SEL-387L Relay: 87L Line Differential Protection, Applications & Testing

The SEL-387L Line Current Differential Relay from Schweitzer Engineering Laboratories (SEL) is designed to provide fast, sensitive, and secure protection for two-terminal transmission and subtransmission lines. It uses current differential protection (ANSI 87L), comparing current measurements from both ends of a protected line through a fiber-optic communications channel.

One of the most distinctive characteristics of the SEL-387L is its zero-settings protection philosophy. For a typical two-terminal application with matching CT ratios at both terminals, the relay can be installed, connected to the current transformers and communications channel, and placed into service after the required communication addresses and installation checks are completed.

The relay is particularly useful for utilities and industrial power systems seeking a straightforward alternative to older pilot-wire differential protection systems.

This guide explains the SEL-387L’s applications, protection functions, differential operating principle, communication interfaces, installation requirements, event reporting, and practical testing considerations.

SEL-387L Line Current Differential Relay: Complete Guide to 87L Protection, Applications, Communication, and Testing

Table Of Contents
  1. 1. What is the SEL-387L relay?
  2. 2. Main applications of the SEL-387L
  3. 3. SEL-387L protection functions and ANSI codes
  4. 4. How SEL-387L line differential protection works
  5. 5. Communication system and fiber-optic interfaces
  6. 6. SEL-387L in two-terminal and three-terminal applications
  7. 7. Breaker control and transfer-trip functions
  8. 8. Metering, event recording and disturbance analysis
  9. 9. SEL-387L settings and configuration
  10. 10. SEL-387L testing and commissioning
  11. 11. SEL-387L and acSELerator QuickSet
  12. 12. SEL-387L vs SEL-311L vs SEL-787L
  13. 13. Advantages of the SEL-387L
  14. 14. Important engineering considerations and limitations
  15. 15. Frequently asked questions about the SEL-387L
  16. 16. Practical SEL-387L training and protection engineering

1. What is the SEL-387L relay?

The SEL-387L is a dedicated line current differential protection relay. It is designed to compare the current entering and leaving a protected transmission line and identify internal faults.

Its protection philosophy is based on the current differential principle:

  • During normal operation, current entering the protected line should approximately equal current leaving it, after considering the current directions and reference conventions.
  • During an external fault, the current flowing into and out of the protected zone should remain balanced.
  • During an internal fault, the difference between the terminal currents increases, allowing the differential protection to operate.

The SEL-387L exchanges current information between the two line terminals over a dedicated fiber-optic communications channel.

Important: SEL-387L is a line differential relay, not the SEL-387 transformer differential relay. The two products have different applications and protection functions.

2. Main applications of the SEL-387L

2.1 Two-terminal transmission line protection

The primary application is protection of a transmission line connected between two substations.

A typical arrangement includes:

  • One SEL-387L at the sending-end substation.
  • One SEL-387L at the receiving-end substation.
  • Current transformers at both terminals.
  • Circuit breakers at both terminals.
  • A fiber-optic communications link between the relays.
  • DC auxiliary supply and trip circuits.

Both relays exchange current information and provide differential protection for the complete line section between their associated CT locations.

2.2 Subtransmission line protection

The SEL-387L can also be applied to subtransmission lines where a straightforward line differential scheme is required.

Its application is particularly attractive where the same CT ratios can be used at both ends and a suitable digital communications channel is available.

2.3 Underground cable protection

Current differential protection is also suitable for underground cable circuits.

For cable applications, engineers must pay attention to charging current and the possibility of current unbalance during external faults. SEL’s application guidance identifies the importance of selecting equal CT ratios and ensuring that line charging current remains within the specified limits for the sensitive unbalance elements.

2.4 Industrial power system interconnections

Industrial facilities often have a connection between a utility substation and an industrial-owned substation.

The SEL-387L can be applied to protect such interconnections. One particularly useful arrangement combines an SEL-387L at the industrial terminal with an SEL-311L at the utility terminal. The SEL-311L acts as the leader and makes the protection decisions using current information received from the SEL-387L.

This arrangement can simplify protection engineering where the industrial owner does not want to manage complicated line differential settings.

2.5 Replacement of older pilot-wire protection

The SEL-387L can be considered when replacing older electromechanical or pilot-wire differential protection systems.

Advantages include:

  • Digital current differential protection.
  • Fiber-optic communications.
  • Continuous communications monitoring.
  • Oscillographic event records.
  • Sequential event recording.
  • Reduced settings-engineering requirements.
  • Modern relay diagnostics.

The suitability of a retrofit depends on the existing CT circuits, trip circuits, communications infrastructure, auxiliary supply and required protection functions.

3. SEL-387L protection functions and ANSI codes

The main protection functions of the SEL-387L are based on phase and sequence-current differential measurements.

ANSI code / elementDescriptionApplication
87LAPhase A differentialInternal phase A faults
87LBPhase B differentialInternal phase B faults
87LCPhase C differentialInternal phase C faults
87LGGround differentialSensitive ground-fault detection
87L2Negative-sequence differentialUnbalanced fault detection
DFRDigital fault recordingOscillographic event records
SERSequential Events RecorderTime-tagged logic transitions
LGCLogic and controlPreconfigured control and logic functions
HMILocal operator interfaceRelay display and pushbuttons
MetMeteringLocal, remote and differential measurements

The exact functions and options should always be checked against the relay’s installed hardware and applicable instruction manual.

3.1 Three-phase differential protection – 87LA, 87LB and 87LC

The SEL-387L provides independent differential protection for the three phases.

The three phase differential elements are:

  • 87LA – Phase A differential protection.
  • 87LB – Phase B differential protection.
  • 87LC – Phase C differential protection.

These elements detect phase faults within the protected line section.

The relay uses local and remote current measurements to determine whether the current difference is consistent with an internal fault.

SEL’s data sheet describes fast operation for substantial phase differential current. The published application data indicates that the phase elements detect bolted phase faults producing more than 1.2 times nominal current difference, under the stated application conditions.

3.2 Negative-sequence differential protection – 87L2

Negative-sequence differential protection improves sensitivity to unbalanced faults.

Negative-sequence current is particularly useful when detecting:

  • Phase-to-phase faults.
  • Single-phase-to-ground faults.
  • Other unbalanced internal faults.

The 87L2 element contributes to the relay’s ability to detect high-resistance ground faults while maintaining security for external faults.

3.3 Ground differential protection – 87LG

The 87LG element provides sensitive ground-fault detection.

It is designed to detect internal ground faults that may produce relatively low fault current.

According to SEL’s data sheet, the sensitive unbalance elements operate for differential current exceeding 10% of nominal current, subject to the application conditions.

The manufacturer’s published example demonstrates detection of internal high-resistance ground faults up to approximately 133 ohms secondary for a 5 A nominal relay under the specified test conditions.

This is not a universal fault-resistance limit. Actual sensitivity depends on load current, CT ratios, line charging current, fault location and the complete application.

3.4 Alpha Plane restraint principle

One of the important characteristics of the SEL-387L is its Alpha Plane restraint principle.

Current differential relays must remain stable during external faults, even when current transformers experience unequal saturation or other measurement errors.

The Alpha Plane principle evaluates the relationship between the local and remote currents to distinguish between internal and external fault conditions.

This provides security against:

  • CT saturation during external faults.
  • Communication channel asymmetry.
  • Current measurement unbalance.
  • Other conditions that could otherwise produce an unwanted differential operating quantity.

This is especially important for transmission lines where external fault current can be very high.

4. How SEL-387L line differential protection works

The basic operating principle is straightforward.

Consider a transmission line connecting Substation A and Substation B.

At each terminal, a current transformer measures the line current. Each SEL-387L exchanges its current measurements with the remote relay.

The relay compares the current measurements using the defined current reference directions.

Normal operating condition

During normal load operation:

[
I_A \approx I_B
]

The differential current is approximately zero after accounting for current direction and the relay’s measurement conventions.

The relay remains stable.

External fault condition

Suppose a fault occurs outside the protected line zone.

The current entering and leaving the protected line should remain balanced.

Although the through-current can be high, the differential protection should remain stable.

Internal fault condition

When a fault occurs inside the protected line zone, the currents measured at the two terminals no longer balance.

The differential current increases and the relay identifies an internal fault.

The associated trip outputs operate according to the configured trip circuit and protection scheme.

Engineering note: The simplified equations above explain the principle only. Actual relay operation uses the manufacturer’s current processing, reference directions, restraint and security logic.

5. Communication system and fiber-optic interfaces

Reliable communication is essential for line current differential protection.

The SEL-387L uses one fiber-optic differential communications channel to exchange current information with the remote relay.

The available communication interfaces include:

InterfaceFiber type / standardPublished application
IEEE C37.94850 nm multimodeMultiplexer connection
1300 nmMultimode or single-modeDirect fiber
1550 nmSingle-modeDirect fiber

According to SEL’s data sheet:

  • 1300 nm fiber interfaces support direct fiber applications up to approximately 80 km.
  • 1550 nm single-mode fiber supports direct fiber connections up to approximately 120 km.
  • The IEEE C37.94 interface can connect directly to a compliant multiplexer.
  • The SEL-3094 interface converter can be used for connection to certain EIA-422 or G.703 multiplexer interfaces.

The exact reach depends on the selected interface, fiber characteristics, optical budget and installation conditions.

5.1 Communication channel monitoring

The SEL-387L continuously monitors its differential communications channel.

The relay provides information about:

  • Communication errors.
  • Channel dropouts.
  • Communication availability.
  • Channel delay.
  • Communication recovery events.

This information helps engineers assess whether the communication system is suitable for dependable differential protection.

A healthy communication channel is essential for the correct operation of the 87L scheme.

5.2 What happens when communication fails?

A communication problem can affect the availability of line differential protection.

Engineers should investigate:

  • Fiber-optic connections.
  • Transmit and receive polarity.
  • Communication addresses.
  • Multiplexer configuration.
  • Optical interface compatibility.
  • Channel delay and asymmetry.
  • Communication alarms and relay targets.

The protection design should also define the response to channel failure, including any independent backup protection and alarm requirements.

6. SEL-387L in two-terminal and three-terminal applications

6.1 Standard two-terminal application

<AsyncImage query=”SEL 387L line current differential relay two terminal transmission line protection schematic current transformers fiber optic communication” aspectRatio=”16:9″ width=”100%” />

For a standard two-terminal application, two SEL-387L relays are installed, one at each end of the protected line.

The typical installation procedure is:

  1. Install both relays.
  2. Connect the CT secondary circuits.
  3. Connect the DC auxiliary supplies.
  4. Connect the trip and alarm circuits.
  5. Connect the differential fiber-optic channel.
  6. Assign the communication transmit and receive addresses.
  7. Verify local and remote current measurements.
  8. Confirm communication channel status.
  9. Perform the required protection and trip-circuit tests.

For the typical application described by SEL, the relay does not require conventional differential characteristic settings.

However, zero-settings protection does not mean zero engineering. Correct CT selection, polarity, wiring, communication configuration and commissioning remain essential.

6.2 Three-terminal line application

<AsyncImage query=”SEL 387L SEL 311L three terminal line differential protection leader follower application diagram” aspectRatio=”16:9″ width=”100%” />

The SEL-387L can participate in a three-terminal line protection scheme using:

  • Two SEL-387L relays.
  • One SEL-311L relay.

In this arrangement, the SEL-311L operates as the leader relay.

The SEL-387L relays operate as follower units. They transmit their current measurements to the SEL-311L, which performs the differential protection decisions and sends transfer-trip signals.

This arrangement is particularly useful for lines with an additional terminal or industrial-owned substation.

It is important to understand that this is not simply three independent SEL-387L relays operating as a conventional three-terminal differential system. The SEL-311L performs the leader protection function.

6.3 Unequal CT ratios and more complex applications

For applications involving unequal CT ratios or more complicated terminal arrangements, SEL describes using an SEL-387L together with an SEL-311L.

The SEL-311L performs the required protection calculations and settings, while the SEL-387L provides remote current information.

This arrangement expands the application flexibility beyond the straightforward two-terminal, equal-CT-ratio installation.

7. Breaker control and transfer-trip functions

The SEL-387L includes preconfigured contact inputs and outputs for basic breaker control and remote signaling.

Depending on the installed configuration and wiring, the available functions include:

  • Trip input.
  • Close input.
  • Trip outputs.
  • Close outputs.
  • Remote transfer inputs T1 and T2.
  • Remote transfer outputs R1 and R2.
  • Breaker status input.
  • Alarm output.
  • Differential protection failure indication.

7.1 Remote transfer contacts

The relay can transfer selected input conditions to the remote terminal.

For example, an energized T1 input at one terminal can cause the corresponding R1 output at the remote relay to operate.

SEL specifies a transfer-contact response of less than 10 ms for the described arrangement.

These contacts can be used for remote signaling or suitable control and tripping applications, subject to the protection design and contact ratings.

7.2 Trip and close circuits

The relay provides preconfigured trip and close contacts.

The actual circuit design should consider:

  • Circuit breaker trip-coil current.
  • Close-coil current.
  • DC supply voltage.
  • Contact interrupting capacity.
  • Trip-circuit supervision requirements.
  • External interlocking.
  • Breaker auxiliary contacts.

Always verify the applicable output contact rating before connecting a breaker coil directly.

8. Metering, event recording and disturbance analysis

The SEL-387L provides useful monitoring and reporting functions for protection engineers.

8.1 Current metering

The relay provides local, remote and differential current measurements.

Available measurements include:

  • Phase A current.
  • Phase B current.
  • Phase C current.
  • Positive-sequence current.
  • Negative-sequence current.
  • Zero-sequence current.
  • System frequency.
  • DC battery voltage.

These measurements are valuable during commissioning and troubleshooting.

For example, comparing local and remote currents can help identify incorrect CT connections or polarity problems.

8.2 Oscillographic event recording

The SEL-387L provides 40 event reports, each containing oscillographic data.

The published data sheet describes:

  • 15 cycles of waveform information per event.
  • Four cycles of prefault data.
  • Eleven cycles of postfault data.
  • 16 samples per cycle.
  • Local, remote and differential current information.
  • Battery voltage and system frequency.
  • Relay logic information.

These records are useful for investigating internal faults, external faults, communication disturbances and unexpected relay operations.

8.3 Sequential Events Recorder

The relay includes an SER function that stores up to 512 time-tagged transitions of more than 30 key logic points.

The SER can help engineers reconstruct the sequence of events during a disturbance.

For example:

  1. A fault occurs.
  2. The differential element detects the fault.
  3. The relay asserts its trip logic.
  4. The trip output operates.
  5. The circuit breaker changes state.
  6. The relay records the corresponding status transitions.

This information is useful for post-fault analysis and commissioning verification.

9. SEL-387L settings and configuration

The SEL-387L is known for its zero-settings philosophy.

For the typical two-terminal application with equal CT ratios, the protection does not require conventional differential settings such as:

  • Differential pickup settings.
  • Differential slope settings.
  • CT ratio compensation settings.
  • Conventional restraint characteristic settings.

Instead, the relay’s protection principle and application design provide the differential protection.

However, engineers must still configure and verify the relay installation.

9.1 Communication address configuration

The transmit and receive addresses must be selected correctly at both terminals.

For example, one terminal may use transmit address 1 and receive address 2, while the opposite terminal uses transmit address 2 and receive address 1.

Incorrect addresses can prevent correct current exchange.

9.2 Relay and terminal identification

Relay identification and terminal labels can be entered to make the installation and maintenance process easier.

9.3 Verify current measurements

After energizing the relay, check:

  • Phase sequence.
  • CT polarity.
  • Local phase currents.
  • Remote phase currents.
  • Differential current.
  • System frequency.
  • Breaker status.

The differential current meter is especially useful for verifying the integrity of the CT and communication arrangement.

9.4 Configure control and output circuits

Confirm the required trip, close, alarm and transfer-contact functions.

Check the output contact ratings against the connected circuit requirements.

9.5 Communication monitoring

Review the communication status and available channel reports.

Investigate any communication errors, dropouts or abnormal delay indications before placing the protection scheme into service.

10. SEL-387L testing and commissioning

Testing a line differential relay requires more than injecting current into one relay.

The complete protection system includes both terminal relays, CT circuits, fiber communication, DC supplies, trip circuits and circuit breakers.

The following checks provide a practical commissioning framework.

10.1 Visual and hardware inspection

Before applying power, verify:

  • Correct relay model.
  • Correct hardware and communication option.
  • Correct mounting arrangement.
  • Auxiliary supply rating.
  • Terminal tightness.
  • CT wiring.
  • Fiber-optic connections.
  • Earthing and panel wiring.

10.2 Auxiliary supply test

Verify the DC auxiliary supply against the relay nameplate and applicable hardware specification.

Check relay startup and self-supervision indications.

10.3 CT circuit verification

Verify:

  • CT ratio.
  • CT polarity.
  • Phase identification.
  • CT secondary grounding.
  • Secondary wiring continuity.
  • Correct phase sequence.
  • Absence of unintended open circuits.

Never open an energized CT secondary circuit.

10.4 Communication channel test

Verify the communication link between both terminals.

Check:

  • Transmit and receive fiber connections.
  • Optical interface type.
  • Communication addresses.
  • Channel status.
  • Channel alarms.
  • Delay and availability reports.

10.5 Metering verification

Compare local and remote current measurements.

Under normal load conditions, the measured differential current should be consistent with the expected current balance and the characteristics of the protected circuit.

A significant unexpected differential current may indicate:

  • Incorrect CT polarity.
  • Incorrect phase connection.
  • Wrong CT ratio.
  • Communication problems.
  • Incorrect application wiring.

10.6 Differential protection testing

Perform the tests specified by the manufacturer and the approved commissioning procedure.

Typical test objectives include:

TestExpected result
Normal load conditionDifferential protection remains stable
External fault simulationNo unwanted differential trip
Internal phase fault simulationCorrect phase differential operation
Internal ground fault simulationCorrect ground differential response
Negative-sequence conditionCorrect response of the 87L2 element
Communication failureCorrect channel alarm and defined scheme response
Relay trip testCorrect output and trip-circuit operation
Event recording testCorrect event and SER information

For a line differential system, end-to-end testing is particularly important because the protection depends on measurements and communication from both terminals.

10.7 Trip circuit and breaker testing

Verify the complete trip path from relay output to the circuit breaker.

Test:

  • Trip output contacts.
  • Circuit breaker trip coil.
  • Breaker auxiliary contacts.
  • Trip indication.
  • Alarm indication.
  • Remote transfer signals where used.

Where the scheme includes automatic reclosing or breaker failure protection, these functions should be tested in the associated protection and control system. Do not assume they are built-in SEL-387L protection functions.

10.8 Event report analysis

After testing, retrieve the event reports and SER information.

Use the records to verify:

  • Correct phase identification.
  • Correct fault indication.
  • Differential current response.
  • Trip timing and sequence.
  • Communication behavior.
  • Breaker status changes.

Important: Always use the correct SEL-387L instruction manual and approved test procedure for the installed hardware and firmware. Do not apply generic settings or test assumptions from another SEL line differential relay.

11. SEL-387L and acSELerator QuickSet

The SEL-387L is supported by acSELerator QuickSet SEL-5030.

QuickSet can be used for engineering access, configuration tasks, monitoring and analysis of relay records.

Typical engineering activities include:

  • Connecting to the relay through a supported serial interface.
  • Retrieving relay information.
  • Accessing metering data.
  • Reviewing event records.
  • Analyzing oscillographic waveforms.
  • Reviewing relay status and communication information.
  • Managing applicable configuration and logic functions.

The SEL-387L’s zero-settings approach does not eliminate the need for engineering software. QuickSet remains useful for commissioning, diagnostics and maintenance.

12. SEL-387L vs SEL-311L vs SEL-787L

These three relays are associated with line current differential protection, but they are designed for different levels of application flexibility.

FeatureSEL-387LSEL-311LSEL-787L
Main applicationSimple line differentialAdvanced line differential and automationLine current differential
Typical two-terminal protectionYesYesYes
Three-terminal applicationWith SEL-311L leaderSupportedCheck specific application
Zero-settings philosophyKey featureConfigurable protectionConfigurable protection
Distance backupNoYes, on applicable configurationsNo conventional distance protection
CommunicationFiber-optic differential channelMultiple differential channel optionsFiber-optic differential channel
Advanced protection flexibilityLimited compared with advanced line relaysMore extensiveMore extensive than a basic zero-settings application
Typical useSimple two-terminal line protectionMore complex transmission line schemesModern line differential applications

The selection should be based on the required protection functions, line topology, CT arrangement, communications infrastructure, backup protection and future expansion requirements.

13. Advantages of the SEL-387L

The main advantages include:

  1. Zero-settings philosophy: Simplifies the typical two-terminal differential protection application.
  2. Fast differential protection: Provides high-speed phase differential protection.
  3. Sensitive ground-fault detection: Includes negative- and zero-sequence differential elements.
  4. Alpha Plane security: Improves stability during CT saturation and communication channel asymmetry.
  5. Fiber-optic communication: Supports direct fiber and compatible multiplexed communication arrangements.
  6. Communication monitoring: Provides channel quality and diagnostic information.
  7. Event recording: Supports post-fault analysis through oscillography and SER.
  8. Industrial interconnection applications: Can be combined with an SEL-311L for more complex applications.
  9. Retrofit potential: Can replace certain older pilot-wire differential protection systems.

14. Important engineering considerations and limitations

Before selecting the SEL-387L for a project, consider the following:

  • The standard simple application is intended for two-terminal lines with matching CT ratios.
  • The line charging current must be considered, particularly for long lines and cables.
  • A suitable fiber-optic or compatible multiplexed communications channel is required.
  • The relay is not a general-purpose distance protection relay.
  • The standard SEL-387L should not be assumed to provide every backup protection function required by a transmission line scheme.
  • Three-terminal applications require the appropriate SEL-311L leader arrangement described by SEL.
  • The actual communication reach depends on the selected interface and fiber installation.
  • The relay’s hardware, firmware, power supply and communication options must be verified before procurement or replacement.

The SEL-387L should be selected for applications that match its intended design rather than treating it as a direct substitute for every modern line protection relay.

15. Frequently asked questions about the SEL-387L

Q1. What is the main function of the SEL-387L relay?

The SEL-387L is designed primarily for line current differential protection (ANSI 87L) of two-terminal transmission and subtransmission lines.

Q2. Does the SEL-387L require differential protection settings?

For its typical two-terminal application with matching CT ratios, SEL describes a zero-settings protection philosophy. The relay still requires correct installation, communication addressing, wiring verification and commissioning.

Q3. What is the Alpha Plane principle?

The Alpha Plane restraint principle evaluates the relationship between local and remote currents to improve differential protection security, particularly during CT saturation and communication channel asymmetry.

Q4. Can the SEL-387L detect high-resistance ground faults?

Yes. The 87LG and 87L2 sensitive unbalance elements are designed to detect high-resistance ground faults under suitable application conditions.

Q5. What communication protocols or interfaces are supported?

The differential communication options include IEEE C37.94-compatible multimode fiber, 1300 nm fiber and 1550 nm single-mode fiber, depending on the selected hardware. The relay also supports serial communications, with optional DNP3 Level 2 capability.

Q6. Can the SEL-387L protect a three-terminal line?

Yes, as part of a scheme using two SEL-387L relays and one SEL-311L. In this arrangement, the SEL-311L operates as the leader and makes the protection decisions.

Q7. Does the SEL-387L provide distance protection?

No. Its principal protection function is line current differential protection. Separate backup protection should be provided where required by the system protection philosophy.

Q8. Which software is used for SEL-387L configuration and analysis?

The relay is supported by acSELerator QuickSet SEL-5030, which can be used for engineering access, monitoring and event analysis.

Q9. Is the SEL-387L suitable for replacing older pilot-wire differential relays?

It can be a suitable replacement in applications where the existing protection arrangement can be adapted to its CT, communication, power supply and trip-circuit requirements.

Q10. What is the most important commissioning test?

End-to-end verification is essential. Both relay terminals, CT circuits, communication channel, differential measurements and trip circuits must be tested as a complete protection system.

16. Practical SEL-387L training and protection engineering

Understanding the SEL-387L requires more than knowing the ANSI 87L function. Protection engineers should understand the complete line differential protection scheme, including CT polarity, current comparison, Alpha Plane security, communication channel monitoring, external fault stability and end-to-end testing.

At Elec-Engg, we provide practical training in power system protection, protection relay testing and commissioning, and substation automation.

Our training subjects include:

  • Line current differential protection.
  • Transformer differential protection.
  • CT and VT circuits.
  • Protection relay configuration and testing.
  • OMICRON CMC and Test Universe.
  • SEL, Siemens SIPROTEC and other protection relay platforms.
  • Protection coordination and commissioning practices.

Online training and customized company training can be arranged based on the requested subject and project requirements.

For information about available courses and customized training, visit https://elec-engg.com/ or contact Elec-Engg.