The SEL-387E Current Differential and Voltage Relay from Schweitzer Engineering Laboratories (SEL) is designed to provide protection, monitoring and control for two- and three-winding power transformers. It combines transformer differential protection, restricted earth fault (REF) protection, overcurrent protection, voltage and frequency elements, and transformer monitoring functions in one numerical protection relay.
The SEL-387E is particularly useful in substations and industrial power systems where engineers need dependable transformer protection together with flexible metering, event recording and automation capabilities.
This guide explains the relay’s applications, main protection functions, differential protection principles, CT compensation, setting considerations, communication features and practical testing methods.
SEL-387E Transformer Protection Relay: Complete Guide to Applications, Differential Protection, REF, Settings and Testing
- 1. What is the SEL-387E relay?
- 2. Applications of the SEL-387E
- 3. Main protection functions and ANSI codes
- 4. Transformer differential protection – 87T
- 5. CT compensation and transformer differential settings
- 6. Restricted earth fault protection – REF
- 7. Overcurrent protection – 50/51
- 8. Overexcitation protection – ANSI 24
- 9. Voltage and frequency protection
- 10. Monitoring, metering and event recording
- 11. Communication and substation automation
- 12. Configuration using acSELerator QuickSet
- 13. SEL-387E testing and commissioning
- 14. SEL-387E vs SEL-787 vs SEL-487E
- 15. Advantages of the SEL-387E
- 16. Frequently asked questions
- 17. SEL-387E protection relay training by Elec-Engg
- 18. Conclusion
1. What is the SEL-387E relay?
The SEL-387E is a microprocessor-based current differential and voltage protection relay. It is intended primarily for two- and three-winding power transformers, but can also be applied to reactors, generators, large motors and other multi-terminal power apparatus.
Its main protection functions include:
- Transformer differential protection (87T).
- Restricted earth fault protection (REF).
- Phase, negative-sequence and ground overcurrent protection.
- Overexcitation protection (24 V/Hz).
- Overvoltage and undervoltage protection.
- Overfrequency and underfrequency protection.
- Breaker-failure logic, where configured.
- Transformer through-fault monitoring.
The relay also provides oscillographic event reports, sequential event recording, metering, breaker contact wear monitoring and station battery monitoring. Exact capabilities and available communication options should always be checked against the relay’s hardware revision and ordering information.
2. Applications of the SEL-387E
The SEL-387E can be applied in several power-system configurations.
2.1 Two-winding power transformers
For a conventional two-winding transformer, current transformers on the primary and secondary sides provide the current measurements required for differential protection.
The relay compares the compensated currents entering and leaving the protected transformer zone. Under normal operating conditions and external faults, the differential current should remain low. An internal fault produces a significant differential current and can initiate transformer tripping.
2.2 Three-winding power transformers
The SEL-387E supports differential protection for transformers with up to three windings. Each winding can be represented by a three-phase current input.
This arrangement is useful for:
- Main transformers with tertiary windings.
- Generator step-up transformers with auxiliary tertiary windings.
- Three-winding grid transformers.
- Industrial transformers supplying multiple voltage levels.
The engineer must correctly define the current inputs included in the differential zone and configure the corresponding CT and transformer compensation.
2.3 Reactors and other power apparatus
The relay can also be applied to reactors, generators, large motors and other multi-terminal equipment where differential protection is required.
The suitability of the application depends on the equipment arrangement, available CTs, current-input configuration and protection philosophy.
3. Main protection functions and ANSI codes
The following table summarizes important SEL-387E protection and monitoring functions.
| ANSI code | Function | Application |
|---|---|---|
| 87T | Transformer differential | Internal phase and earth faults within the transformer differential zone |
| 87U | Unrestrained differential | Fast operation for high-magnitude internal faults |
| 64REF / REF | Restricted earth fault | Sensitive detection of grounded-wye winding earth faults |
| 50P / 51P | Phase overcurrent | Instantaneous and time-delayed phase fault protection |
| 50G / 51G | Ground overcurrent | Ground-fault backup protection |
| 50Q / 51Q | Negative-sequence overcurrent | Unbalanced fault detection |
| 24 | Volts-per-hertz | Transformer overexcitation protection |
| 27 | Undervoltage | Detection of low-voltage conditions |
| 59 | Overvoltage | Detection of excessive voltage |
| 81O / 81U | Overfrequency / underfrequency | Frequency protection and load shedding |
| 50BF | Breaker failure | Breaker-failure logic where configured |
| DFR | Digital fault recording | Oscillographic event reports |
| SER | Sequential Events Recorder | Recording changes in relay status and logic |
| BRM | Breaker wear monitoring | Monitoring breaker contact wear |
| SBM | Station battery monitoring | Monitoring station DC supply |
The exact implementation of some functions depends on the application and configuration. For example, breaker-failure protection may require application-specific logic rather than being treated as a universal standalone element.
4. Transformer differential protection – 87T
Transformer differential protection is the principal function of the SEL-387E.
The differential principle is based on comparing the currents entering and leaving the protected zone. After appropriate compensation, the relay calculates the differential and restraint quantities.
A simplified representation is:
Differential current:
[
I_{\mathrm{diff}} = \left|I_1+I_2+\cdots+I_n\right|
]
The currents are expressed using the relay’s configured reference directions and compensation.
Restraint current:
The restraint quantity is derived from the magnitudes of the compensated winding currents. Its exact calculation depends on the relay’s differential algorithm.
When the differential current exceeds the configured operating characteristic, the relay can identify an internal fault and issue a trip.
4.1 Percentage differential protection
The SEL-387E provides programmable single-slope or dual-slope percentage restraint characteristics.
Percentage restraint improves security during external faults and conditions where CT errors or saturation may create unwanted differential current.
A typical dual-slope characteristic has:
- A lower slope for normal operating conditions and relatively low restraint current.
- A higher slope for increased restraint current, improving stability during severe external faults and CT saturation.
The actual slope values and breakpoint must be selected according to the transformer, CT characteristics and protection study.
4.2 Unrestrained differential protection
The unrestrained differential element is intended to provide fast operation for high-magnitude internal faults.
It operates independently of the percentage-restraint characteristic and must be set high enough to remain secure for external faults and other abnormal current conditions.
4.3 Transformer inrush detection
Transformer energization can produce a high magnetizing inrush current. Since this current enters the transformer without an equivalent current leaving the other windings, it can appear as differential current.
The SEL-387E provides several methods to improve security during energization, including:
- Second-harmonic blocking or restraint.
- Fourth-harmonic blocking or restraint.
- Fifth-harmonic elements for overexcitation-related security.
- DC blocking.
The engineer can select the applicable blocking or restraint philosophy and configure the thresholds according to the transformer and system characteristics.
It is important not to copy harmonic settings from another transformer without checking the actual application.
5. CT compensation and transformer differential settings
Correct CT and transformer compensation is essential for reliable differential protection.
The currents measured on different transformer windings may have different magnitudes because of:
- Transformer rated voltage and power.
- CT ratios.
- Transformer winding connections.
- Phase displacement between windings.
- Tap-changer operating range.
- CT connection arrangements.
The SEL-387E provides settings for winding CT connections and current compensation. It also provides automatic tap calculations to assist engineers with differential settings.
Important setting considerations include:
- Transformer rated MVA.
- Rated voltage of each winding.
- Transformer vector group.
- CT ratios and secondary ratings.
- CT connection type.
- Differential element enablement for each winding.
- Differential tap calculations.
- Percentage-restraint slopes.
- Unrestrained differential pickup.
- Harmonic blocking and restraint settings.
A practical engineering workflow should begin with the transformer nameplate, single-line diagram, CT data and protection study. The relay settings should then be independently checked against the expected load and fault conditions.

6. Restricted earth fault protection – REF
Restricted earth fault protection is a sensitive protection method for detecting earth faults within a defined grounded-wye winding zone.
The SEL-387E provides REF protection by comparing the direction and magnitude of the winding residual current with the associated neutral current.
The basic principle is:
- During normal operation, the residual current and neutral current should balance according to the configured polarity and reference directions.
- During an external earth fault, the protection should remain stable.
- During an internal earth fault within the protected zone, the current relationship changes and the REF element can operate.
REF protection is particularly valuable where transformer differential protection alone may not provide the required sensitivity for low-level winding earth faults.
Correct CT polarity, CT ratio, neutral CT connection and grounding arrangement are critical. Engineers should verify the complete REF circuit before enabling the trip output.
7. Overcurrent protection – 50/51
The SEL-387E includes extensive overcurrent protection for the individual winding current inputs.
Available functions include:
- Instantaneous phase overcurrent.
- Time-overcurrent phase protection.
- Instantaneous ground overcurrent.
- Time-overcurrent ground protection.
- Negative-sequence overcurrent.
These elements can provide backup protection for transformer faults and protection for associated power-system conditions.
The relay also provides combined overcurrent elements using the sum of currents from Windings 1 and 2. This can be useful in ring-bus and breaker-and-a-half arrangements where two breaker CT sets are used.
Overcurrent settings should be coordinated with upstream and downstream protection devices, transformer damage limits and the available short-circuit current.
8. Overexcitation protection – ANSI 24
Transformer overexcitation occurs when the magnetic flux in the transformer core becomes excessive. This can happen when voltage increases or system frequency decreases.
The volts-per-hertz relationship is:
[
\text{V/Hz} \propto \frac{V}{f}
]
where:
- (V) is the applied voltage.
- (f) is the system frequency.
Excessive V/Hz can lead to core saturation, increased magnetizing current, overheating and possible insulation damage.
The SEL-387E provides volts-per-hertz protection with definite-time and curve-based options. Engineers can configure alarm and trip stages according to transformer manufacturer limits and the protection philosophy.
9. Voltage and frequency protection
The SEL-387E includes voltage inputs that support metering and voltage/frequency protection functions.
These include:
- ANSI 27 – undervoltage.
- ANSI 59 – overvoltage.
- ANSI 81U – underfrequency.
- ANSI 81O – overfrequency.
These functions can support transformer protection and wider substation automation schemes. Frequency elements may also be used in load-shedding and load-restoration applications.
The correct voltage transformer connection and relay voltage configuration must be verified before enabling these elements.
10. Monitoring, metering and event recording
Beyond protection, the SEL-387E provides several useful monitoring and recording functions.
Oscillographic event reports
Event reports capture current and voltage waveforms around protection events. Engineers can use them to investigate:
- Transformer internal faults.
- External faults.
- Transformer energization.
- Differential element operation.
- CT saturation.
- Unexpected relay trips.
Sequential Events Recorder
The SER records changes in relay status and logic signals. It is particularly useful for reconstructing the sequence of events during a trip or abnormal operating condition.
Through-fault monitoring
The relay records and accumulates through-fault duty. This information can support transformer maintenance and assessment of the stress caused by external faults.
Breaker and battery monitoring
Additional monitoring functions include circuit-breaker contact wear monitoring and station battery voltage monitoring.
These features can help maintenance teams identify developing problems and improve maintenance planning.
11. Communication and substation automation
The SEL-387E provides serial and Ethernet communication options, depending on the installed hardware.
Supported communication capabilities can include:
- SEL ASCII protocol.
- SEL binary protocol.
- SEL Distributed Port Switch communications.
- DNP3 on supported hardware revisions.
- IEC 61850 communication options.
The relay also provides a built-in read-only web interface for viewing selected information such as metering, settings, targets and event records.
For IEC 61850 applications, engineers should verify the exact relay hardware and firmware support, available communication interfaces and applicable documentation before designing the SAS architecture.
Do not assume that every SEL-387E hardware revision supports the same Ethernet protocols.
12. Configuration using acSELerator QuickSet
SEL acSELerator QuickSet is used to configure, manage and commission SEL protection devices.
A typical SEL-387E configuration workflow includes:
- Establish communication with the relay.
- Read and save the existing settings.
- Confirm the relay model and hardware revision.
- Configure transformer and CT information.
- Enable the required differential winding inputs.
- Calculate and verify differential taps.
- Configure differential slopes and pickup levels.
- Set harmonic blocking or restraint functions.
- Configure REF protection.
- Configure backup overcurrent and voltage/frequency elements.
- Develop SELogic control equations.
- Verify trip logic, alarms and output contacts.
- Save and document the final settings.
Always retain a backup of the original relay settings before making changes. The final configuration should be checked against the approved protection design and commissioning documents.
13. SEL-387E testing and commissioning
Testing is an essential part of deploying the SEL-387E. A relay that has been configured correctly must also be verified through secondary injection and functional testing.
13.1 Visual inspection and wiring checks
Before applying test currents and voltages:
- Verify relay model and hardware.
- Check auxiliary DC supply.
- Inspect CT and VT wiring.
- Verify CT polarity and terminal identification.
- Check trip and alarm circuits.
- Verify communication connections.
- Confirm relay settings and setting group.
13.2 Differential protection testing
Using a suitable relay test set, such as an OMICRON CMC, engineers can perform:
- Differential pickup tests.
- Differential slope characteristic tests.
- Restraint-current tests.
- Unrestrained differential pickup tests.
- External-fault stability tests.
- Internal-fault operating tests.
The test plan should account for the relay’s configured CT compensation and differential reference quantities.
13.3 Harmonic restraint and blocking tests
Inject test currents containing the required harmonic components and verify the expected relay response.
Test cases may include:
- Fundamental current only.
- Second-harmonic content.
- Fourth-harmonic content.
- Fifth-harmonic content.
- DC offset, where applicable.
The purpose is to verify both security during inrush or overexcitation conditions and dependable operation for internal faults.
13.4 REF protection testing
REF testing should verify:
- Neutral CT polarity.
- Winding residual-current polarity.
- Pickup level.
- Operating direction.
- Stability for external earth faults.
- Correct trip logic.
13.5 Overcurrent and voltage/frequency testing
Verify the configured phase, ground and negative-sequence overcurrent elements. Test the applicable voltage and frequency elements using the relay test set.
13.6 Trip and control circuit testing
Finally, verify the complete trip path, including relay output contacts, interposing relays, lockout relays and circuit-breaker trip coils where applicable.
Record the test results and compare them with the approved commissioning criteria.
14. SEL-387E vs SEL-787 vs SEL-487E
These three SEL relays are designed for transformer protection, but they have different capabilities and application characteristics.
| Feature | SEL-387E | SEL-787 | SEL-487E |
|---|---|---|---|
| Main application | Two-/three-winding transformer protection | Transformer protection | Advanced transformer protection |
| Current inputs | Three three-phase inputs | Model-dependent | Up to seven three-phase restraint inputs |
| Differential protection | Yes | Yes | Advanced multiwinding differential |
| REF | Yes | Model-dependent | Multiple independent REF elements |
| Voltage inputs | One three-phase voltage input | Model-dependent | Two three-phase voltage inputs |
| Overexcitation | Yes | Model-dependent | Yes |
| Monitoring | Through-fault, breaker and battery monitoring | Model-dependent | Advanced transformer monitoring |
| Advanced digital options | Hardware-dependent | Model-dependent | Includes specific TiDL and Sampled Values options on SEL-487E-5 |
The SEL-387E remains a useful choice for applications requiring transformer differential and voltage protection with monitoring and automation features.
The SEL-787 family provides dedicated transformer protection solutions, while the SEL-487E is intended for more demanding multiwinding and advanced transformer protection applications.
Always compare the exact model, hardware and firmware specifications before selecting a relay.
15. Advantages of the SEL-387E
Key advantages include:
- Protection for two- and three-winding transformers.
- Programmable single- or dual-slope differential protection.
- Harmonic blocking and restraint options.
- Sensitive REF protection.
- Extensive winding overcurrent protection.
- Volts-per-hertz protection.
- Voltage and frequency functions.
- Through-fault monitoring.
- Oscillographic event recording and SER.
- Flexible SELogic control equations.
- Communication and substation automation capabilities.
16. Frequently asked questions
Can the SEL-387E protect a three-winding transformer?
Yes. The relay provides three three-phase current inputs and supports differential protection for transformers with up to three windings.
Does the SEL-387E support REF protection?
Yes. It provides restricted earth fault protection for applicable grounded-wye and autotransformer-connected winding arrangements.
Does the SEL-387E support harmonic restraint?
Yes. It provides second- and fourth-harmonic blocking or restraint options, together with fifth-harmonic and DC-related security features.
Can the SEL-387E be configured using QuickSet?
Yes. SEL acSELerator QuickSet is used for configuration, commissioning and management.
Can the SEL-387E be tested using OMICRON CMC?
Yes. A suitable OMICRON CMC test set and test software can be used for secondary injection and functional testing. Test plans must reflect the actual relay settings and application.
Does the SEL-387E support IEC 61850?
IEC 61850 capability depends on the relay’s hardware and configuration. Check the exact device documentation before including it in an IEC 61850 substation automation design.
17. SEL-387E protection relay training by Elec-Engg
Understanding the SEL-387E requires more than knowing the ANSI protection functions. Protection engineers should understand how to calculate differential settings, configure CT compensation, apply REF protection, develop relay logic and perform practical commissioning tests.
At Elec-Engg, we provide practical training in power system protection, transformer differential protection, SEL protection relays, relay configuration and testing.
Training can be arranged online based on request, with practical engineering topics such as:
- Transformer differential protection principles.
- CT ratio and vector-group compensation.
- Differential slope and harmonic restraint settings.
- REF protection application and testing.
- SEL relay configuration using QuickSet.
- Protection logic and trip circuit verification.
- Secondary injection using OMICRON CMC.
For information about customized SEL relay training and other power system protection courses, contact Elec-Engg.
Website: https://elec-engg.com/
18. Conclusion
The SEL-387E is a versatile current differential and voltage relay for two- and three-winding transformer protection. Its combination of percentage differential protection, harmonic security, REF, overcurrent, voltage and frequency functions makes it suitable for a range of transformer and multi-terminal equipment applications.
For protection engineers, understanding the differential algorithm, CT compensation, REF settings and commissioning procedures is essential to applying the relay safely and effectively.