acSELerator QuickSet Tutorial: Step-by-Step SEL-751 Relay Configuration, Settings, SELogic and Commissioning
- Introduction
- 1. Preparing for the QuickSet tutorial
- 2. Downloading and installing acSELerator QuickSet
- 3. Understanding the QuickSet main window
- 4. Creating a new SEL-751 settings file
- 5. Understanding the SEL-751 settings structure
- 6. Reading existing settings from an SEL-751
- 7. Configuring basic system parameters
- 8. Configuring phase overcurrent protection
- 9. Configuring earth-fault protection
- 10. Developing SELogic control equations
- 11. Using the Graphical Logic Editor
- 12. Configuring communication parameters
- 13. Saving and comparing settings
- 14. Sending settings to the SEL-751
- 15. Using the QuickSet HMI
- 16. Retrieving and analysing event records
- 17. Practical commissioning test using OMICRON CMC
- 18. Troubleshooting common QuickSet problems
- 19. Recommended QuickSet learning sequence
- 20. Official SEL QuickSet tutorials and learning resources
- Conclusion
- Practical SEL Relay Training with Elec-Engg
Introduction
Learning acSELerator QuickSet SEL-5030 is an important skill for protection engineers working with SEL protection relays. QuickSet provides an engineering environment for creating relay settings, configuring protection functions, developing control logic, communicating with IEDs and analysing relay information.
In this practical tutorial, we will use the SEL-751 Feeder Protection Relay as an example and follow a typical engineering workflow, from opening QuickSet to testing the configured relay.
The tutorial is intended for protection engineers, commissioning engineers, electrical maintenance engineers and technicians who want to develop practical skills in SEL relay configuration.
What you will learn:
- How to prepare and install QuickSet.
- How to select the correct SEL relay driver.
- How to create a new SEL-751 settings file.
- How to connect QuickSet to a physical relay.
- How to read and back up existing relay settings.
- How to configure basic system parameters.
- How to configure overcurrent and earth-fault protection.
- How to develop SELogic control equations.
- How to save, compare and transfer settings.
- How to use the QuickSet HMI for monitoring.
- How to retrieve and analyse relay event records.
- How to verify the configuration during commissioning.
Important: This tutorial describes the general QuickSet workflow using an SEL-751 example. Exact menu names, settings, functions and communication options may differ according to the relay model, firmware and QuickSet device driver. Never use example settings as approved protection settings for an actual installation.
1. Preparing for the QuickSet tutorial
Before starting, prepare the following:
| Item | Purpose |
|---|---|
| Computer with supported Windows version | Running QuickSet |
| SEL-5030 acSELerator QuickSet | Relay configuration |
| SEL-751 relay | Practical configuration example |
| Communication cable or Ethernet connection | Connecting to the relay |
| SEL-751 instruction manual | Device-specific technical reference |
| Relay single-line diagram | Understanding the protection application |
| CT and VT drawings | Verifying measurement connections |
| OMICRON CMC test set (optional) | Secondary injection testing |
For an offline exercise, a physical relay is not essential. You can create and edit a settings file without connecting to an installed device, provided the required device driver is available.
For a complete practical course, however, it is beneficial to work with a physical relay and test equipment.
2. Downloading and installing acSELerator QuickSet
QuickSet is available through SEL’s official software resources.
Start by visiting the official product page:
The general installation procedure is:
- Download the appropriate QuickSet installation package.
- Review the supported Windows versions and installation requirements.
- Run the installer with the required permissions.
- Complete the installation.
- Open QuickSet.
- Confirm that the required SEL device drivers are installed.
SEL Compass can also be used to manage SEL software and obtain applicable updates.
Selecting the correct device driver
QuickSet uses device-specific drivers to understand the settings structure of each supported relay.
For example, when working with an SEL-751, the selected device driver must match the appropriate relay family and supported revision.
This is important because the available settings and their organization may change between device revisions and firmware versions.
Do not select a driver simply because its name looks similar to the relay installed at site.
3. Understanding the QuickSet main window
After starting QuickSet, become familiar with the main application interface.
The main engineering operations include:
| Operation | Purpose |
|---|---|
| File → New | Create a new settings instance |
| File → Open | Open an existing settings file |
| File → Read | Retrieve settings from a connected device |
| File → Save / Save As | Store the current settings |
| File → Send | Transfer selected settings to a connected relay |
| Edit → Compare | Compare settings instances, where supported |
| Tools | Access additional engineering functions |
| HMI | Access supported relay monitoring functions |
| Terminal | Communicate with the relay using supported commands |
The Settings Editor is the central workspace for relay configuration.
In supported device drivers, it may present settings in a structured graphical interface. Other device drivers may use a grid-style editor.
The available interface depends on the device driver.
4. Creating a new SEL-751 settings file
Let’s create a new configuration for an SEL-751 feeder protection relay.
Step 1: Open QuickSet
Start acSELerator QuickSet from the Windows Start menu.
Step 2: Create a new settings instance
Select:
File → New
QuickSet will prompt you to select the device type or an applicable device definition.
Step 3: Select the SEL-751 device
Choose the appropriate SEL-751 device driver and revision.
Check the device information carefully. Depending on the available driver, the settings editor may display the relay part number or device version.
Step 4: Open the Settings Editor
After selecting the correct device, QuickSet opens the settings editor.
You should now be able to navigate through the available setting categories.
Step 5: Save the new file
Save the settings instance using a meaningful project name.
For example:
PowerPlant_Feeder01_SEL751_Rev00
A good naming convention helps engineers distinguish between original, working, approved and final settings.
5. Understanding the SEL-751 settings structure
The SEL-751 Settings Editor organizes parameters into logical sections.
The exact structure depends on the device driver and firmware, but a typical configuration may include:
| Section | Typical purpose |
|---|---|
| Global | General relay configuration |
| Group 1 | Protection setting group |
| Group 2, 3, 4 | Additional setting groups, where supported |
| Front Panel | Front-panel configuration |
| Report | Event and report-related parameters |
| Communication ports | Serial and Ethernet communication configuration |
| Protocol maps | Supported communication protocol configuration |
| Touchscreen | Applicable display configuration |
The Global section contains general device settings. Protection functions are typically organized within the available protection setting groups.
Why are there multiple setting groups?
Setting groups allow a relay to use different protection settings for different operating conditions.
For example, an industrial network may have different operating configurations depending on whether two transformers are operating in parallel or one transformer is out of service.
An engineer can develop appropriate setting groups for the approved operating conditions.
However, the group selection logic must also be engineered and tested. Merely creating multiple groups does not automatically ensure that the relay selects the correct group.
6. Reading existing settings from an SEL-751
When working with an installed relay, reading the existing configuration is normally the first practical operation.
Step 1: Establish communication
Connect the computer to the relay using a supported communication interface.
Depending on the SEL-751 hardware and configuration, communication may be available through serial or Ethernet interfaces.
Step 2: Configure the communication parameters
Check the applicable relay port configuration and QuickSet communication settings.
For an Ethernet connection, verify:
- Relay IP address.
- Computer IP address.
- Subnet configuration.
- Network connectivity.
- Required communication protocol.
- Any applicable access restrictions.
For serial communication, verify the correct port and the communication parameters required by the relay.
Step 3: Read the relay settings
Select:
File → Read
QuickSet communicates with the relay and retrieves the selected settings.
A transfer status window may appear during the operation.
Step 4: Save the retrieved settings
After a successful read, save the settings as the original configuration.
For example:
PowerPlant_Feeder01_SEL751_Original_2026
Step 5: Verify the relay identity
Check that the connected device is the intended relay.
Record the relay identification, device version and relevant firmware information.
Engineering recommendation: Never begin changing an installed relay before obtaining and safely storing its existing settings.
7. Configuring basic system parameters
Before configuring protection elements, review the basic system parameters.
For a feeder protection application, these may include:
- Nominal system frequency.
- CT ratios.
- VT ratios, where applicable.
- Current measurement configuration.
- Voltage measurement configuration.
- Phase rotation.
- Ground current measurement arrangement.
- Relevant breaker and input/output configuration.
Example: CT ratio configuration
Assume the feeder uses a CT with the following ratio:
- Primary rating: 600 A
- Secondary rating: 1 A
The ratio is:
[
CTR=\frac{600}{1}=600
]
The engineer must configure the appropriate CT information in the relay settings.
If the CT ratio is entered incorrectly, measured primary current values and protection calculations may be incorrect.
Always verify the CT nameplate, approved drawings and the specific relay’s measurement configuration.
8. Configuring phase overcurrent protection
Overcurrent protection is one of the most common applications of the SEL-751.
Depending on the device configuration, the relay may provide instantaneous and time-overcurrent protection elements.
8.1 Instantaneous overcurrent protection
Instantaneous overcurrent protection operates when the measured current exceeds a configured pickup threshold and the required logic conditions are satisfied.
The engineering process generally involves:
- Reviewing the maximum load current.
- Determining the minimum and maximum fault current.
- Checking the CT ratio and measurement arrangement.
- Selecting an appropriate pickup threshold.
- Reviewing the required operating logic.
- Testing the element using secondary injection.
The pickup setting must be selected using the protection coordination study and the actual system data.
8.2 Time-overcurrent protection
Time-overcurrent protection provides a delayed response according to the selected characteristic and operating settings.
Depending on the relay and supported functions, engineers may configure:
- Pickup current.
- Time dial or time multiplier.
- Operating curve.
- Definite-time characteristics.
- Reset behavior.
- Associated logic.
Common inverse-time characteristics include standard inverse, very inverse and extremely inverse curves. The exact available characteristics must be checked in the SEL-751 documentation.
8.3 Protection coordination
The overcurrent settings must coordinate with the upstream and downstream protective devices.
For example, the outgoing feeder relay should normally operate before the upstream incomer relay for faults within the feeder protection zone, subject to the approved protection philosophy.
The engineer should check:
- Minimum and maximum fault current.
- Load current and permissible overload.
- CT performance.
- Downstream protective device characteristics.
- Upstream protection operating times.
- Breaker clearing time.
- Equipment thermal limits.
QuickSet is the configuration tool. It does not replace the protection coordination study.
9. Configuring earth-fault protection
Earth-fault protection is essential for detecting phase-to-ground faults.
The SEL-751 may support different ground-current measurement and protection arrangements depending on the installed hardware and configuration.
Before configuring the protection, identify how ground current is measured:
- Residual current calculated from phase currents.
- Dedicated neutral CT input.
- Other supported measurement arrangements.
The engineer should then configure the applicable protection elements and verify the measurement direction and polarity.
Practical checks
During commissioning, verify:
- Correct CT polarity.
- Correct phase-current measurements.
- Correct residual-current calculation or neutral-current measurement.
- Correct protection pickup.
- Correct operating time.
- Correct trip logic and output assignment.
Do not assume that all ground-current elements use the same input or measurement source.
10. Developing SELogic control equations
SELogic is an important feature of SEL protection relays.
It allows engineers to combine protection elements, digital inputs, timers and internal relay signals to implement application-specific logic.
For example, a simplified feeder trip function may combine two overcurrent elements:
TRIP = 50P1 OR 51P1
This represents a conceptual relationship in which either protection element can initiate the trip logic.
The actual SEL variable names, equation locations and output assignments must be checked for the selected relay driver.
Typical SELogic applications
- Trip logic.
- Breaker closing permissive.
- Breaker failure initiation.
- Protection blocking.
- Alarm generation.
- Interlocking.
- External trip inputs.
- Setting group selection.
Example: External trip input
Suppose an external protection device provides a trip signal to a binary input on the SEL-751.
The engineering process includes:
- Identify the physical binary input.
- Confirm the input polarity and voltage requirements.
- Verify the input assignment.
- Identify the corresponding internal logic variable.
- Incorporate the signal into the relevant SELogic equation.
- Assign the resulting logic to the intended output, where appropriate.
- Test the complete signal path.
A logic equation should never be implemented without verifying the actual wiring and intended protection philosophy.
11. Using the Graphical Logic Editor
QuickSet includes a Graphical Logic Editor (GLE) for supported devices.
The editor provides a graphical environment for designing logic using function blocks and connections.
It can be useful for:
- Interlocking schemes.
- Breaker control.
- Alarm logic.
- Signal combination.
- Custom automation functions.
A graphical representation can make complicated logic easier to review and document.
However, GLE support and available function blocks depend on the device driver and relay model.
After developing logic, review the complete signal path and test its behavior under normal, abnormal and failure conditions.
12. Configuring communication parameters
The SEL-751 supports communication options that depend on the hardware and configuration.
Communication settings may include:
- Ethernet parameters.
- Serial port parameters.
- Communication protocol selection.
- IP addressing.
- Protocol-specific configuration.
- Time synchronization settings, where supported.
QuickSet can be used to configure applicable device communication parameters.
For example, if the relay is connected to a station SCADA system, engineers may need to configure the required protocol and communication interface.
However, configuring an IP address or protocol in QuickSet does not automatically complete a full IEC 61850 system configuration.
For supported IEC 61850 applications, system engineering tasks such as SCL configuration and GOOSE engineering are handled using the appropriate tools, including SEL-5032 acSELerator Architect.

13. Saving and comparing settings
After making configuration changes, save the settings file.
Use a separate revision for every significant engineering change.
For example:
Feeder01_SEL751_OriginalFeeder01_SEL751_Engineering_Rev01Feeder01_SEL751_Approved_Rev02Feeder01_SEL751_AsLeft
QuickSet provides settings comparison capabilities for supported settings instances.
Comparison is useful for identifying:
- Changed protection pickups.
- Modified time delays.
- Different setting group configurations.
- Changes to logic equations.
- Communication parameter differences.
Review all differences before transferring settings to an installed relay.
14. Sending settings to the SEL-751
Once the settings have been checked and approved, the engineer can transfer the required configuration to the relay.
The general procedure is:
- Open the correct settings file.
- Confirm the target relay identity.
- Review the settings and any applicable warnings.
- Save the final engineering revision.
- Select File → Send.
- Select the appropriate settings sections in the transfer dialog, where applicable.
- Start the transfer.
- Review the transfer status.
- Confirm the relay configuration after the transfer.
Important commissioning warning: Sending settings to a protection relay can affect its protection and control behavior. Do not perform this operation on an in-service relay without authorization, an approved switching and protection procedure, and an appropriate risk assessment.
After transfer, verify the actual relay configuration rather than relying only on the software file.
15. Using the QuickSet HMI
QuickSet provides HMI functionality for supported SEL devices.
The HMI can help engineers monitor relay information during testing and commissioning.
Depending on the relay, information may include:
- Metered current.
- Metered voltage.
- Frequency.
- Relay Word bit status.
- Binary input status.
- Output contact status.
- Protection element operation.
- Other available measurements.
Example: Checking overcurrent pickup
During a secondary injection test:
- Connect the test set to the relay current inputs.
- Inject the required current.
- Monitor the relevant measurements through the HMI.
- Observe the applicable protection element status.
- Check the corresponding trip logic.
- Verify the output contact operation.
This makes it easier to identify whether a problem is associated with measurement, protection pickup, logic or output assignment.
16. Retrieving and analysing event records
Event records are valuable for investigating relay operation.
The SEL-751 stores event information that can help engineers understand how the relay responded to a disturbance.
QuickSet provides event retrieval and analysis functions for supported devices.
A typical workflow is:
- Connect to the relay.
- Open the applicable event retrieval function.
- Retrieve the available event records.
- Save the event files.
- Open the records using the available analysis tools.
- Examine analogue waveforms and digital signals.
Event analysis can help answer questions such as:
- Did the relay measure the expected fault current?
- Which protection element operated?
- Did the trip logic become active?
- Did the output contact operate?
- Was the breaker status correctly detected?
- Did the relay receive an external blocking signal?
For more detailed disturbance analysis, SEL synchroWAVe Event is another relevant engineering application.
17. Practical commissioning test using OMICRON CMC
After configuring the relay, perform the required protection tests.
An OMICRON CMC test set can be used with appropriate Test Universe modules to verify protection functions.
A typical test sequence for an SEL-751 feeder relay may include:
| Test | Objective |
|---|---|
| Current measurement | Verify measured phase currents |
| Overcurrent pickup | Verify element pickup threshold |
| Overcurrent timing | Verify operating time |
| Earth-fault pickup | Verify ground protection sensitivity |
| Earth-fault timing | Verify operating time |
| Binary input test | Verify external signal recognition |
| SELogic test | Verify control equation behavior |
| Binary output test | Verify output contact operation |
| Trip circuit test | Verify the intended trip path |
| Event record test | Verify event capture and retrieval |
Example: Secondary injection test
Suppose the approved engineering setting requires an overcurrent element to operate at a particular secondary current.
The test engineer should:
- Review the approved pickup setting.
- Confirm the CT ratio and test injection basis.
- Calculate the corresponding test current.
- Inject current using the appropriate test procedure.
- Record the actual pickup value.
- Compare the measured result with the permitted tolerance.
- Repeat for the relevant operating-time points.
Do not use arbitrary test values. The test plan should be based on the approved settings, relay specifications and applicable commissioning requirements.
18. Troubleshooting common QuickSet problems
Problem 1: The relay is not communicating with QuickSet
Check:
- Physical communication connection.
- Correct communication interface.
- Serial parameters or Ethernet configuration.
- Relay IP address.
- Network connectivity.
- Access restrictions and security settings.
Problem 2: The wrong device driver is selected
Check the relay model, part number, firmware and driver compatibility.
A mismatched driver may cause settings differences or prevent correct configuration.
Problem 3: The settings file cannot be sent
Check:
- Device compatibility.
- Communication status.
- Selected transfer sections.
- Relay access permissions.
- Any software or device warnings.
Problem 4: A protection element does not operate
Investigate the complete protection chain:
- CT secondary input.
- Relay measured current.
- Protection element enable status.
- Pickup threshold.
- Operating timer.
- SELogic conditions.
- Output assignment.
- Physical output contact.
This systematic approach helps identify whether the problem is associated with measurement, protection settings, logic or wiring.
Problem 5: Event records do not show the expected fault
Check the event trigger configuration, available records, relay time settings and event retrieval procedure.
Also verify that the test or fault condition actually met the applicable event recording criteria.
19. Recommended QuickSet learning sequence
For engineers who are new to SEL software, the following sequence provides a practical way to develop their skills.
| Stage | Practical exercise |
|---|---|
| 1 | Install QuickSet and identify device drivers |
| 2 | Create a new SEL-751 settings file |
| 3 | Explore the Settings Editor |
| 4 | Read and save existing relay settings |
| 5 | Configure CT and system parameters |
| 6 | Configure phase overcurrent protection |
| 7 | Configure earth-fault protection |
| 8 | Develop SELogic equations |
| 9 | Configure communication parameters |
| 10 | Send settings to a test relay |
| 11 | Monitor relay measurements and logic |
| 12 | Retrieve and analyse event records |
| 13 | Perform secondary injection testing |
| 14 | Prepare the final configuration and commissioning report |
This learning sequence combines software operation with the protection engineering knowledge required to use the software correctly.
20. Official SEL QuickSet tutorials and learning resources
SEL provides a collection of software demonstrations and product-specific training videos.
The following resources are particularly relevant:
- SEL-5030 acSELerator QuickSet: Official product page
- QuickSet software videos: SEL Video Support Portal
- SEL-751 product and tutorial videos: SEL-751 official product page
- SEL-751 instruction manual: Available through the SEL product documentation resources.
- QuickSet settings conversion tutorial: Watch the SEL tutorial
SEL’s SEL-751 video series includes demonstrations covering communications, overcurrent and time-overcurrent protection, and event analysis.
These resources are useful alongside the practical exercises in this tutorial.
Conclusion
acSELerator QuickSet is more than a settings editor. It is an important engineering environment for configuring, monitoring, commissioning and maintaining SEL protection relays.
By following a structured workflow, engineers can learn how to create settings files, read and transfer configurations, configure protection elements, develop SELogic equations and investigate relay operation through event records.
The most effective way to learn QuickSet is to combine software exercises with real protection applications, relay drawings and secondary injection testing.
Practical SEL Relay Training with Elec-Engg
Elec-Engg provides practical training in power system protection, SEL protection relays, relay configuration, testing and commissioning.
Training can cover:
- SEL-751 feeder protection relay configuration.
- SEL-787 transformer protection.
- SEL-421 and SEL-411L line protection.
- SEL-487B busbar protection.
- acSELerator QuickSet and SELogic.
- IEC 61850 engineering using SEL Architect.
- OMICRON CMC relay testing and commissioning.
Online training can be arranged based on the requested relay model, engineering subject and practical application.
Visit https://elec-engg.com/ for further information.