Siemens SIPROTEC 4 7UM Generator Protection Relays: 7UM61, 7UM621 & 7UM622

Table Of Contents
  1. 1. Introduction to Siemens SIPROTEC 4 7UM Relays
  2. 2. SIPROTEC 4 7UM61 and 7UM62 Models
  3. 3. Generator Differential Protection – ANSI 87G
  4. 4. Stator Earth-Fault Protection – ANSI 64G
  5. 5. Rotor Earth-Fault Protection – ANSI 64R
  6. 6. Loss of Excitation Protection – ANSI 40
  7. 7. Reverse Power Protection – ANSI 32R
  8. 8. Underexcitation and Overexcitation Protection
  9. 9. Negative-Sequence Protection – ANSI 46
  10. 10. Stator Overload Protection – ANSI 49
  11. 11. Overcurrent Protection – ANSI 50/51
  12. 12. Inadvertent Energization Protection – ANSI 50/27
  13. 13. Out-of-Step and Loss-of-Synchronism Protection – ANSI 78
  14. 14. Generator Protection Functions and ANSI Codes
  15. 15. DIGSI 4 Engineering for 7UM61 and 7UM62
  16. 16. Binary Inputs, Outputs and Generator Trip Logic
  17. 17. IEC 61850 and Substation Automation
  18. 18. Testing and Commissioning of SIPROTEC 4 7UM Relays
  19. 19. Common Generator Protection Problems and Troubleshooting
  20. 20. SIPROTEC 4 7UM Compared with Other Siemens Generator Protection Relays
  21. 21. Training on Siemens SIPROTEC 4 7UM Relays – Elec-Engg
  22. 22. Conclusion

This article covers the Siemens SIPROTEC 4 7UM61 and 7UM62 generator and machine protection relays, including generator differential protection, stator earth-fault protection, rotor earth-fault protection, loss of excitation, reverse power, negative-sequence protection, overexcitation, DIGSI 4 engineering, settings, testing and commissioning.

Siemens SIPROTEC 4 7UM Series – Complete Guide to Generator Protection Relays (7UM61 and 7UM62)

The SIPROTEC 4 7UM series is designed for generator and motor protection in industrial power plants, utility generating stations, hydroelectric plants, diesel generator installations, gas turbine plants and other power generation facilities. The 7UM62 extends the protection capabilities of the 7UM61 platform with additional functions for more demanding machine protection applications. cache.industry.siemens.com+2

1. Introduction to Siemens SIPROTEC 4 7UM Relays

Generator protection is different from ordinary feeder protection. A generator is a complex and valuable machine, and faults can damage its stator winding, rotor winding, magnetic circuit, bearings and associated equipment.

A comprehensive generator protection scheme must detect different types of electrical and mechanical problems, including:

  • Stator phase faults.
  • Stator earth faults.
  • Rotor earth faults.
  • Generator differential faults.
  • Loss of excitation.
  • Reverse power.
  • Unbalanced loading.
  • Overload and overheating.
  • Overvoltage and undervoltage.
  • Overfrequency and underfrequency.
  • Overexcitation.
  • Inadvertent energization.
  • Loss of synchronism.

The Siemens SIPROTEC 4 7UM series provides numerical protection functions for these applications. The available functions depend on the relay model, function package, hardware and configuration.

2. SIPROTEC 4 7UM61 and 7UM62 Models

2.1 SIPROTEC 4 7UM61

The 7UM61 is a multifunction generator and motor protection relay.

It can be used for:

  • Small and medium-sized synchronous generators.
  • Generator backup protection.
  • Synchronous motor protection.
  • Asynchronous motor protection.
  • Generator applications with busbar or unit connections.
  • Power plant protection and network decoupling applications.

The 7UM61 has different function packages. The basic, standard and full versions provide different combinations of protection functions.

Typical functions include stator earth-fault protection, overcurrent protection, overload protection, voltage and frequency protection, reverse power, overexcitation and underexcitation protection. More advanced packages add functions such as negative-sequence protection, breaker failure, forward power and inadvertent energization protection. automation-berlin.com+1

2.2 SIPROTEC 4 7UM62

The 7UM62 is a multifunction generator, motor and transformer protection relay designed for more extensive machine protection applications.

In addition to the functions available in the 7UM61 platform, the 7UM62 can provide additional protection functions, including:

  • Generator differential protection (ANSI 87G).
  • Transformer differential protection (ANSI 87T), in applicable configurations.
  • Motor differential protection (ANSI 87M).
  • Earth-current differential protection / REF (ANSI 87GN).
  • 100% stator earth-fault protection using 20 Hz injection.
  • Rotor earth-fault protection using an injection method.
  • Out-of-step protection.
  • Rate-of-frequency-change protection.
  • Additional motor protection functions.
  • Additional measuring and monitoring capabilities.

The 7UM62 is particularly suitable for more comprehensive generator protection schemes and can also be applied to large motors and selected transformer protection applications. cache.industry.siemens.com+2

2.3 7UM621 and 7UM622

The 7UM62 family includes the 7UM621 and 7UM622 variants.

These variants have different binary input and output capacities. The 7UM622 is useful in applications requiring more external signals and control connections, such as larger power plants.

The exact I/O configuration must be checked against the device order number and hardware documentation. www.slideshare.net+1

2.4 Model comparison

RelayMain applicationMain characteristics
7UM61Generator and motor protectionMultifunction protection with selectable function packages
7UM621Generator, motor and transformer protection7UM62 platform with a lower I/O configuration
7UM622Generator, motor and transformer protection7UM62 platform with a higher I/O configuration

The 7UM621 and 7UM622 should not be treated as different protection generations. Their function availability and I/O arrangements must be checked against the relevant Siemens documentation and ordered function package.

3. Generator Differential Protection – ANSI 87G

Generator differential protection is one of the most important functions available in the 7UM62.

It detects phase-to-phase and three-phase faults inside the protected generator stator zone.

The principle is based on comparing the current entering and leaving the protected winding.

For a simplified differential protection scheme:

\[ I_{\mathrm{diff}} = |I_1 + I_2| \]

Where:

  • \(I_1\) is the current entering the protected zone.
  • \(I_2\) is the current leaving the protected zone, with the appropriate reference direction.

Under normal operation and for external faults, the compensated current sum should remain close to zero.

For an internal fault, the differential current increases and the relay can issue a trip command.

The relay also uses a restraint or stabilizing quantity to maintain stability during external faults and CT errors.

Generator differential protection applications

  • Stator phase-to-phase faults.
  • Three-phase stator winding faults.
  • Internal faults between the generator terminal CTs and neutral CTs.
  • Generator winding faults within the defined differential zone.

Important engineering considerations

  • CT ratio selection.
  • CT polarity.
  • CT location.
  • CT accuracy and saturation performance.
  • Correct phase assignment.
  • Differential pickup and restraint settings.
  • Trip circuit and lockout relay configuration.

The 7UM62 documentation describes differential protection for generators, motors and transformers using the current differential principle.

4. Stator Earth-Fault Protection – ANSI 64G

Stator earth-fault protection detects insulation failures between the generator stator winding and earth.

A stator earth fault can occur because of:

  • Insulation ageing.
  • Moisture.
  • Thermal deterioration.
  • Mechanical damage.
  • Contamination.
  • Winding movement.
  • Electrical stress.

The grounding arrangement of the generator neutral determines the appropriate earth-fault protection method.

Common arrangements include:

  • High-resistance grounding.
  • Low-resistance grounding.
  • Solid grounding.
  • Distribution transformer grounding.
  • Neutral grounding resistor arrangements.

4.1 90% stator earth-fault protection

The 7UM61 provides stator earth-fault protection based on measured neutral displacement voltage and/or residual quantities, depending on the configuration.

A conventional neutral-voltage method can detect most stator winding earth faults, but its sensitivity may be limited for faults close to the generator neutral point.

This is why a 90% stator earth-fault protection scheme is often described as protecting approximately 90% of the winding, rather than the complete winding.

4.2 100% stator earth-fault protection using third harmonic

The 7UM61 includes a third-harmonic-based method in applicable function packages.

The principle uses the distribution of third-harmonic voltage along the stator winding.

Changes in the third-harmonic voltage measured at the generator terminals or neutral can indicate an earth fault close to the neutral point.

The method requires a suitable generator design and sufficient third-harmonic voltage. It must be engineered and tested for the actual machine.

4.3 100% stator earth-fault protection using 20 Hz injection

The 7UM62 supports a 100% stator earth-fault protection method using an external 20 Hz injection system in supported configurations.

This method can detect earth faults across the stator winding, including the region close to the neutral point.

The scheme requires compatible injection equipment and correct connection and configuration.

5. Rotor Earth-Fault Protection – ANSI 64R

Rotor earth-fault protection detects insulation failure between the generator rotor winding and earth.

A single rotor earth fault may not immediately produce a large fault current, depending on the excitation system and grounding arrangement. However, a second earth fault can create a short circuit across part of the rotor winding and cause severe damage.

Common rotor earth-fault protection methods

  • Injection of a DC measuring voltage.
  • Injection of a low-frequency square-wave voltage.
  • Insulation resistance measurement.
  • External rotor earth-fault monitoring equipment.

The 7UM62 supports rotor earth-fault protection using an injection method in applicable configurations. The manual also describes a sensitive rotor earth-fault protection method using a low-frequency square-wave voltage injection system.

The correct external measuring and injection equipment must be selected for the specific relay configuration. cache.industry.siemens.com+1

6. Loss of Excitation Protection – ANSI 40

Loss of excitation occurs when a synchronous generator loses its field current or excitation system.

Possible causes include:

  • Excitation system failure.
  • AVR malfunction.
  • Field circuit interruption.
  • Exciter failure.
  • Incorrect excitation control.
  • Rotor field winding problems.

When a generator loses excitation, it may start absorbing reactive power from the power system. This can cause instability and affect the voltage profile of the network.

The 7UM61 includes underexcitation or loss-of-field protection.

The protection commonly uses impedance measurement or related characteristics to detect operation in the underexcited region.

Typical effects of loss of excitation

  • Increased reactive power absorption.
  • Reduced generator terminal voltage.
  • Rotor and stator heating.
  • Loss of synchronism.
  • Power system voltage instability.

Engineering considerations

  • Generator capability curve.
  • Underexcitation limiter characteristics.
  • Generator operating region.
  • Impedance characteristic.
  • Time delays.
  • Coordination with excitation system protection.

The settings should be based on the generator manufacturer’s capability curve and the power system study. cache.industry.siemens.com+1

7. Reverse Power Protection – ANSI 32R

Reverse power protection detects the condition in which a generator starts absorbing active power from the network instead of supplying it.

This condition is especially important for prime movers such as:

  • Steam turbines.
  • Gas turbines.
  • Diesel engines.
  • Hydro turbines.

For example, if a turbine loses its mechanical input while the generator remains connected to the network, the generator may operate as a motor.

This can cause mechanical and thermal problems for the prime mover.

The 7UM61 provides reverse-power protection.

Reverse power protection settings

Typical engineering parameters include:

  • Reverse-power pickup.
  • Operating delay.
  • Generator rated active power.
  • Active power direction.
  • CT and VT ratios.
  • Power measurement polarity.

Correct active-power direction configuration is essential. Incorrect CT or VT polarity can cause the relay to interpret normal generator output as reverse power.

The 7UM61 manual includes a dedicated reverse-power protection function (ANSI 32R). cache.industry.siemens.com+1

8. Underexcitation and Overexcitation Protection

8.1 Underexcitation – ANSI 40

Underexcitation protection prevents the generator from operating beyond its permitted underexcited operating region.

It is important for:

  • Generator stability.
  • Reactive power control.
  • Stator end-region heating.
  • Coordination with the AVR.
  • Prevention of loss of synchronism.

8.2 Overexcitation – ANSI 24

Overexcitation protection monitors the voltage-to-frequency ratio:

\[ \frac{V}{f} \]

An increase in voltage or decrease in frequency can increase the magnetic flux in the generator and associated transformer.

Excessive flux can cause:

  • Magnetic core saturation.
  • Increased magnetizing current.
  • Excessive heating.
  • Insulation deterioration.

The 7UM61 includes overexcitation protection, and the 7UM62 also provides this function in its documented function range. automation-berlin.com+1

9. Negative-Sequence Protection – ANSI 46

Negative-sequence protection detects unbalanced three-phase currents.

Unbalanced loading can produce negative-sequence current, which induces double-frequency currents in the rotor.

These currents can cause significant rotor heating and damage.

Typical causes include:

  • Unbalanced loads.
  • Open phases.
  • Asymmetrical system faults.
  • Incorrect switching.
  • Unequal phase impedances.

The relay measures negative-sequence current and compares it with configured limits.

Generator manufacturers normally specify a negative-sequence withstand capability, often represented by an \(I_2^2t\) limit.

The protection settings should be coordinated with the generator manufacturer’s data.

The 7UM61 standard function package includes negative-sequence protection. automation-berlin.com+1

10. Stator Overload Protection – ANSI 49

Stator overload protection protects the generator against excessive thermal loading.

It monitors current and uses a thermal model to estimate heating.

Typical causes of generator overload include:

  • Excessive active power output.
  • Excessive reactive power output.
  • Cooling system problems.
  • High ambient temperature.
  • Incorrect generator loading.
  • Abnormal operating conditions.

The thermal model and alarm/trip thresholds must be configured using the generator manufacturer’s thermal limits.

11. Overcurrent Protection – ANSI 50/51

The 7UM61 and 7UM62 can provide overcurrent protection for generator backup protection and other supported applications.

Common functions include:

  • Definite-time overcurrent.
  • Inverse-time overcurrent.
  • Directional overcurrent in supported configurations.
  • Overcurrent with undervoltage supervision.
  • Earth-fault overcurrent.

Overcurrent protection may act as backup for generator differential protection and external network faults.

Settings should be coordinated with:

  • Generator rated current.
  • Generator short-circuit capability.
  • Transformer protection.
  • Feeder protection.
  • Network fault-clearing times.
  • Generator thermal limits.

12. Inadvertent Energization Protection – ANSI 50/27

Inadvertent energization occurs when a generator is energized while it is not in the expected operating condition, for example when it is stationary or not properly synchronized.

Possible causes include:

  • Incorrect circuit breaker operation.
  • Control circuit failure.
  • Switching errors.
  • Incorrect interlocking.
  • Unintended closing of the generator breaker.

This condition can produce severe electrical and mechanical stress.

The 7UM61 full function package and 7UM62 provide inadvertent energization protection in supported configurations. The function commonly uses current and voltage conditions to identify the abnormal energization state. automation-berlin.com+1

13. Out-of-Step and Loss-of-Synchronism Protection – ANSI 78

Out-of-step protection detects unstable generator operation when the generator loses synchronism with the power system.

Possible causes include:

  • Severe system faults.
  • Loss of transmission capacity.
  • Generator excitation problems.
  • Large disturbances.
  • Incorrect protection clearing times.

The 7UM62 includes out-of-step protection in its extended function range.

The protection scheme should be coordinated with generator stability studies and the system operator’s requirements. Electric Motor+1

14. Generator Protection Functions and ANSI Codes

The following table summarizes important protection functions available across the 7UM family. Availability depends on the model and function package.

ANSI codeFunctionApplication
87GGenerator differentialInternal stator phase faults
87TTransformer differentialTransformer protection in supported configurations
87MMotor differentialMotor differential protection
87GNEarth-current differential / REFSensitive earth-fault protection
64GStator earth faultStator winding earth faults
64RRotor earth faultRotor insulation faults
40Loss of excitationGenerator underexcitation
32RReverse powerPrime mover failure
32FForward power supervisionPower direction monitoring
46Negative sequenceUnbalanced current protection
49Thermal overloadGenerator thermal protection
50/51OvercurrentPhase fault backup
50BFBreaker failureFailure of generator circuit breaker
24OverexcitationExcessive V/Hz
27UndervoltageLow generator voltage
59OvervoltageHigh generator voltage
81FrequencyUnderfrequency and overfrequency
81RRate of frequency changeFrequency disturbance detection
78Out of stepLoss of synchronism
21Impedance protectionBackup impedance protection in supported configurations

This is a family-level overview, not a guarantee that every function is present in every 7UM device. Confirm the function package and device documentation before preparing a protection specification.

15. DIGSI 4 Engineering for 7UM61 and 7UM62

DIGSI 4 is used to configure SIPROTEC 4 protection relays.

Typical engineering activities include:

  1. Creating a new project.
  2. Adding the correct 7UM61 or 7UM62 relay.
  3. Selecting the appropriate device version.
  4. Configuring generator rated data.
  5. Entering CT and VT ratios.
  6. Configuring the active power direction.
  7. Enabling the required protection functions.
  8. Configuring differential protection, where available.
  9. Configuring stator and rotor earth-fault protection.
  10. Setting loss-of-excitation protection.
  11. Configuring reverse-power protection.
  12. Setting negative-sequence protection.
  13. Configuring overcurrent and overload protection.
  14. Assigning binary inputs and outputs.
  15. Configuring trip logic and alarms.
  16. Downloading settings to the relay.
  17. Retrieving measured values, event records and disturbance records.

The DIGSI project must match the actual relay type, firmware and ordered function package.

16. Binary Inputs, Outputs and Generator Trip Logic

Generator protection normally requires several external signals from the generator, turbine, excitation system and switchgear.

Typical binary inputs include:

  • Generator circuit breaker status.
  • Field breaker status.
  • AVR alarm.
  • Excitation system trip.
  • Turbine trip.
  • Emergency shutdown.
  • Buchholz alarm and trip, for unit transformer applications.
  • Cooling system alarm.
  • External lockout relay status.
  • Generator earth-fault system signals.

Typical binary outputs include:

  • Generator differential trip.
  • Stator earth-fault trip.
  • Rotor earth-fault alarm or trip, according to the scheme.
  • Reverse-power trip.
  • Loss-of-excitation trip.
  • Overcurrent trip.
  • Generator lockout relay operation.
  • Circuit breaker trip.
  • Field breaker trip.
  • General alarm.

The actual trip matrix must follow the generator protection philosophy and the manufacturer’s recommendations.

17. IEC 61850 and Substation Automation

SIPROTEC 4 7UM relays can be integrated into substation automation systems when the required communication hardware and protocol support are provided.

Engineering topics may include:

  • IEC 61850 communication.
  • Logical node configuration.
  • Data object mapping.
  • GOOSE communication, where supported.
  • Station bus integration.
  • Time synchronization.
  • SCADA indications and controls.
  • SCL engineering.
  • Alarm and event mapping.

Always verify the communication options and supported firmware for the exact 7UM device.

18. Testing and Commissioning of SIPROTEC 4 7UM Relays

Generator protection testing must be planned carefully because some functions may initiate trips to the generator breaker, field breaker or turbine shutdown system.

Use an appropriate relay test set, such as an OMICRON CMC, and follow the approved commissioning procedure.

18.1 Initial inspection

Check:

  • Relay model and order number.
  • Auxiliary DC supply.
  • CT wiring and polarity.
  • VT wiring and phase sequence.
  • Generator neutral connections.
  • Binary inputs and outputs.
  • Trip circuit wiring.
  • Communication connections.
  • Relay configuration and firmware.

18.2 CT and VT measurement tests

Verify:

  • Current scaling.
  • Voltage scaling.
  • Phase sequence.
  • CT polarity.
  • VT polarity.
  • Active and reactive power measurement.
  • Frequency measurement.
  • Power direction.

18.3 Generator differential protection tests

Where the 7UM62 differential function is used, test:

  • Differential pickup.
  • Restraint characteristic.
  • Stability during normal load conditions.
  • Stability during external faults.
  • Internal phase fault response.
  • Internal three-phase fault response.
  • Trip logic and output contacts.

18.4 Stator earth-fault tests

Test the applicable earth-fault protection method.

For voltage-based protection, verify the voltage inputs, measuring circuit and configured pickup and delay.

For 20 Hz injection protection, follow the manufacturer’s procedure and test the external injection equipment and measuring circuits.

18.5 Rotor earth-fault tests

For injection-based rotor earth-fault protection, verify:

  • Injection equipment.
  • Measuring circuit.
  • Alarm threshold.
  • Trip threshold, if configured.
  • External wiring and supervision.

18.6 Loss-of-excitation tests

Test the configured impedance characteristic and operating time.

Verify the relay response for operating conditions inside and outside the configured underexcitation characteristic.

18.7 Reverse-power tests

Inject the appropriate current and voltage quantities to simulate:

  • Normal forward generator power.
  • Reverse active power.
  • Pickup threshold.
  • Operating delay.
  • Correct trip output.

Pay particular attention to the configured active-power direction.

18.8 Additional protection tests

Where functions are enabled, test:

  • Negative-sequence protection.
  • Overload protection.
  • Overexcitation protection.
  • Overvoltage and undervoltage.
  • Frequency protection.
  • Breaker failure.
  • Inadvertent energization.
  • Out-of-step protection.

18.9 Final trip and functional tests

Verify the complete trip matrix, including generator breaker trip, field breaker trip, lockout relay and turbine trip signals where applicable.

After testing, restore all protection functions to their approved in-service state and confirm that no test blocks or temporary settings remain active.

19. Common Generator Protection Problems and Troubleshooting

ProblemPossible causeRecommended checks
Generator differential current during normal operationCT polarity or ratio errorCheck CT wiring, ratios and phase assignment
Stator earth-fault alarmInsulation problem or measuring circuit issueCheck neutral voltage, residual current and wiring
Rotor earth-fault alarmReduced rotor insulation resistanceCheck rotor circuit and injection system
Reverse-power trip during normal generationIncorrect power directionCheck CT/VT polarity and active power settings
Loss-of-excitation alarmExcitation problem or incorrect characteristicCheck excitation system and generator capability curve
Negative-sequence alarmUnbalanced currentsCheck phase currents and system conditions
Overexcitation alarmHigh V/HzCheck voltage, frequency and AVR operation
Generator overload tripExcessive loading or thermal model settingsCheck loading and thermal parameters
Incorrect frequency indicationVT or measurement configuration issueCheck voltage inputs and frequency measurement
Breaker failure operationBreaker did not clear the faultCheck breaker mechanism, auxiliary contacts and trip circuit

Use the event records, fault records and measured values to identify the cause before changing protection settings.

20. SIPROTEC 4 7UM Compared with Other Siemens Generator Protection Relays

RelayProduct familyMain application
7UM61SIPROTEC 4Multifunction generator and motor protection
7UM621SIPROTEC 4Generator, motor and transformer protection
7UM622SIPROTEC 4Generator, motor and transformer protection with different I/O capacity
7UM85SIPROTEC 5Generator and machine protection

The 7UM85 belongs to SIPROTEC 5 and is not a SIPROTEC 4 relay. When replacing an existing 7UM61 or 7UM62, compare protection functions, measuring inputs, binary I/O, communication interfaces and application requirements rather than selecting a replacement based only on the relay family name.

21. Training on Siemens SIPROTEC 4 7UM Relays – Elec-Engg

Elec-Engg provides practical training in generator protection, machine protection, transformer protection and Siemens SIPROTEC relays.

Training is designed for protection engineers, commissioning engineers, testing engineers, power plant maintenance engineers and electrical professionals.

Training topics can include:

  • Generator protection fundamentals.
  • SIPROTEC 4 7UM61 and 7UM62 hardware.
  • Generator differential protection – ANSI 87G.
  • Stator earth-fault protection.
  • 100% stator earth-fault protection.
  • Rotor earth-fault protection.
  • Loss of excitation – ANSI 40.
  • Reverse power – ANSI 32R.
  • Negative-sequence protection – ANSI 46.
  • Overexcitation – ANSI 24.
  • Overload and overcurrent protection.
  • DIGSI 4 configuration and parameterization.
  • Generator protection settings.
  • Binary inputs, outputs and trip logic.
  • OMICRON CMC testing and commissioning.
  • Fault record analysis and troubleshooting.

Available training methods:

  • Online training.
  • Structured self-paced training.
  • Customized in-house training for companies and utilities.
  • Face-to-face training.
  • Practical relay testing and commissioning training.

For more information about protection and substation automation courses, visit:

Elec-Engg – Practical Courses by Dr Saeed Roostaee / Elec-Engg

https://elec-engg.com

  • Siemens 7UM61 relay
  • Siemens 7UM62 relay
  • SIPROTEC 4 7UM621
  • SIPROTEC 4 7UM622
  • Generator protection relay
  • Generator differential protection
  • ANSI 87G protection
  • Stator earth-fault protection
  • 100% stator earth-fault protection
  • Rotor earth-fault protection
  • Loss of excitation protection
  • Reverse power protection
  • Negative-sequence protection
  • Generator protection settings
  • DIGSI 4 generator protection
  • OMICRON generator relay testing
  • Siemens generator protection training

22. Conclusion

The Siemens SIPROTEC 4 7UM series provides comprehensive protection solutions for generators, motors and selected transformer applications.

The 7UM61 offers a range of generator and motor protection functions, while the 7UM62 adds more advanced machine protection capabilities, including differential protection, REF and additional stator and rotor earth-fault protection methods.

Correct application requires detailed knowledge of the generator, CT and VT circuits, excitation system, neutral grounding arrangement, protection settings and trip philosophy.

DIGSI 4 engineering, secondary injection testing and complete commissioning checks are essential to ensure reliable generator protection.