Siemens DIGSI 4 Tutorial: Installation, Project Management, Device Configuration & Parameterization
Siemens DIGSI 4 is an engineering software tool used for configuring, parameterizing, commissioning, and operating SIPROTEC 4 protection relays.
This tutorial introduces the main DIGSI 4 engineering procedures, from software installation and project creation to device selection, project organization, and parameter configuration.
The tutorial covers four important areas:
- Installing DIGSI 4
- Managing Projects
- Working with SIPROTEC 4 Devices
- Optimizing Parameterization
1. Installing DIGSI 4
Before starting relay engineering, DIGSI 4 must be correctly installed on the engineering PC or notebook.
The installation should include the required software components, supported SIPROTEC device packages, and communication drivers.
After installation, start the DIGSI 4 Manager to begin creating and managing engineering projects.
2. Managing Projects in DIGSI 4
Project management is the first step in engineering a SIPROTEC 4 protection relay.
DIGSI 4 Manager provides a structured environment for organizing protection devices, substation configurations, and engineering data.
2.1 Creating a New Project
To create a new project:
- Start the DIGSI 4 Manager.
- Click File → New in the menu bar.
- Enter a name for the new project, for example, Project 1.
- Do not modify other settings unless required.
- Click OK.
The new project window will appear in the DIGSI 4 Manager workspace.
2.2 Understanding the Project Window
The DIGSI 4 Manager interface consists of two main areas:
Tree View – Left Window Pane
The left pane displays project containers in a hierarchical tree structure. It shows the organization of the project, including folders and substation-related levels.
List View – Right Window Pane
The right pane displays the objects contained within the selected project folder or hierarchical level.
Depending on the installed DIGSI components, additional objects such as phone books and modem profiles may also be displayed.
2.3 Project Objects in DIGSI 4
A DIGSI 4 project can contain different types of objects:
- Project: The main container representing the entire engineering project.
- Folder: Used to organize project information and structure.
- Phone Book: Stores station addresses for modem-based communication.
- Modem: Stores modem profiles used for remote communication.
- SIPROTEC 4 Device: Represents a real SIPROTEC 4 relay with its parameter settings and process data.
- V3/V2 Device: Provides access to older SIPROTEC device data processed using DIGSI V3.x.
- SIPROTEC 4 Version: Stores different parameter setting versions associated with a SIPROTEC 4 device.
Phone Book and Modem objects are created automatically when the DIGSI 4 Remote component is installed.
2.4 Organizing the Project Structure
A well-organized project structure makes relay engineering easier, especially when working with multiple feeders, substations, and protection devices.
For example, a project can be organized as follows:
- Project 1
- Region North
- Substation 1
- Feeder 1
- Feeder 2
- Transformer 1
- Substation 2
- Feeder 1
- Feeder 2
- Substation 1
- Region North
To create this structure:
- Create a new project.
- Rename the automatically created hierarchical level to Region North.
- Right-click an existing hierarchical level.
- Select Insert New Object → Hierarchical Level.
- Enter the required name.
- Repeat the procedure to create additional levels.
Folder names and hierarchical levels can be customized according to the requirements of the engineering project.
The project hierarchy supports up to nine levels.
3. Working with SIPROTEC 4 Devices
After creating the project structure, the next step is to insert the required protection relays.
DIGSI 4 includes a Device Catalog containing the SIPROTEC 4 devices installed in the DIGSI 4 Manager.
3.1 Opening the Device Catalog
To open the Device Catalog:
- Select the required folder or hierarchical level.
- Click View → Device Catalog.
- The Device Catalog window will open.
- Browse the available device families.
The catalog can remain open while working in the DIGSI 4 Manager.
3.2 Selecting a SIPROTEC 4 Relay
The Device Catalog is organized into different protection relay families.
For example, selecting the 7SJ family displays the installed SIPROTEC 4 overcurrent protection relay models and their available variants.
Other device families can be selected according to the required protection application.
The lower section of the Device Catalog displays technical information about the selected device.
After selecting the required relay, insert it into the appropriate hierarchical level of the project.
Important: Protection devices cannot be inserted directly underneath the main project folder. They must be assigned to an appropriate hierarchical level.
3.3 Understanding the MLFB Number
MLFB stands for Maschinenlesbare Fabrikatebezeichnung, the machine-readable product designation used by Siemens.
The MLFB number identifies the specific SIPROTEC 4 device type and hardware configuration.
The Device Catalog includes an MLFB tab for selecting the appropriate device order number.
The MLFB selection is important because it determines the available hardware configuration and subsequent parameterization options.
The configured DIGSI device must correspond to the actual SIPROTEC relay when establishing communication.
Incorrect device or hardware identification can cause compatibility and communication problems.
4. Configuring Device Properties
DIGSI 4 provides an Object Properties dialog box for managing project and device information.
Properties may include:
- Object name.
- Description and comments.
- Date of creation.
- Device MLFB number.
- Device communication settings.
- Other device-specific configuration information.
4.1 Opening Object Properties
To view or modify object properties:
- Select the required project object.
- Click View → Details.
- Alternatively, right-click the object and select its properties.
- You can also use Edit → Object Properties.
The Object Properties dialog box displays the available settings.
4.2 Editing Property Values
The dialog box uses different text box states:
- White text boxes: Property values can generally be edited.
- Grayed text boxes: Values are not editable.
- Conditionally activated fields: Some fields become available depending on other selected configuration values.
Modify the required properties and save the changes.
5. Optimizing Parameterization
Correct project organization and device identification provide the foundation for efficient relay parameterization.
Before modifying protection settings, engineers should verify:
- Correct SIPROTEC relay model.
- Correct MLFB and hardware configuration.
- Current and voltage transformer ratios.
- Rated frequency.
- Protection application and function availability.
- Binary input and output configuration.
- Communication parameters.
- Device-specific settings and parameter groups.
Always compare the configured settings with the approved protection design and coordination study.
6. DIGSI 4 Training by Elec-Engg
Want to learn Siemens DIGSI 4 and SIPROTEC 4 relay engineering practically?
Elec-Engg offers comprehensive training covering DIGSI 4, DIGSI 5, SIPROTEC protection relays, and IEC 61850 engineering.
Our professional training programs cover:
- DIGSI 4 installation and project management.
- SIPROTEC 4 device configuration.
- Protection function parameterization.
- Overcurrent and earth fault protection.
- Distance and transformer protection.
- Binary inputs and outputs.
- CFC logic and interlocking.
- Communication and IEC 61850 configuration.
- Relay testing and commissioning.
Explore our DIGSI 4, DIGSI 5 and IEC 61850 Configuration Professional Training Package:
https://elec-engg.com/professional-package-digsi-4-digsi-5-iec-61850-configuration-pack
Training is available through online courses, structured self-paced learning, face-to-face training, and customized in-house programs.
Elec-Engg – Practical Courses by Dr Saeed Roostaee / Elec-Engg.
- Installing DIGSI 4
- Managing Projects
- Working with the Devices
- Optimizing Parameterization
Sample page of the file:
The first step is to create a new project. The DIGSI Manager has been started, a project dialog box has not yet been opened.
Click File- New of the menu bar, enter a new project name and confirm with OK.
The project dialog box is displayed.
Names and symbols of all project containers are displayed in a hierarchical tree structure. To put it less complicated, we could say that containers are displayed. This pane is called a tree view. An opened folder is the first symbol to be displayed in this pane. The opened folder is designated as project 1 and represents the top level, the project itself.
The right pane of the window shows a folder-type object. If the DIGSI 4 Remote program is installed, a phone book type object and modem type object each are displayed in addition. Otherwise, this pane of the window continues to remain empty. This page serves to display further names of symbols of objects, which are contained in one of the selected containers of the tree view. To put it less complicated, we could say that this pane shows objects. Since the right pane of the window is represented as a list, this structure is called a list view.
Up to four objects are first automatically created within a new project of the tree view.
– Project (cannot be inserted manually)
– Folder (to structure a project)
– Phone Book (station addresses for a modem connection)
– Modem (for the communication SIPROTEC between your computer and the SIPROTEC 4 device
modem connection for the storage of modem profiles).
Phone Book and modem will be created automatically if the DIGSI 4 Remote component has been loaded.
The SIPROTEC 4 device object type represents a real SIPROTEC 4 device with all its setting values and process data.
The V3/V2 device object type serves to create shortcuts linked to the V3/V2 devices within the project structure. These device data are processed with DIGSI-V3.x.
The SIPOROTEC 4 version object type is created to document different parameter settings groups of a SIPROTEC 4 device. The device address (VD number) of the corresponding versions is identical to that of the original device.

The left window pane contains the names and symbols of all project containers in a hierarchical tree structure.
The right window pane displays the objects of the selected folders. The structure is designated as a list view.
Your first step to creating a system-specific project structure is to insert folder-type blank containers in the corresponding levels.
Click a folder object to insert a subordinate folder via the menu command ® Paste. A maximum of 9 levels is the permissible hierarchy depth.
Several objects can be juxtaposed in parallel.
The names of the folders can be renamed to easily adjust to the requirements of your operation.
As a first step, you create a new project. The DIGSI 4 Manager is started, no project window is open.
- Click File ® New in the menu bar.
- In the New dialog box, enter Project 1 as a name for the new project.
Don‘t modify any other settings. - Click OK.
The project window is now displayed in the working range. Put it to full size. - An object of the type Hierarchical level is inserted automatically upon creating a new project.
- Click this object and then click the selected name. Enter Region Nord as a new name.
- Right-click an existing hierarchical level and insert the lower-level hierarchical level via the context menu Insert new object ® Hierarchical level. Enter the new name.
- Click a hierarchical level, e.g. Feeder 1, and open the device catalog via the context menu.
- Select the device and draw it on the hierarchical level.
The Device Catalog shows all SIPROTEC 4 devices available (installed) in the DIGSI 4 Manager.
The device catalog is an independent item. When you open the catalog, a button is created in the taskbar by Windows. The device catalog can remain open while working with the DIGSI 4 Manager to install all required SIPROTEC 4 devices.
Select a folder type object and click View ® Device Catalog to open the Device Catalog window.
The device catalog has a structure. Clicking a plus sign or double-clicking a folder icon will open the subordinate level.
For example, if you double-click 7SJ (time overcurrent protection), all installed SIPROTEC 4 devices with the device type names and the variant numbers will be displayed.
Short technical information is displayed on the lower catalog border for each device selected.
Note: Devices cannot be placed directly underneath the project folder!
The MLFB tab serves to determine the order number of the selected SIPROTEC 4 device in DIGSI 4. The order number is the code for the type and variant of the SIPROTEC 4 device. The order number is called the MLFB number.
Order number determination in DIGSI 4 affects all further parameterization options. Identical MLFB numbers are necessary for the communication between the DIGSI 4 device operation and the connected SIPROTEC 4 device. This is checked when setting up the connection.
The MLFB tab contains several drop-down list boxes. The drop-down list boxes related to the selected SIPROTEC 4 device are activated, only. These drop-down list boxes serve to select the order numbers to define the SIPROTEC 4 design and type in DIGSI 4.

As a first step, create a new project. The DIGSI 4 Manager is started, no project window is open.
Click File ® New in the menu bar.
- In the New dialog box, enter Project 1 as a new project name.
Don‘t change any other settings. - Click OK.
The project window is now displayed in the working range. Put it to full size.
When creating a new project, an object of the type Hierarchical level is inserted automatically.
- Click this object and then click the selected name. Enter Region North as a new name.
- Right-click on an existing hierarchical level and insert a lower hierarchical level vie the context menu Insert new object ® Hierarchical level. Enter the new name.
- Click a hierarchical level, e.g. Feeder 1, and open the device catalog via the context menu.
- Select the device and draw it on the hierarchical level.
- As a first step, create a new project. The DIGSI 4 Manager is started, no project window is open. Click File ® New in the menu bar.
- In the New dialog box, enter Project 1 as a new project name.
Don‘t change any other settings. - Click OK.
The project window is now displayed in the working range. Put it to full size.
When creating a new project, an object of the type Hierarchical level is inserted automatically.
- Click this object and then click the selected name. Enter Region North as a new name.
- Right-click on an existing hierarchical level and insert a lower hierarchical level vie the context menu Insert new object ® Hierarchical level. Enter the new name.
- Click a hierarchical level, e.g. Feeder 1, and open the device catalog via the context menu.
- Select the device and draw it on the hierarchical level.
- In the New dialog box, enter Project 1 as a new project name.
Properties like object name, comment, or date of creation, have been assigned to all objects (General tab).
Some properties only refer to certain objects, for ex. the MLFB number for the SIPROTEC 4 devices or the device communication settings.
The values of the majority of the properties can be changed.
Select the object and click the View ® Details menu item to display the object properties. You can also open the Object Properties dialog box via the context menu or via the menu item Edit ® Object Properties.
If the property values are grayed, they cannot be changed. Depending on the entries you made in other text boxes, such text boxes may be activated. Property values in white/empty text boxes can be edited.