acSELerator QuickSet Tutorial: Step-by-Step Guide to SEL Relay Configuration, Communication and Settings Management
- Introduction
- 1. What do you need before starting?
- 2. Downloading and installing acSELerator QuickSet
- 3. Understanding the QuickSet interface
- 4. Creating a new relay settings file
- 5. Connecting your computer to an SEL relay
- 6. Reading existing settings from an SEL relay
- 7. Understanding and modifying protection settings
- 8. Working with setting groups
- 9. Saving and organizing settings files
- 10. Sending settings to an SEL relay
- 11. Comparing two settings files
- 12. Retrieving event reports from an SEL relay
- 13. Retrieving Sequential Events Recorder (SER) data
- 14. Using the QuickSet HMI
- 15. Using the QuickSet Terminal
- 16. Setting up Ethernet communication
- 17. Troubleshooting common QuickSet problems
- 18. Recommended practical exercises
- 19. Official SEL QuickSet learning resources
- Conclusion
- Learn SEL acSELerator QuickSet with Elec-Engg
Introduction
If you work with SEL protection relays, learning acSELerator QuickSet SEL-5030 is an important practical skill. QuickSet allows protection engineers and commissioning technicians to configure relays, read and modify settings, communicate with installed devices, retrieve event reports and investigate relay operation.
In this tutorial, we will go through the main QuickSet workflows step by step, using a typical SEL feeder protection relay as an example.
You will learn how to:
- Install and prepare acSELerator QuickSet.
- Navigate the QuickSet interface.
- Create a new relay settings file.
- Connect a computer to an SEL protection relay.
- Read and save existing relay settings.
- Modify protection settings.
- Send settings to a relay.
- Compare settings files.
- Retrieve event reports and Sequential Events Recorder (SER) information.
- Use the HMI and terminal tools.
- Troubleshoot common communication and configuration problems.
This tutorial is intended for electrical engineers, protection engineers, commissioning engineers and technicians who want to develop practical skills in SEL relay configuration.
1. What do you need before starting?
Before using QuickSet, prepare the following items.
| Item | Purpose |
|---|---|
| Windows computer | Running the QuickSet software |
| acSELerator QuickSet SEL-5030 | Relay configuration and communication |
| SEL protection relay | For example, SEL-751 or SEL-351 |
| Communication cable | Compatible with the relay’s available port |
| Relay documentation | Instruction manual and communication information |
| Relay settings file | Existing configuration, if available |
| Approved protection study | Required when changing protection settings |
For this tutorial, we will use an SEL-751 feeder protection relay as the example.
The same general principles apply to many other SEL devices, but the settings structure and available functions depend on the selected relay model, hardware and firmware.
Important: If you are working with an operational protection system, do not change or send settings without the required engineering approval and site authorization.
2. Downloading and installing acSELerator QuickSet
The first step is to obtain the official software installation package.
Step 1: Open the SEL website
Visit the official QuickSet page:
Open the support section to find the available software downloads, release information and installation requirements.
Step 2: Download the installation package
Select the appropriate QuickSet installation package.
Check the following before downloading:
- Software version.
- Supported Windows operating system.
- Installation requirements.
- Available device drivers.
- Compatibility with your target SEL relay.
SEL’s support page lists the current installation package and supported operating systems.
Step 3: Install QuickSet
Run the installation package and follow the installation instructions.
Depending on the selected installation method, additional components or drivers may be required.
Step 4: Verify the installation
After installation:
- Open acSELerator QuickSet.
- Confirm that the application starts correctly.
- Check the installed version.
- Confirm that the required relay drivers are available.
- Check whether any additional device-specific components are required.
Engineering tip: Keep a record of the QuickSet version used for each project. When sharing settings files with other engineers, software and device compatibility should be considered.
3. Understanding the QuickSet interface
When you open QuickSet, you will find the main engineering environment used to manage devices, settings and communication.
The exact appearance depends on the installed version and selected components, but the main working areas generally include:
- Device Manager or device navigation area.
- Settings Editor.
- Communication tools.
- HMI tools.
- Terminal interface.
- File and settings management functions.
- Output and status information.
<IMAGE_PLACEHOLDER_1>
Suggested screenshot: acSELerator QuickSet main window showing the device navigation area and settings workspace.
Important QuickSet functions
| Function | Purpose |
|---|---|
| New Settings | Create a new settings file |
| Open Settings | Open an existing settings file |
| Read Settings | Retrieve settings from a connected relay |
| Send Settings | Transfer an approved configuration to a relay |
| Compare Settings | Identify differences between settings files |
| HMI | Access supported relay monitoring and control functions |
| Terminal | Communicate with the relay using supported commands |
| Device Manager | Organize devices and their associated engineering data |
The availability and exact presentation of these functions depend on the installed QuickSet components and the connected device.
4. Creating a new relay settings file
You do not always need to connect to a physical relay to start engineering.
QuickSet supports offline settings development for supported devices.
This is particularly useful when preparing a relay configuration before equipment installation or commissioning.
Step 1: Start a new settings file
Open QuickSet and select the function for creating a new settings file.
Step 2: Select the relay model
Choose the appropriate SEL device from the supported device list.
For this example, select the applicable SEL-751 device definition.
Make sure that the selected model and device revision match the actual relay.
Step 3: Open the Settings Editor
After selecting the device, QuickSet opens the applicable settings structure.
Depending on the relay, settings may be arranged into sections such as:
- Global settings.
- Current and voltage inputs.
- Protection elements.
- Setting groups.
- Control equations.
- Communication.
- Inputs and outputs.
- Metering and monitoring.
Step 4: Save the settings file
Save the configuration using a clear project name.
Example:
33kV_Feeder01_SEL751_Initial_Settings
This file can be developed offline and reviewed before it is transferred to the relay.
Important: A settings file created offline is not proof that the physical relay has the same configuration. Always read and verify the installed device before making changes.
5. Connecting your computer to an SEL relay
One of the most important QuickSet operations is establishing communication with an installed relay.
The connection method depends on the available relay hardware and communication configuration.
Common possibilities include:
- Front-panel serial communication.
- Rear-panel serial communication.
- Ethernet communication.
- Other interfaces supported by the particular device.
<IMAGE_PLACEHOLDER_2>
Suggested screenshot or photograph: an engineer connecting a laptop to an SEL protection relay using a compatible communication cable.
Step 1: Identify the relay communication port
Check the relay front and rear panels.
Consult the instruction manual to identify the correct communication port and cable requirements.
Do not assume that every SEL relay uses the same connector or communication interface.
Step 2: Connect the communication cable
Connect the computer to the selected relay port.
For a USB-to-serial adapter, confirm that the required driver is installed and that Windows recognizes the adapter.
Step 3: Check the communication parameters
For serial communication, verify the applicable settings, which may include:
- Communication port.
- Baud rate.
- Data bits.
- Parity.
- Stop bits.
- Protocol or communication mode.
For Ethernet communication, verify:
- Relay IP address.
- Computer IP address.
- Subnet configuration.
- Network connectivity.
- Applicable access and security settings.
The actual requirements must be obtained from the relay configuration and device documentation.
Step 4: Configure QuickSet communication
Open the communication configuration tools and select the appropriate connection method.
Enter the required communication parameters.
Step 5: Establish communication
Use the available connection or communication function.
If communication is successful, verify the device identification information before proceeding.
Important: Never assume that a successful connection means you are communicating with the intended relay. Confirm the relay model and identification before reading or sending settings.
6. Reading existing settings from an SEL relay
When working with an installed protection relay, reading its existing settings should normally be one of the first operations.
This allows you to understand the actual configuration before making any changes.
Step 1: Establish communication
Connect to the relay using the appropriate interface.
Step 2: Select the read-settings function
Use QuickSet’s available function to retrieve settings from the connected device.
Step 3: Wait for the reading process
QuickSet communicates with the relay and retrieves the supported configuration data.
Step 4: Save the settings file
Save the retrieved settings in an appropriate project folder.
Example:
33kV_Feeder01_SEL751_Original_From_Relay
Step 5: Verify the file
Check the relay identification and settings content.
Keep this original file unchanged.
<IMAGE_PLACEHOLDER_3>
Suggested screenshot: QuickSet Settings Editor displaying settings read from an SEL relay.
Engineering recommendation: Always save a separate original settings file before making any modifications. This gives you a reference configuration for future comparison and recovery.
7. Understanding and modifying protection settings
Once the settings file is open, you can review and modify the parameters supported by the selected relay.
For our SEL-751 feeder example, typical protection areas may include:
- Phase overcurrent protection.
- Ground overcurrent protection.
- Directional overcurrent, where supported.
- Negative-sequence protection, where supported.
- Voltage-related functions, where supported.
- Breaker failure and control logic, where supported.
Example: Phase overcurrent protection
Suppose you are reviewing a feeder protection configuration.
The engineering study identifies the required phase overcurrent pickup and time-current characteristics.
The workflow is:
- Open the relevant protection settings section.
- Locate the applicable phase overcurrent element.
- Review its enable or disable status.
- Enter the approved pickup value.
- Select the required operating characteristic, if applicable.
- Enter the associated time multiplier or delay.
- Review any related supervision or blocking conditions.
- Validate and save the configuration.
The actual setting names and available characteristics depend on the relay model and firmware.
Example: Earth-fault protection
For earth-fault protection, first identify how the relay obtains its ground or residual current measurement.
This may involve residual calculation from phase currents or a dedicated neutral current input.
Then review the applicable protection settings and confirm that the CT arrangement matches the drawings.
Important: Do not use example values from another installation as actual protection settings. Pickup levels and operating times must come from the approved protection study.
8. Working with setting groups
Many SEL relays support multiple protection setting groups.
Setting groups allow different protection configurations to be selected for different operating conditions.
For example, a network may have different protection requirements depending on whether it is operating with:
- One transformer in service.
- Two transformers in parallel.
- A normally open bus coupler closed.
- An alternative supply arrangement.
The actual number of groups and switching mechanisms depend on the relay.
General setting-group workflow
- Open the relevant settings group.
- Review the protection parameters.
- Enter the approved settings.
- Repeat the process for the other required groups.
- Review the group selection logic.
- Verify the active setting group.
- Test group selection and protection behavior.
Do not assume that changing a setting group automatically changes the physical network configuration. The group selection logic must be engineered and tested.
9. Saving and organizing settings files
Good configuration management is essential for protection engineering.
Use a consistent file naming convention to distinguish original, modified, approved and installed settings.
For example:
| File name | Description |
|---|---|
| Feeder01_SEL751_Original | Settings initially read from the relay |
| Feeder01_SEL751_Rev01 | First engineering revision |
| Feeder01_SEL751_Approved | Approved configuration |
| Feeder01_SEL751_AsInstalled | Final verified installed configuration |
Keep the associated engineering documents in the same project structure where practical.
Recommended records include:
- Relay identification.
- Firmware version.
- CT and VT ratios.
- Approved protection settings.
- Settings revision.
- Date of modification.
- Engineer or reviewer identification.
- Commissioning test report.
10. Sending settings to an SEL relay
After completing and reviewing the configuration, you may need to transfer the settings to the physical relay.
This operation must be performed carefully.
Step 1: Open the approved settings file
Confirm that you have selected the correct file and revision.
Step 2: Verify relay identification
Connect to the target relay and confirm its model and identification.
Step 3: Compare the settings
Where appropriate, compare the proposed configuration with the existing relay settings.
Investigate unexpected differences before proceeding.
Step 4: Send the settings
Use the applicable QuickSet function to transfer the approved settings.
Follow any prompts or device-specific requirements.
Step 5: Confirm successful transfer
Check the communication result and verify the settings on the relay.
Step 6: Perform functional testing
After settings transfer, perform the required checks and protection tests.
Safety note: Sending settings to an in-service relay may affect protection operation. Follow the site’s switching, isolation, authorization and protection management procedures.
11. Comparing two settings files
QuickSet can help engineers identify differences between settings files.
This is useful when:
- Reviewing engineering changes.
- Comparing the original and modified configurations.
- Checking whether an approved file matches the installed relay.
- Investigating unexpected changes.
- Managing multiple revisions.
General comparison procedure
- Open the settings comparison function.
- Select the first settings file.
- Select the second settings file.
- Run the comparison.
- Review the identified differences.
- Investigate each important change.
- Save the reviewed configuration according to the project procedure.
<IMAGE_PLACEHOLDER_4>
Suggested screenshot: QuickSet settings comparison showing differences between two relay configuration files.
Remember that a settings difference is not automatically an error. Every change must be evaluated against the protection design and approved engineering documentation.
12. Retrieving event reports from an SEL relay
Event reports are extremely useful for protection engineers.
They help identify what happened during a fault, switching operation or abnormal system condition.
Depending on the relay model, event information may include:
- Current waveforms.
- Voltage waveforms.
- Digital input states.
- Output contact states.
- Protection element operation.
- Time information.
- Trigger information.
General event retrieval workflow
- Connect to the relay.
- Open the relevant event or report retrieval tool.
- Review the available event records.
- Select the required record.
- Retrieve the event file.
- Save the file in the project folder.
- Open the event using the appropriate analysis software.
For supported oscillography records, SEL event files may be analyzed using SIGRA or other compatible analysis tools, depending on the file format and device.
Event reports can help engineers answer questions such as:
- Which protection element operated?
- What was the fault current?
- Did the relay detect the fault correctly?
- Was the breaker trip output issued?
- Did the breaker open?
- Were there unexpected digital input changes?
13. Retrieving Sequential Events Recorder (SER) data
The Sequential Events Recorder provides a time-ordered record of selected relay status changes.
Depending on the relay configuration, SER data can include:
- Digital input transitions.
- Protection element pickup and dropout.
- Trip logic changes.
- Output contact status.
- Breaker status changes.
- Other configured internal signals.
The SER is particularly useful when investigating protection and control problems.
Example: Investigating a feeder trip
Suppose a feeder breaker trips unexpectedly.
The engineer may retrieve the SER and investigate the sequence of events:
- Did a protection element pick up?
- Did the trip logic operate?
- Did the output contact change state?
- Did the breaker auxiliary contact indicate opening?
- Were there any unexpected blocking or interlocking signals?
The SER should be considered together with oscillography, relay targets, event reports and the physical breaker circuit.
14. Using the QuickSet HMI
QuickSet provides an HMI tool for supported SEL devices.
The HMI can display relay information and provide access to certain device operations, depending on the model and configuration.
Typical information may include:
- Measured currents.
- Measured voltages.
- Frequency.
- Protection element status.
- Digital input status.
- Output contact status.
- Relay operating information.
<IMAGE_PLACEHOLDER_5>
Suggested screenshot: SEL relay HMI displaying measured electrical quantities and digital status.
Practical example
During secondary injection testing, an engineer injects current into the relay.
Using the HMI, the engineer can check whether:
- The relay measures the expected current.
- The relevant protection element picks up.
- The associated logic changes state.
- The assigned output operates.
This can significantly simplify troubleshooting.
Important: HMI functions that operate or control a device should be used only under approved testing and operating procedures. Monitoring and control capabilities differ between devices.
15. Using the QuickSet Terminal
QuickSet also provides terminal functionality for communicating with supported SEL devices.
This is useful when an engineer needs to enter commands or retrieve information not directly available through the graphical interface.
Depending on the relay and communication method, terminal commands may be used to:
- Check relay status.
- Retrieve information.
- Review device reports.
- Investigate communication problems.
- Access Sequential Events Recorder data.
- Perform supported maintenance operations.
Basic workflow
- Establish communication with the relay.
- Open the QuickSet terminal tool.
- Confirm that the terminal is communicating with the intended device.
- Enter a command supported by the specific relay.
- Review the response.
- Save relevant information where required.
Important: Terminal commands are device-specific. Do not copy commands from another relay model without checking the applicable instruction manual and command reference.
SEL provides an official video explaining essential terminal commands in QuickSet.
16. Setting up Ethernet communication
Ethernet communication is useful when the engineering computer must communicate with a relay over a local network.
The exact procedure depends on the relay’s Ethernet hardware and communication settings.
Step 1: Identify the relay IP address
Obtain the configured IP address from the relay documentation or approved network configuration.
Step 2: Configure the engineering computer
Configure the computer’s network interface according to the approved network plan.
Step 3: Check network connectivity
Verify that the computer can reach the relay over the intended network path.
Step 4: Configure QuickSet
Select the applicable Ethernet communication method and enter the required connection information.
Step 5: Establish communication
Connect to the relay and confirm the device identification.
Step 6: Verify communication stability
Read settings or retrieve a non-disruptive information record to verify the communication path.
SEL provides an official QuickSet video specifically covering Ethernet connection setup.
Cybersecurity note: Use approved network access, authentication and security controls. Do not connect protection relays to unrestricted networks or expose their engineering interfaces unnecessarily.
17. Troubleshooting common QuickSet problems
Problem 1: The computer does not recognize the USB communication cable
Possible causes:
- Missing USB driver.
- Incorrect adapter driver.
- Faulty cable.
- Incorrect Windows communication port assignment.
Recommended checks:
- Check the cable and physical connection.
- Open Windows Device Manager.
- Confirm whether the adapter is recognized.
- Install the correct driver.
- Check the assigned communication port.
- Retry the QuickSet connection.
Problem 2: QuickSet cannot communicate with the relay
Check:
- Correct communication interface.
- Correct serial parameters.
- Correct IP address.
- Network connectivity.
- Relay communication configuration.
- Device access permissions.
Problem 3: QuickSet cannot find the relay model
Possible causes include missing drivers, unsupported device revisions or software compatibility issues.
Check the official SEL support page and install the required device components.
Problem 4: Settings cannot be sent
Check:
- Device identification.
- Settings-file compatibility.
- Communication stability.
- Access permissions.
- Relay-specific transfer requirements.
Do not repeatedly attempt to send settings without understanding the reported error.
Problem 5: Event reports cannot be retrieved
Check whether the relay supports the required report type, whether records are available and whether the selected communication method supports the retrieval operation.
18. Recommended practical exercises
To become familiar with QuickSet, practice the following tasks using a training relay or a suitable offline settings file.
| Exercise | Practical task |
|---|---|
| 1 | Install QuickSet and verify the software version |
| 2 | Open an existing SEL settings file |
| 3 | Create a new settings file for a supported relay |
| 4 | Identify the main protection settings sections |
| 5 | Review CT and VT parameters |
| 6 | Read settings from a training relay |
| 7 | Save an original configuration backup |
| 8 | Modify a permitted setting in an offline copy |
| 9 | Compare two settings files |
| 10 | Retrieve an event report |
| 11 | Review SER information |
| 12 | Open the HMI and review measured quantities |
| 13 | Establish Ethernet communication in a controlled training environment |
| 14 | Use the terminal to retrieve supported relay information |
These exercises provide a useful foundation before working with live protection systems.
19. Official SEL QuickSet learning resources
SEL provides several useful resources for engineers who want to learn QuickSet.
SEL eLearning: Introduction to acSELerator QuickSet
SEL offers a complimentary two-hour introductory course called eSW 101: Introduction to acSELerator QuickSet.
The course includes:
- QuickSet orientation.
- Installation.
- Connecting to SEL devices.
- Reading and sending settings.
- Comparing settings.
- Settings-file management.
- Retrieving event reports.
- HMI features.
- Basic terminal commands.
Official course page:
Official QuickSet support and video tutorials
The SEL support page provides videos covering topics such as:
- QuickSet Device Manager.
- Relay firmware updates.
- Using the HMI.
- Ethernet connection setup.
- Copying relay setting groups.
- Settings conversion.
- Terminal commands.
- Device Manager database management.
Official support page:
QuickSet documentation
Official product documentation and application guides:
Conclusion
acSELerator QuickSet is an essential engineering tool for working with SEL protection relays.
The most important practical skills are establishing communication, reading and backing up existing settings, understanding the settings structure, modifying approved protection parameters, transferring configurations, comparing settings and retrieving event records.
Engineers should develop these skills using training devices or offline settings files before performing configuration changes on operational protection systems.
Remember that learning the software is only one part of protection engineering. Correct relay configuration also requires knowledge of power system faults, CT and VT circuits, protection coordination, control logic and commissioning procedures.
Learn SEL acSELerator QuickSet with Elec-Engg
Elec-Engg provides practical power system protection and substation automation training for engineers and technical professionals.