- 1. Introduction
- 2. What Is Restricted Earth Fault Protection?
- 3. Why Is REF Protection Required?
- 4. REF Protection Operating Principle
- 5. REF Protection Zone
- 6. Transformer Applications
- 7. High-Impedance REF Protection
- 8. Low-Impedance REF Protection
- 9. High-Impedance Versus Low-Impedance REF
- 10. CT Requirements and Connections
- 11. REF Protection and Transformer Vector Group
- 12. REF Protection Settings
- 13. Practical Calculation Example: Transformer REF
- 14. REF Protection and Transformer Differential Protection (ANSI 87T)
- 15. GE Multilin REF Protection Applications
- 16. General GE Multilin REF Configuration Workflow
- 17. REF Testing and Commissioning
- 18. Common REF Protection Problems and Troubleshooting
- 19. REF Commissioning Checklist
- 20. Best Engineering Practices
- 21. Training on GE Multilin Protection Relays by Elec-Engg
- 22. Frequently Asked Questions
- What is REF protection in a transformer?
- What is the difference between REF and transformer differential protection?
- Why is a neutral CT required for REF?
- Can REF detect an earth fault close to the transformer neutral?
- What is the difference between high-impedance and low-impedance REF?
- Can REF operate for an external earth fault?
- Does every GE Multilin transformer relay support REF?
- Is REF applicable to an unearthed transformer winding?
- How is REF protection tested?
- 23. Related Articles
- Conclusion
1. Introduction
Restricted Earth Fault (REF) protection is a sensitive protection function used to detect earth faults within a defined zone of electrical equipment, particularly power transformers.
It is designed to provide sensitive detection of winding-to-earth faults while remaining stable during external earth faults and normal load conditions.
REF protection is particularly valuable for transformer windings where conventional transformer differential protection (ANSI 87T) may not provide sufficient sensitivity for certain earth faults close to the transformer neutral point.
In GE Multilin protection applications, REF functionality and implementation depend on the relay model, firmware, CT input arrangement, and protection scheme. Some applications use an integrated low-impedance REF element, while others use a dedicated high-impedance REF scheme or external protection equipment.
This article explains REF operating principles, CT connections, high- and low-impedance schemes, practical calculations, engineering settings, commissioning, and troubleshooting.
2. What Is Restricted Earth Fault Protection?
Restricted Earth Fault protection detects earth faults within a specific electrical zone.
For a transformer winding, the protected zone is generally defined by the phase CTs and the neutral CT.
The principle is based on comparing the residual current calculated from the three phase CTs with the current measured by the neutral CT.
Under normal operating conditions and for external faults, the currents should balance according to the CT polarity and connection arrangement.
For an internal earth fault, the balance is disturbed and a differential current appears.
The REF function detects this imbalance and issues a trip when the operating conditions satisfy the configured criteria.
Main characteristics
- Sensitive detection of internal earth faults.
- Restricted protection zone.
- Stability for external earth faults when correctly engineered.
- Application to grounded transformer windings.
- Complementary protection to transformer differential protection.
- High-impedance or low-impedance implementation.
3. Why Is REF Protection Required?
Transformer differential protection (ANSI 87T) is the main protection against internal phase and earth faults within the transformer differential zone.
However, the sensitivity of differential protection to earth faults may be limited by several factors:
- Fault location along the winding.
- Neutral grounding arrangement.
- Fault current magnitude.
- Transformer vector group.
- CT ratio and accuracy.
- Differential protection restraint characteristics.
- Zero-sequence current compensation.
For example, an earth fault close to the neutral point of a grounded-wye winding may produce relatively low fault current.
Depending on the system grounding arrangement and protection design, the differential current may not be sufficient to operate the transformer differential element quickly.
REF protection can provide a more sensitive dedicated earth-fault protection zone.
4. REF Protection Operating Principle
The REF scheme compares the residual current from the three phase CTs with the neutral CT current.
The residual current is:
[
I_{\text{res}}=I_A+I_B+I_C
]
The signs and directions of the currents must be defined consistently according to the CT polarity and wiring arrangement.
For a simplified REF arrangement, the operating or differential current can be expressed as:
[
I_{\text{diff}}=|I_A+I_B+I_C-I_N|
]
Where:
- (I_A) = phase-A CT secondary current.
- (I_B) = phase-B CT secondary current.
- (I_C) = phase-C CT secondary current.
- (I_N) = neutral CT secondary current.
The equation is illustrative. The actual relay convention may use different current directions, scaling, or compensation.
4.1 Normal load condition
During normal balanced load operation:
[
I_A+I_B+I_C\approx0
]
The neutral current is also approximately zero for a balanced system without relevant earth-current components.
Therefore, the REF operating current should remain below the pickup threshold.
4.2 External earth fault
For an external earth fault, the phase residual current and neutral current should balance when the CTs are correctly connected and have suitable characteristics.
The REF scheme should remain stable.
4.3 Internal earth fault
For an earth fault inside the protected zone, the current balance is disturbed.
A differential current develops, and the REF protection operates when the configured pickup and operating conditions are satisfied.
5. REF Protection Zone
The protected zone is defined by the location of the phase CTs and neutral CT.
<AsyncImage query=”restricted earth fault transformer protection CT connection phase CT neutral CT protected zone single line schematic” aspectRatio=”16:9″ width=”100%”/>
For a typical grounded-wye transformer winding:
- Three phase CTs are installed on the phase connections.
- A neutral CT is installed in the transformer neutral connection.
- The REF scheme compares the residual phase current with the neutral current.
- The protected winding section lies between the CT measurement boundaries.
The precise zone depends on the physical CT locations and the scheme design.
Any equipment or conductor section between the CT boundaries may be included in the protected zone. Conversely, faults outside the boundaries should be treated as external faults.
6. Transformer Applications
REF protection is commonly applied to grounded transformer windings.
Typical applications include:
- 132/33 kV power transformers.
- 132/11 kV power transformers.
- 33/11 kV distribution transformers.
- Generator step-up transformers.
- Autotransformers, where the protection design supports the required arrangement.
- Grounded-wye transformer windings in industrial power systems.
REF protection requires a suitable neutral grounding arrangement and an appropriate CT configuration.
A winding with an isolated or unearthed neutral does not provide the conventional neutral-current measurement required by a standard REF scheme.
The protection engineer must assess the actual grounding arrangement before selecting REF protection.
7. High-Impedance REF Protection
High-impedance REF is a traditional and widely used differential protection arrangement.
It uses an external stabilizing resistor and, in many designs, a nonlinear voltage-limiting device such as a metal-oxide varistor (MOV).
The principle is to ensure that the scheme remains stable during external faults even when CT saturation produces an unwanted differential voltage.
7.1 Operating principle
Under normal conditions, the CT secondary currents balance and the voltage across the high-impedance circuit remains low.
During an internal earth fault, the differential current drives current through the high-impedance operating circuit.
If the resulting voltage exceeds the relay operating threshold, the protection trips.
7.2 Stabilizing resistor
The stabilizing resistor increases the circuit impedance and helps prevent unwanted operation caused by CT mismatch or saturation during external faults.
The resistor value must be calculated using the scheme design, CT characteristics, maximum through-fault current, and relay operating requirements.
It must not be selected arbitrarily.
7.3 Nonlinear voltage-limiting device
During severe internal faults, the voltage across the high-impedance circuit can become high.
A suitable nonlinear voltage-limiting device may be installed to protect the relay circuit and insulation.
The device must be selected according to the scheme design and expected fault conditions.
7.4 High-impedance scheme requirements
Typical engineering considerations include:
- CT ratio matching.
- CT class and excitation characteristics.
- CT secondary resistance.
- Lead resistance.
- Stabilizing resistor selection.
- Relay operating voltage.
- Voltage-limiting device characteristics.
- CT secondary wiring and earthing.
High-impedance REF is often implemented using a dedicated relay arrangement rather than a numerical relay’s conventional low-impedance differential element.
The exact scheme must be checked against the manufacturer’s application documentation.
8. Low-Impedance REF Protection
Low-impedance REF uses numerical differential protection principles.
The relay receives the phase-current measurements and neutral-current measurement, then calculates the operating and restraint quantities.
Unlike a conventional high-impedance scheme, the low-impedance arrangement does not rely on the same external stabilizing resistor principle.
8.1 Operating principle
The relay compares the residual phase current with the neutral current.
A simplified operating current is:
[
I_{\text{op}}=|I_A+I_B+I_C-I_N|
]
A restraint quantity may also be calculated from the measured currents.
One possible simplified representation is:
[
I_{\text{rest}}=|I_A+I_B+I_C|+|I_N|
]
However, actual relay restraint definitions vary by manufacturer and algorithm.
The relay operates when the differential current satisfies its configured characteristic.
8.2 Advantages of low-impedance REF
- Numerical measurement and supervision.
- Flexible pickup and characteristic settings.
- Potential integration with transformer protection.
- Event recording and fault analysis.
- Configurable logic and trip outputs.
- Reduced dependence on a dedicated external stabilizing resistor arrangement.
The actual advantages and available features depend on the selected relay.
9. High-Impedance Versus Low-Impedance REF
| Feature | High-impedance REF | Low-impedance REF |
|---|---|---|
| Operating principle | High-impedance differential circuit | Numerical differential calculation |
| Stabilizing resistor | Normally required | Not used in the same conventional arrangement |
| CT matching | Very important | Important |
| CT saturation stability | Achieved through scheme design and high impedance | Managed by relay algorithm and CT engineering |
| Settings | Resistor, voltage, stability calculations | Pickup and characteristic settings |
| Event recording | Depends on relay | Often available in numerical relay |
| Configuration | External wiring and components | Relay settings and signal logic |
| Application | Dedicated REF schemes | Integrated numerical protection schemes |
Neither arrangement should be considered universally superior. Selection depends on the transformer design, CT installation, protection philosophy, and available relay technology.
10. CT Requirements and Connections
CT engineering is one of the most important parts of REF protection.
Incorrect CT polarity, ratio, phase assignment, or wiring can cause unwanted operation or failure to detect an internal earth fault.
10.1 Phase CTs
The three phase CTs provide the current measurements used to calculate residual current.
Their ratios and secondary ratings must be suitable for the protection scheme.
10.2 Neutral CT
The neutral CT measures current flowing through the transformer neutral grounding connection.
It must be installed and connected so that its measured current has the correct polarity relative to the phase CT residual current.
10.3 CT ratio matching
For many conventional REF schemes, matching CT ratios is important.
For numerical low-impedance schemes, ratio differences may be accommodated by relay scaling or compensation where supported, but this must be verified in the product documentation.
10.4 CT polarity
CT polarity must be checked carefully.
A reversed neutral CT can cause the measured currents to add rather than balance, resulting in incorrect REF operation.
The engineer should verify:
- P1/P2 orientation.
- S1/S2 terminal connections.
- Phase CT polarity consistency.
- Neutral CT polarity.
- Secondary current direction.
- Correct relay input assignment.
10.5 CT secondary earthing
CT secondary circuits must be earthed in accordance with the approved protection and instrumentation design.
Multiple unintended earth connections can create circulating currents and measurement errors.
Never open-circuit an energized CT secondary circuit. Use approved shorting facilities and safe testing procedures.
11. REF Protection and Transformer Vector Group
Transformer vector group affects current phase displacement and zero-sequence current behavior.
REF protection is normally applied to an individual grounded winding and its associated neutral connection.
Unlike transformer differential protection, which may require compensation for transformer vector-group phase displacement, a conventional REF scheme compares currents within the same winding zone.
However, the complete transformer protection design must consider:
- Winding connection.
- Neutral grounding.
- CT locations.
- Phase CT arrangement.
- Neutral CT arrangement.
- Zero-sequence current paths.
- Autotransformer connections, where applicable.
Do not assume that a standard REF connection can be transferred directly to every transformer vector group.
12. REF Protection Settings
REF settings must be selected according to the protection scheme, transformer data, CT characteristics, and minimum internal earth-fault current.
Important setting considerations include:
- REF pickup current.
- Operating characteristic.
- Restraint or bias settings, where applicable.
- High-impedance stabilizing voltage, where applicable.
- Stabilizing resistor.
- CT circuit resistance.
- CT excitation performance.
- Trip logic.
- Alarm and supervision signals.
12.1 REF pickup current
The pickup setting must be sensitive enough to detect the minimum internal earth-fault current while remaining secure under normal and external-fault conditions.
For a numerical low-impedance scheme, pickup may be specified in secondary amperes or as a percentage of the relay rated current, depending on the product.
12.2 Minimum internal earth-fault current
The available fault current depends on the grounding method and the fault location.
For a resistance-grounded transformer neutral, a simplified approximation is:
[
I_f\approx\frac{V_{\text{ph}}}{R_N}
]
Where:
- (V_{\text{ph}}) is the phase-to-neutral voltage.
- (R_N) is the neutral grounding resistance.
This simplified equation neglects other circuit impedances and must not replace a complete fault study.
12.3 Sensitivity near the neutral point
The fault voltage to earth generally decreases as the fault location approaches the neutral point of a grounded-wye winding.
Therefore, the available earth-fault current may also decrease, depending on the grounding arrangement and system impedance.
The engineer must calculate the minimum fault current at the most difficult location to protect.
REF pickup should be assessed against this minimum value with adequate security margin.
13. Practical Calculation Example: Transformer REF
Consider a 40 MVA, 132/33 kV transformer with a grounded-wye 33 kV winding.
Assume:
- Transformer rating: 40 MVA.
- LV voltage: 33 kV.
- Neutral grounding resistor: 100 ohms.
- Neutral CT ratio: 600/1 A.
- Illustrative minimum fault voltage at the neutral connection: 19.05 kV phase-to-neutral.
The approximate earth-fault current for a fault at the phase terminal, neglecting other impedances, is:
[
I_f\approx\frac{19,050}{100}
]
[
I_f\approx190.5\text{ A}
]
The corresponding neutral CT secondary current is:
[
I_s=\frac{190.5}{600}
]
[
I_s\approx0.318\text{ A}
]
This calculation illustrates the relationship between grounding resistance, fault current, and CT secondary current.
It does not establish the REF pickup setting. The actual setting must consider:
- Minimum fault current throughout the protected winding.
- Neutral grounding system.
- CT accuracy and excitation.
- Relay pickup tolerance.
- Through-fault stability.
- Measurement scaling.
- Manufacturer-specific operating characteristic.
14. REF Protection and Transformer Differential Protection (ANSI 87T)
REF and transformer differential protection are complementary functions.
| Feature | Transformer differential (87T) | REF (64REF) |
|---|---|---|
| Main purpose | Internal phase and earth-fault protection | Sensitive earth-fault protection |
| Protected zone | Defined by transformer phase CT boundaries | Defined by phase and neutral CT boundaries |
| Fault coverage | Phase and earth faults, subject to scheme design | Earth faults within restricted zone |
| CT arrangement | CTs on transformer connections | Phase CTs and neutral CT |
| Sensitivity | Depends on differential characteristics and fault current | Designed for sensitive internal earth-fault detection |
| External fault stability | Bias/restraint and CT compensation | CT balance and scheme-specific stability |
| Application | Main transformer protection | Complementary winding protection |
Both functions may operate for an internal earth fault.
The trip matrix must ensure that the required circuit breakers are opened and that the appropriate lockout and alarm logic is activated.
15. GE Multilin REF Protection Applications
GE Multilin protection products offer different protection capabilities depending on the relay family and firmware.
Transformer protection applications may involve products such as:
- T60 Transformer Protection System.
- 845 Transformer Protection System.
- Other GE Multilin products where the required protection elements are explicitly supported.
The engineer must verify whether the selected relay provides:
- Integrated low-impedance REF.
- Dedicated neutral or residual current inputs.
- Required current input configuration.
- Suitable differential or REF characteristics.
- Applicable trip and alarm logic.
- The necessary setting and supervision features.
Do not assume that every GE Multilin transformer relay includes the same REF implementation.
A high-impedance REF scheme may require separate hardware and external components even where the main transformer relay provides conventional differential protection.
16. General GE Multilin REF Configuration Workflow
The following is a generic engineering workflow. Actual settings, menu structures, and function names depend on the relay model and firmware.
Step 1 – Verify relay capability
Confirm:
- Exact relay model.
- Firmware version.
- Current input configuration.
- Available protection elements.
- REF functionality.
- Required neutral CT input.
- Applicable engineering software.
Step 2 – Review the CT arrangement
Document:
- Phase CT ratios.
- Neutral CT ratio.
- CT secondary ratings.
- CT polarity.
- Physical CT locations.
- Secondary wiring.
- Earthing arrangement.
Step 3 – Calculate the expected operating current
Calculate:
- Normal residual current.
- External-fault through current.
- Minimum internal earth-fault current.
- CT secondary current.
- Expected REF differential current.
Step 4 – Select the protection implementation
Determine whether the project requires:
- High-impedance REF.
- Low-impedance REF.
- Dedicated REF relay.
- Integrated transformer protection element.
- External differential protection arrangement.
Step 5 – Configure settings
Where supported, configure:
- REF enable/disable.
- Pickup current.
- Restraint characteristic.
- CT scaling.
- Operating delay, if applicable.
- Alarm and trip logic.
- Binary output mapping.
For high-impedance schemes, calculate and verify the external stabilizing components separately.
Step 6 – Configure trip logic
Verify the intended trip destinations.
For a transformer internal earth fault, the trip scheme may include:
- HV circuit breaker.
- LV circuit breaker.
- Tertiary circuit breaker, where applicable.
- Transformer lockout relay (86).
- Alarm and event indications.
The final trip arrangement must follow the approved transformer protection philosophy.
17. REF Testing and Commissioning
REF testing must verify current measurement, CT polarity, operating sensitivity, external-fault stability, and the complete trip path.
17.1 Pre-commissioning checks
Before testing:
- Confirm approved protection settings.
- Verify relay model and firmware.
- Check phase CT ratios.
- Check neutral CT ratio.
- Verify CT polarity.
- Confirm secondary wiring.
- Check CT secondary earthing.
- Verify the protected zone.
- Review the transformer grounding arrangement.
- Confirm trip output destinations.
17.2 CT polarity and balance test
Inject suitable current into the phase and neutral CT circuits according to the approved test arrangement.
Verify that the measured residual and neutral currents balance under the simulated external-fault condition.
Incorrect polarity should be identified before enabling the protection for service.
17.3 REF pickup test
For low-impedance REF:
- Establish the correct CT input configuration.
- Inject the required current quantities.
- Increase the differential current gradually.
- Record the pickup value.
- Compare the result with the approved setting and relay tolerance.
For high-impedance REF, follow the dedicated scheme test procedure, including verification of the stabilizing resistor and operating voltage.
17.4 External-fault stability test
Simulate an external earth fault using the approved test method.
Verify that the phase residual and neutral current quantities balance and that the REF scheme remains stable.
The test should consider CT ratio and polarity errors and the applicable scheme stability requirements.
17.5 Internal-fault operating test
Simulate an internal earth fault by creating the required differential current in the test circuit.
Confirm:
- Correct REF pickup.
- Correct operating indication.
- Correct trip output.
- Correct lockout operation.
- Correct event recording.
17.6 Trip circuit verification
Verify that the REF trip command reaches all required circuit breakers and the lockout system.
Check:
- Trip output contact.
- Interposing relays, where used.
- Breaker trip coil.
- Breaker auxiliary contacts.
- Lockout relay.
- Alarm and indication circuits.
Never perform live primary fault tests without an approved test plan, risk assessment, and safe isolation arrangements.
18. Common REF Protection Problems and Troubleshooting
Problem 1 – REF trips during an external earth fault
Possible causes:
- Incorrect CT polarity.
- CT ratio mismatch.
- CT saturation.
- Incorrect secondary wiring.
- Incorrect relay current assignment.
- High-impedance scheme design error.
- Incorrect low-impedance restraint configuration.
Recommended checks:
- Verify phase and neutral CT polarity.
- Check CT ratios and input scaling.
- Review event records and oscillography.
- Examine CT excitation characteristics.
- Verify scheme calculations.
Problem 2 – REF does not operate for an internal earth fault
Possible causes:
- REF function disabled.
- Pickup too high.
- Incorrect neutral CT connection.
- Incorrect phase CT wiring.
- Missing current input.
- Incorrect trip logic.
- Insufficient fault current.
Recommended checks:
- Verify REF enable status.
- Check all current measurements.
- Review the minimum earth-fault current calculation.
- Test pickup using secondary injection.
- Verify trip output mapping.
Problem 3 – REF operates during normal load
Possible causes:
- CT polarity error.
- Incorrect phase assignment.
- CT ratio mismatch.
- Secondary wiring problem.
- Unbalanced CT performance.
- Incorrect current scaling.
Recommended checks:
- Compare phase and neutral current measurements.
- Verify CT polarity.
- Review measured residual current.
- Inspect secondary connections.
Problem 4 – REF sensitivity is insufficient
Possible causes:
- Pickup setting too high.
- High neutral grounding resistance.
- Fault location close to the neutral point.
- Incorrect CT ratio.
- Inadequate protection-zone design.
Recommended checks:
- Calculate minimum winding earth-fault current.
- Review grounding resistance.
- Confirm CT ratios.
- Assess the relay sensitivity.
- Consider additional neutral or stator/winding earth-fault protection where appropriate.
Problem 5 – High-impedance REF operates incorrectly
Possible causes:
- Incorrect stabilizing resistor.
- Incorrect CT secondary resistance.
- Inadequate CT excitation performance.
- Incorrect voltage-limiting device selection.
- Wiring or component failure.
Recommended checks:
- Recalculate scheme stability.
- Measure resistor value.
- Verify CT excitation data.
- Inspect the voltage-limiting device.
- Check all CT secondary connections.
19. REF Commissioning Checklist
| No. | Inspection or test | Result |
|---|---|---|
| 1 | Confirm REF protection application | ☐ |
| 2 | Verify relay model and firmware | ☐ |
| 3 | Confirm protected-zone boundaries | ☐ |
| 4 | Verify phase CT ratios | ☐ |
| 5 | Verify neutral CT ratio | ☐ |
| 6 | Check phase CT polarity | ☐ |
| 7 | Check neutral CT polarity | ☐ |
| 8 | Verify CT secondary wiring | ☐ |
| 9 | Check CT secondary earthing | ☐ |
| 10 | Calculate minimum internal fault current | ☐ |
| 11 | Verify REF pickup setting | ☐ |
| 12 | Test current measurement and balance | ☐ |
| 13 | Perform REF pickup test | ☐ |
| 14 | Test external-fault stability | ☐ |
| 15 | Test internal-fault operation | ☐ |
| 16 | Verify trip logic | ☐ |
| 17 | Test lockout operation | ☐ |
| 18 | Verify alarms and event records | ☐ |
| 19 | Save final settings | ☐ |
| 20 | Complete commissioning report | ☐ |
20. Best Engineering Practices
For reliable REF protection:
- Define the protected zone clearly using the physical CT locations.
- Verify that the transformer winding has a suitable grounding arrangement.
- Select high-impedance or low-impedance REF according to the application.
- Verify phase and neutral CT ratios and polarity.
- Calculate the minimum internal earth-fault current.
- Check CT performance during maximum external earth faults.
- Coordinate REF with transformer differential protection.
- Verify all trip destinations and lockout logic.
- Perform both operating and stability tests.
- Retain the CT calculations, approved settings, and commissioning records.
REF protection is highly dependent on correct CT engineering. Even a sophisticated numerical relay cannot compensate for an incorrectly designed or wired protection zone.
21. Training on GE Multilin Protection Relays by Elec-Engg
Practical REF engineering requires an understanding of transformer winding connections, neutral grounding, CT circuits, differential protection, relay settings, and secondary injection testing.
Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for engineers involved in power-system protection, transformer protection, relay engineering, commissioning, operation, and maintenance.
Relevant training subjects include:
- GE Multilin transformer protection relays.
- T60 and 845 transformer protection applications.
- Transformer differential protection (ANSI 87T).
- Restricted earth fault protection (ANSI 64REF).
- CT ratio, polarity, and secondary circuit verification.
- Transformer vector-group compensation.
- Neutral grounding and earth-fault protection.
- EnerVista configuration and settings management.
- Secondary injection and functional testing.
- Protection coordination and troubleshooting.
Training delivery options include:
- Pre-recorded technical video courses.
- Structured self-paced training.
- Live online training.
- Face-to-face technical training.
- Customized in-house training for companies and utilities.
Visit Elec-Engg to explore available courses or contact us to discuss a customized training requirement.
22. Frequently Asked Questions
What is REF protection in a transformer?
Restricted Earth Fault protection detects earth faults within a defined transformer winding zone using phase CT residual current and neutral CT current.
What is the difference between REF and transformer differential protection?
Transformer differential protection covers internal phase and earth faults across its defined transformer zone. REF provides dedicated, sensitive earth-fault protection for a specific grounded winding section.
Why is a neutral CT required for REF?
The neutral CT measures the current flowing through the transformer neutral connection. Its measurement is compared with the residual current from the three phase CTs.
Can REF detect an earth fault close to the transformer neutral?
Yes, REF can provide sensitive detection of earth faults within its protected zone. However, the available fault current may decrease toward the neutral point. The protection sensitivity must therefore be assessed using the actual grounding arrangement and minimum fault-current calculation.
What is the difference between high-impedance and low-impedance REF?
High-impedance REF uses an external high-impedance operating circuit, generally with a stabilizing resistor and voltage-limiting device. Low-impedance REF uses numerical current measurement and differential/restraint calculations.
Can REF operate for an external earth fault?
A correctly designed REF scheme should remain stable for external faults. CT polarity, ratio, wiring, CT performance, and scheme design are critical.
Does every GE Multilin transformer relay support REF?
No. The availability and implementation of REF depend on the exact relay model, firmware, and hardware configuration. The product documentation must be checked.
Is REF applicable to an unearthed transformer winding?
Conventional neutral-CT-based REF requires a suitable grounded-neutral arrangement. Other earth-fault protection methods may be required for unearthed or isolated-neutral systems.
How is REF protection tested?
Testing includes CT polarity and balance verification, pickup testing, external-fault stability testing, internal-fault operation testing, and complete trip-circuit verification.
23. Related Articles
- GE Multilin Transformer Differential Protection (ANSI 87T).
- GE Multilin CT and VT Configuration.
- GE Multilin Protection Functions and ANSI Device Numbers.
- GE Multilin Transformer Protection: T60 and 845.
- GE Multilin Protection Relay Testing and Commissioning.
- GE Multilin Overcurrent and Earth-Fault Protection.
- GE Multilin EnerVista Software: Configuration and Troubleshooting.
Conclusion
Restricted Earth Fault protection is an important component of transformer protection, particularly for grounded-wye windings where sensitive earth-fault detection is required.
By comparing the residual current from the phase CTs with the neutral CT current, REF detects internal earth faults within a clearly defined protection zone while remaining stable for external faults when correctly engineered.
Reliable REF protection depends on correct CT selection, polarity, wiring, grounding arrangements, pickup calculations, and comprehensive commissioning tests.
For GE Multilin applications, engineers must verify the exact REF capability and implementation of the selected relay model and firmware before developing the final protection scheme.
