q5. Why is second-harmonic restraint used?

It helps distinguish transformer magnetizing inrush from internal fault current and prevents unwanted differential tripping during energization.

Q6. What is the purpose of ANSI 24 protection?

It detects excessive transformer magnetic flux caused by abnormal voltage-to-frequency conditions.

Q7. What software is used to configure Sepam protection relays?

SFT2841 is the engineering and setting software used with compatible Sepam Series 20, 40, 60 and 80 relays.

Q8. Can Sepam transformer protection be tested using Omicron CMC?

Yes. Compatible secondary injection test equipment can be used to verify protection pickup, operating time, differential stability, REF operation and trip logic.

Q9. What causes unwanted transformer differential operation?

Common causes include incorrect CT polarity, CT ratio mismatch, incorrect vector group compensation, CT saturation and unsuitable protection settings.

Q10. What information is required to calculate transformer protection settings?

Transformer rating, voltage, vector group, impedance, CT ratios, grounding arrangement, fault levels, transformer thermal data and protection coordination requirements are essential.