Siemens SIPROTEC 4 7UT Transformer Protection Relays: 7UT612, 7UT613, 7UT633 & 7UT635

Table Of Contents
  1. 1. Introduction to SIPROTEC 4 7UT Transformer Protection
  2. 2. Applications of SIPROTEC 4 7UT Relays
  3. 3. SIPROTEC 4 7UT6 Models and Differences
  4. 4. Transformer Differential Protection – ANSI 87T
  5. 5. Transformer Vector Group Compensation
  6. 6. CT Ratio Matching and Current Compensation
  7. 7. Inrush Current and Harmonic Restraint
  8. 8. Restricted Earth-Fault Protection – ANSI 87N / REF
  9. 9. Additional Protection Functions
  10. 10. Transformer Overload Protection – ANSI 49
  11. 11. Overexcitation Protection – ANSI 24
  12. 12. Transformer Differential Protection Settings
  13. 13. DIGSI 4 Configuration for SIPROTEC 4 7UT
  14. 14. Binary Inputs, Outputs and Trip Logic
  15. 15. IEC 61850 and Substation Automation
  16. 16. Testing and Commissioning of SIPROTEC 4 7UT Relays
  17. 17. Common Problems and Troubleshooting
  18. 18. SIPROTEC 4 7UT Compared with Other Siemens Transformer Protection Relays
  19. 19. Training on Siemens SIPROTEC 4 7UT Relays – Elec-Engg
  20. 20. Conclusion

This article covers the Siemens SIPROTEC 4 7UT612, 7UT613 and 7UT63x transformer protection relays, including transformer differential protection (ANSI 87T), restricted earth-fault protection (REF), backup overcurrent protection, transformer inrush restraint, DIGSI 4 engineering, settings, testing and commissioning.

The article is prepared as copy-and-paste-ready content for Elec-Engg, with no images inside the article body. Suggested images are listed separately at the end.

Siemens SIPROTEC 4 7UT Series – Complete Guide to Transformer Differential Protection Relays

1. Introduction to SIPROTEC 4 7UT Transformer Protection

The Siemens SIPROTEC 4 7UT6 family is designed for differential protection of transformers, generators, motors and selected busbar arrangements. It combines transformer differential protection with additional protection and monitoring functions, depending on the relay model and ordered configuration.

The main protection function is transformer differential protection (ANSI 87T). It compares the currents entering and leaving the protected transformer. After compensating for transformer ratio, vector group and other relevant characteristics, the relay determines whether the measured current difference represents an internal fault.

The 7UT6 family includes several models with different numbers of current measuring inputs and protected terminals:

  • 7UT612: typically used for two-terminal protected objects.
  • 7UT613: supports up to three three-phase measuring sides.
  • 7UT633: supports up to three three-phase measuring sides and includes voltage inputs in the relevant hardware configuration.
  • 7UT635: supports up to five three-phase measuring sides.

The 7UT633 and 7UT635 have a graphic display, while the 7UT612 and 7UT613 use a four-line display. Always verify the exact hardware and order number before selecting a device. cache.industry.siemens.com+2

2. Applications of SIPROTEC 4 7UT Relays

SIPROTEC 4 7UT relays can be applied to several types of electrical equipment.

Power transformer protection

  • Two-winding power transformers.
  • Three-winding power transformers.
  • Autotransformers.
  • Transformers with grounded or ungrounded star points.
  • Transformer banks, subject to the applicable relay configuration.

Other differential protection applications

  • Generators.
  • Motors.
  • Shunt reactors.
  • Selected busbar protection arrangements.
  • Neutral earthing transformers and other protected objects where the application is supported.

The 7UT6 manual describes differential protection for transformers, generators, motors and busbars. The suitability of an individual model depends on its number of current inputs and the protected-object configuration. cache.industry.siemens.com+1

3. SIPROTEC 4 7UT6 Models and Differences

3.1 SIPROTEC 4 7UT612

The 7UT612 is a transformer differential protection relay designed for two-terminal protected objects.

Typical applications include:

  • Two-winding transformers.
  • Autotransformers in supported configurations.
  • Generators and motors.
  • Small busbar arrangements.
  • Differential protection with additional overcurrent and earth-fault protection functions.

The 7UT612 has fewer measuring locations than the larger 7UT6 models. Siemens documentation describes up to two three-phase sides for this model.

Depending on the ordered function package, additional functions can include:

  • Restricted earth-fault protection.
  • Phase overcurrent protection.
  • Earth-fault overcurrent protection.
  • Thermal overload protection.
  • Negative-sequence protection.
  • Breaker failure protection.
  • Trip-circuit supervision.

Not every function is included in every order configuration. cache.industry.siemens.com+1

3.2 SIPROTEC 4 7UT613

The 7UT613 is designed for protected objects with up to three three-phase measuring sides.

It is commonly associated with applications such as:

  • Three-winding transformers.
  • Transformers with multiple current measuring locations.
  • Generator and motor differential protection.
  • Differential protection schemes requiring additional measuring inputs.

The 7UT613 supports transformer differential protection, REF and a range of additional protection functions depending on its configuration.

Its additional measuring capability makes it suitable for more complex protected objects than the two-side 7UT612. The exact number of available inputs and functions must be checked against the device’s hardware configuration

3.3 SIPROTEC 4 7UT633

The 7UT633 is a larger 7UT6 device designed for more extensive protection and measuring requirements.

Typical characteristics include:

  • Up to three three-phase measuring sides.
  • Additional voltage measuring inputs in the relevant configuration.
  • Graphic display.
  • Transformer differential protection.
  • Restricted earth-fault protection.
  • Additional voltage, frequency and directional protection functions in supported configurations.

It can be used for transformer protection applications requiring more measuring and protection functionality than the basic 7UT612. ManualsLib+1

3.4 SIPROTEC 4 7UT635

The 7UT635 supports up to five three-phase measuring locations and is intended for more complex differential protection arrangements.

Potential applications include:

  • Protected objects with multiple measuring sides.
  • More complex transformer arrangements.
  • Selected busbar differential applications.
  • Protection schemes requiring additional current inputs.

The 7UT635 has a graphic display. Its maximum measuring capacity should not be confused with the number of transformer windings: the actual protected-object arrangement must be defined in the engineering configuration. ManualsLib+1

3.5 Model comparison

ModelThree-phase measuring sidesDisplayTypical application
7UT612Up to 2Four-line LCDTwo-terminal protected objects
7UT613Up to 3Four-line LCDThree-side protected objects
7UT633Up to 3GraphicMore extensive measuring and voltage functions
7UT635Up to 5GraphicComplex multi-side applications

These are family-level distinctions. Confirm the exact input count, sensitive current inputs, voltage inputs and function package using the full order number and Siemens documentation.

4. Transformer Differential Protection – ANSI 87T

Transformer differential protection is the main function of the 7UT6 family.

The principle is based on comparing the currents measured on the transformer sides. Under normal operating conditions, the currents should balance after accounting for:

  • Transformer ratio.
  • Vector group.
  • Phase displacement.
  • CT ratios.
  • Zero-sequence current behaviour.
  • Relay measurement and compensation settings.

If the compensated currents do not balance, the relay calculates a differential current.

A simplified differential current equation is:

\[ I_{\mathrm{diff}} = \left|I_1′ + I_2′ \right| \]

Where \(I_1’\) and \(I_2’\) are the currents referred to a common reference after the necessary compensation.

The relay also calculates a stabilizing or restraint current. A simplified representation is:

\[ I_{\mathrm{rest}} = |I_1’| + |I_2’| \]

The differential operating characteristic uses both quantities to distinguish internal faults from normal load and external faults. Page 409+1

Internal transformer faults

Examples include:

  • Phase-to-earth faults inside the transformer.
  • Phase-to-phase faults.
  • Three-phase winding faults.
  • Inter-turn faults that produce sufficient differential current.
  • Internal bushing faults within the CT-defined protection zone.
  • Faults in connections located between the CTs.

External faults

An external fault is outside the differential protection zone. Even when high current flows through the transformer, the relay should remain stable if the current measurements and CTs behave correctly.

This is why CT selection, CT saturation performance, correct wiring and differential restraint settings are essential.

5. Transformer Vector Group Compensation

One of the most important tasks when configuring transformer differential protection is vector group compensation.

The primary and secondary transformer currents can have different phase angles because of the transformer’s winding connection.

For example:

  • Dyn11
  • Dyn1
  • YNd1
  • YNd11
  • Yy0
  • Yd1
  • Yd11
  • Other transformer vector groups

The relay must compensate for the phase displacement before comparing the currents.

Example: Dyn11 transformer

A Dyn11 transformer has a phase displacement between its high-voltage and low-voltage sides. The relay must be configured for the correct vector group so that the measured currents are correctly aligned for differential comparison.

Incorrect vector group configuration can cause:

  • Differential current during normal load.
  • Incorrect phase comparison.
  • Unwanted differential operation.
  • Reduced protection sensitivity.
  • Incorrect commissioning test results.

The transformer nameplate, vector group and CT connection diagrams must be checked before setting the relay.

6. CT Ratio Matching and Current Compensation

CT ratios on different transformer sides are often different because the rated currents differ.

The relay must convert the measured secondary currents into comparable quantities.

For example, consider a transformer with:

  • HV rated voltage: 132 kV.
  • LV rated voltage: 33 kV.
  • Transformer rating: 40 MVA.

The approximate rated line currents are:

\[ I_{\mathrm{HV}} = \frac{40 \times 10^6} {\sqrt{3}\times132\times10^3} \approx 175\ \mathrm{A} \]

\[ I_{\mathrm{LV}} = \frac{40 \times 10^6} {\sqrt{3}\times33\times10^3} \approx 700\ \mathrm{A} \]

The rated currents are different, so the CT ratios must be selected appropriately and the relay configured to compensate for them.

For example, possible CT ratios might be:

  • HV CT: 200/1 A.
  • LV CT: 800/1 A.

These are illustrative values only. Actual CT selection must consider the transformer rating, maximum load, fault current, CT performance and protection design.

7. Inrush Current and Harmonic Restraint

Transformer magnetizing inrush current can be high when a transformer is energized.

This current may flow into the transformer from one side without an equivalent current flowing out from the other side. Therefore, it can appear as differential current even though there is no internal fault.

The 7UT6 differential protection includes harmonic restraint features to help distinguish transformer inrush from internal faults.

Second harmonic restraint

Transformer energization inrush current commonly contains a significant second-harmonic component.

The relay can use the second-harmonic content of the differential current to restrain operation.

Cross-blocking

Cross-blocking can be used so that the presence of an inrush condition in one phase influences the restraint behaviour of the other phases, according to the configured logic.

High-current differential stage

The 7UT613/63x documentation describes an additional high-current unrestrained differential stage for high-current internal faults. This can provide fast operation when the measured current exceeds a threshold that is not expected for an external through-fault. The exact availability and implementation depend on the model. cache.industry.siemens.com+2

8. Restricted Earth-Fault Protection – ANSI 87N / REF

Restricted earth-fault protection is a highly sensitive protection function for detecting earth faults within a defined zone of a transformer winding.

It is particularly valuable for detecting winding-to-earth faults close to the transformer neutral, where differential protection may have limited sensitivity.

The REF protection zone is defined by:

  • The three phase CTs.
  • The neutral CT.
  • The protected transformer winding and its earthing connection.

The relay compares the residual current from the phase CTs with the neutral current.

A simplified conceptual equation is:

\[ I_{\mathrm{REF}} = \left| I_A + I_B + I_C + I_N \right| \]

The current directions and polarity conventions must be applied correctly when implementing the actual scheme.

REF applications

  • Star-connected transformer windings with an accessible earthed neutral.
  • Autotransformer grounded windings.
  • Neutral earthing transformers.
  • Other supported protected objects with an appropriate neutral CT arrangement.

Low-impedance REF

Low-impedance REF protection uses current measurement and relay restraint or stability logic. The 7UT6 family supports low-impedance REF in applicable configurations.

High-impedance REF

The 7UT613/63x manual also describes high-impedance earth-fault protection arrangements using an external stabilizing resistor and voltage-limiting varistor, with the relay measuring the relevant current in the circuit.

High-impedance schemes require careful CT matching and stability calculations. cache.industry.siemens.com+2

9. Additional Protection Functions

Depending on the relay model and ordered function package, SIPROTEC 4 7UT devices can provide several additional functions.

ANSI codeProtection functionPurpose
87TTransformer differentialMain protection against internal transformer faults
87NRestricted earth faultSensitive earth-fault protection
50/51Phase overcurrentBackup phase fault protection
50N/51NResidual earth overcurrentEarth-fault backup
49Thermal overloadProtects against excessive thermal loading
46Negative-sequence protectionDetects current unbalance
50BFBreaker failureInitiates backup clearing if the breaker fails
74TCTrip-circuit supervisionMonitors the trip circuit
24Overexcitation / V/HzProtects against excessive magnetic flux
27/59Under/overvoltageVoltage protection in supported models
81Frequency protectionUnder/overfrequency in supported models
67/67NDirectional overcurrentDirectional backup protection in supported models

The availability of voltage, frequency and directional functions is model- and configuration-dependent. For example, the Siemens manual identifies several voltage-related functions specifically with the 7UT633 configuration. ManualsLib+1

10. Transformer Overload Protection – ANSI 49

Transformer overload protection monitors the thermal loading of the transformer.

Depending on the ordered configuration, the 7UT6 can provide thermal overload protection for a winding.

The thermal model considers current loading and the thermal characteristics defined by the relevant settings.

Engineering considerations include:

  • Transformer rated current.
  • Thermal time constant.
  • Alarm and trip thresholds.
  • Cooling arrangement.
  • Transformer temperature monitoring requirements.
  • Coordination with transformer monitoring equipment.

Some transformer monitoring features require additional hardware, such as an external temperature monitoring box. Check the specific order configuration before assuming that hot-spot monitoring is available. cache.industry.siemens.com+1

11. Overexcitation Protection – ANSI 24

Overexcitation occurs when the magnetic flux in a transformer core becomes excessive.

A common indicator is the voltage-to-frequency ratio:

\[ \frac{V}{f} \]

If voltage increases or frequency decreases, the magnetic flux may rise above the permitted level.

Overexcitation can cause:

  • Core saturation.
  • Increased magnetizing current.
  • Excessive heating.
  • Insulation deterioration.
  • Unwanted operation of differential protection if severe.

Voltage-related protection functions, including V/Hz protection, are not universal across all 7UT6 models. Verify the availability of the function in the exact relay configuration. ManualsLib+1

12. Transformer Differential Protection Settings

Correct settings are essential for dependable transformer protection.

The following topics should be considered during the setting study.

12.1 Transformer rated power

Enter the transformer rated power according to the nameplate and the project protection philosophy.

For multi-winding transformers, define the rated data for each relevant winding.

12.2 Rated voltage

Configure the rated voltage of each transformer winding.

12.3 CT ratios

Enter the primary and secondary CT ratings for each measuring side.

12.4 Vector group

Select the correct transformer vector group and confirm the phase displacement.

12.5 Differential pickup

The differential pickup determines the minimum operating current.

It must be selected considering:

  • Transformer magnetizing current.
  • CT errors.
  • Tap changer operating range.
  • Measurement errors.
  • Expected internal fault current.
  • The manufacturer’s recommended setting procedure.

12.6 Differential restraint characteristic

The restraint characteristic improves stability during external faults and CT saturation.

Check the relay manual for the available characteristic and setting ranges. Do not copy slope or pickup values from another transformer without a calculation.

12.7 Harmonic restraint

Configure the harmonic restraint parameters according to the transformer application and the relay manual.

Relevant settings may include:

  • Second-harmonic restraint threshold.
  • Additional harmonic restraint.
  • Cross-blocking.
  • Restraint duration.

12.8 REF settings

For REF protection, verify:

  • Correct phase CT assignment.
  • Correct neutral CT polarity.
  • Protected winding selection.
  • REF pickup.
  • Stability requirements.
  • Low-impedance or high-impedance arrangement.
  • Correct trip output assignment.

The Siemens manual notes that REF is delivered switched off in the documented configuration and should not be enabled until the protected side and CT polarity have been correctly configured. ManualsLib

13. DIGSI 4 Configuration for SIPROTEC 4 7UT

DIGSI 4 is used to configure and manage SIPROTEC 4 protection relays.

Typical engineering steps include:

  1. Create a new DIGSI 4 project.
  2. Add the correct 7UT6 relay type.
  3. Confirm the complete device order number.
  4. Configure the protected object.
  5. Enter transformer rated data.
  6. Configure CT ratios.
  7. Set the transformer vector group.
  8. Configure differential protection.
  9. Configure harmonic restraint.
  10. Configure REF protection, where available.
  11. Configure overcurrent and other backup functions.
  12. Assign binary inputs and outputs.
  13. Configure LEDs and annunciations.
  14. Prepare trip logic.
  15. Download the configuration to the relay.
  16. Retrieve measured values, events and fault records.

The configuration must match the actual relay hardware and firmware. Different 7UT6 models have different measuring input capacities and function packages.

14. Binary Inputs, Outputs and Trip Logic

Binary inputs and outputs connect the protection relay to the transformer control and protection circuits.

Typical binary inputs include:

  • Circuit breaker status.
  • Transformer Buchholz relay alarm.
  • Buchholz trip.
  • Pressure relief device trip.
  • Winding temperature alarm.
  • Oil temperature alarm.
  • External trip.
  • Lockout relay status.
  • Transformer cooling system status.
  • External blocking signals.

Typical binary outputs include:

  • Transformer differential trip.
  • REF trip.
  • Backup overcurrent trip.
  • Alarm output.
  • Breaker failure initiation.
  • Lockout relay operation.
  • General protection operation.

The exact input/output allocation depends on the hardware and project design.

15. IEC 61850 and Substation Automation

SIPROTEC 4 relays can be integrated into substation automation systems when the appropriate communication interface and protocol support are available.

Engineering topics may include:

  • IEC 61850 communication.
  • Logical node configuration.
  • Data object mapping.
  • GOOSE communication, where supported.
  • Station bus integration.
  • Time synchronization.
  • SCADA indication and control.
  • SCL engineering.
  • Alarm and event mapping.

Always confirm the exact IEC 61850 support, edition and firmware for the individual relay. Do not assume all 7UT6 variants have identical communication options.

16. Testing and Commissioning of SIPROTEC 4 7UT Relays

Transformer differential protection commissioning must verify the complete protection scheme, including CT circuits, relay settings, trip logic and associated circuit breakers.

A suitable relay test system, such as an OMICRON CMC, can be used for secondary injection and functional testing.

16.1 Visual inspection

Check:

  • Relay model and order number.
  • Auxiliary DC supply.
  • CT wiring and polarity.
  • Neutral CT wiring.
  • VT wiring, if applicable.
  • Binary input and output wiring.
  • Earthing and shielding.
  • Relay configuration and firmware.

16.2 CT circuit tests

Verify:

  • CT ratio.
  • CT polarity.
  • Phase identification.
  • Secondary continuity.
  • Correct neutral CT connection.
  • Correct grounding arrangement.
  • CT secondary circuit integrity.

16.3 Differential protection tests

Typical tests include:

  • Differential pickup.
  • Differential operating characteristic.
  • Stability under simulated load.
  • Stability during external faults.
  • Internal phase-to-earth fault.
  • Internal phase-to-phase fault.
  • Internal three-phase fault.
  • High-current differential stage, where available.

16.4 Transformer inrush restraint tests

The Siemens commissioning documentation discusses checking inrush restraint by recording differential currents and harmonic content during transformer energization.

The test procedure must be planned carefully. The trip circuit should be isolated or the differential function placed in the prescribed test/blocking mode to avoid an unintended transformer trip. Restore the protection to service and independently verify its final enabled state after testing. ManualsLib

16.5 REF protection tests

Test the REF scheme by injecting current into the appropriate phase and neutral CT circuits.

Verify:

  • Correct current polarity.
  • Correct protected zone.
  • Pickup sensitivity.
  • Stability for external earth faults.
  • Correct trip output.
  • Correct alarm and event indications.

16.6 Backup protection tests

Where included, test:

  • Phase overcurrent.
  • Earth-fault overcurrent.
  • Thermal overload.
  • Negative-sequence protection.
  • Breaker failure.
  • Trip-circuit supervision.
  • Voltage and frequency functions, where available.

16.7 Trip circuit and breaker tests

Verify the complete trip path from the relay to the circuit breaker, including:

  • Trip output contacts.
  • Interposing relays.
  • Lockout relay.
  • Breaker trip coil.
  • Breaker auxiliary contacts.
  • Breaker failure initiation.
  • Trip-circuit supervision.

17. Common Problems and Troubleshooting

ProblemPossible causeRecommended checks
Differential current during normal loadIncorrect CT polarity or ratioCheck CT wiring, polarity and scaling
Differential trip during transformer energizationInrush restraint not correctly configuredReview harmonic content and restraint settings
Differential trip after transformer tap changeIncorrect compensation or setting rangeVerify transformer data and tap changer range
REF operates during an external earth faultCT polarity or stability problemCheck phase and neutral CT circuits
REF does not operate for an internal earth faultIncorrect protected side or REF settingsVerify zone, CT assignment and pickup
Incorrect phase comparisonWrong vector groupCheck transformer nameplate and DIGSI settings
Transformer overload alarmExcessive loading or incorrect thermal dataReview loading and thermal settings
Communication alarmInterface or network issueCheck communication hardware and configuration
Relay does not tripOutput assignment or trip circuit issueCheck logic, output contacts and wiring

Always investigate relay event records, measured values, fault records and the approved protection design before changing settings.

18. SIPROTEC 4 7UT Compared with Other Siemens Transformer Protection Relays

RelayProduct familyMain application
7UT612SIPROTEC 4Transformer and other two-side differential protection
7UT613SIPROTEC 4Differential protection with up to three three-phase measuring sides
7UT633SIPROTEC 4Differential protection with additional voltage measuring capability
7UT635SIPROTEC 4Differential protection with up to five three-phase measuring locations
7UT85SIPROTEC 5Transformer differential protection
7UT86SIPROTEC 5Transformer differential protection
7UT87SIPROTEC 5Transformer differential protection

The SIPROTEC 5 7UT8 family is a different product generation. It should not be confused with the SIPROTEC 4 7UT6 devices when preparing replacement specifications or engineering projects.

19. Training on Siemens SIPROTEC 4 7UT Relays – Elec-Engg

Elec-Engg provides practical training in transformer protection, differential protection, REF protection and Siemens SIPROTEC relays.

Our training is intended for protection engineers, commissioning engineers, testing engineers, maintenance engineers and substation professionals.

Training topics can include:

  • Transformer protection fundamentals.
  • Transformer differential protection – ANSI 87T.
  • Restricted earth-fault protection – ANSI 87N.
  • Transformer vector group compensation.
  • CT ratio and polarity.
  • Differential pickup and restraint settings.
  • Inrush current and harmonic restraint.
  • Transformer backup protection.
  • DIGSI 4 configuration and parameterization.
  • Binary inputs, outputs and trip logic.
  • IEC 61850 integration, where supported.
  • OMICRON CMC testing.
  • Transformer differential and REF commissioning.
  • Fault record analysis and troubleshooting.

Training delivery methods:

  • Online training.
  • Structured self-paced training.
  • Customized in-house training for companies and utilities.
  • Face-to-face training.
  • Practical relay testing and commissioning training.

For more information about our protection and substation automation courses, visit:

Elec-Engg – Practical Courses by Dr Saeed Roostaee / Elec-Engg

https://elec-engg.com

  • Siemens 7UT612 relay
  • Siemens 7UT613 relay
  • SIPROTEC 4 7UT633
  • SIPROTEC 4 7UT635
  • Transformer differential protection
  • ANSI 87T protection
  • Restricted earth fault protection
  • ANSI 87N REF
  • Transformer protection relay settings
  • Transformer vector group compensation
  • Transformer inrush current restraint
  • DIGSI 4 transformer protection
  • OMICRON transformer differential testing
  • Siemens transformer protection training
  • SIPROTEC 4 commissioning

20. Conclusion

The Siemens SIPROTEC 4 7UT6 family provides flexible differential protection solutions for transformers and other electrical equipment. Its main functions include transformer differential protection, REF, overcurrent backup, thermal overload and additional protection functions depending on the model and ordered configuration.

Correct application requires careful engineering of transformer data, CT ratios, CT polarity, vector group compensation, differential restraint and REF circuits.

DIGSI 4 configuration, secondary injection, end-to-end functional checks where required, and complete commissioning records are essential to ensure dependable transformer protection.