- 1. Introduction
- 2. What Is a Bay Controller?
- 3. SIPROTEC 6MD85 vs 6MD86 – Main Differences
- 4. SIPROTEC 6MD85 – Bay Controller for Distribution and High-Voltage Applications
- 5. SIPROTEC 6MD86 – Bay Controller for Transmission Applications
- 6. Bay Control Functions
- 7. Switchgear Interlocking
- 8. Synchrocheck – Function 25
- 9. Automatic Reclosing – Function 79
- 10. Circuit-Breaker Failure Protection – Function 50BF
- 11. Point-on-Wave Switching
- 12. Protection Functions
- 13. Measurement and Monitoring
- 14. Fault Recording and Event Analysis
- 15. IEC 61850 Communication
- 16. Other Communication Protocols
- 17. DIGSI 5 Engineering for 6MD85 and 6MD86
- 18. Practical Example – Circuit-Breaker Closing Logic
- 19. Testing and Commissioning
- 20. Common Problems and Troubleshooting
- 21. Cybersecurity and Network Reliability
- 22. 6MD85 and 6MD86 in Substation Automation Systems
- 23. SIPROTEC 6MD85 and 6MD86 vs SIPROTEC 4 Bay Controllers
- 24. Important Engineering Considerations
- 25. Training on Siemens SIPROTEC 5 Bay Controllers
- 26. Frequently Asked Questions
- What is the Siemens SIPROTEC 6MD85?
- What is the Siemens SIPROTEC 6MD86?
- What is the main difference between 6MD85 and 6MD86?
- Which software is used to configure 6MD85 and 6MD86?
- Do 6MD85 and 6MD86 support IEC 61850?
- Can the 6MD85 and 6MD86 control circuit breakers and disconnectors?
- Does the 6MD86 support automatic reclosing?
- Does the 6MD86 support Point-on-Wave switching?
- Can a 6MD85 or 6MD86 replace a dedicated protection relay?
- Is DIGSI 4 used for 6MD85 and 6MD86?
- 27. Conclusion
Siemens SIPROTEC 5 6MD85 and 6MD86 Bay Controllers – Complete Guide to Bay Control, Interlocking and IEC 61850
1. Introduction
The Siemens SIPROTEC 5 6MD85 and 6MD86 are modular bay controller units (BCUs) designed for control, automation, monitoring and protection applications in electrical substations.
They are used in medium-voltage, high-voltage and extra-high-voltage switchgear. As members of the SIPROTEC 5 family, both devices combine bay control capabilities with configurable protection functions, communication interfaces, programmable logic and flexible input/output arrangements.
A bay controller provides the interface between the substation operator, the station automation system and the primary equipment. It receives equipment status signals, processes control commands, applies interlocking conditions and operates circuit breakers, disconnectors and earthing switches.
The 6MD85 and 6MD86 are engineered using DIGSI 5 and can be integrated into modern substation automation systems through IEC 61850 and other supported communication protocols.
2. What Is a Bay Controller?
A bay controller is an intelligent electronic device responsible for controlling and monitoring the primary equipment associated with an individual substation bay.
A typical transmission or distribution bay may include:
- Circuit breaker
- Busbar disconnectors
- Line disconnector
- Earthing switch
- Current transformers (CTs)
- Voltage transformers (VTs)
- Protection relays
- Local and remote control interfaces
- Auxiliary relays and indication circuits
The bay controller collects equipment status information through binary inputs and, where applicable, measurements through current and voltage inputs.
It processes control commands from the local HMI, remote control centre or station automation system. Before executing a switching command, it checks the relevant operating conditions and interlocking logic.
For example, a circuit-breaker closing command may require:
- The circuit breaker to be in a suitable position.
- The relevant disconnector positions to be correct.
- The earthing switch to be open.
- The interlocking conditions to be satisfied.
- The synchronism-check condition to be fulfilled, where required.
- No active blocking condition to prevent operation.
The exact control and interlocking logic depends on the substation design and the application configuration.
3. SIPROTEC 6MD85 vs 6MD86 – Main Differences
Both devices belong to the SIPROTEC 5 platform, but Siemens positions them for different application requirements.
| Feature | SIPROTEC 6MD85 | SIPROTEC 6MD86 |
|---|---|---|
| Main application | Distribution and transmission systems | Transmission systems |
| Device type | Modular bay controller | Modular bay controller |
| Protection functions | Configurable | Configurable |
| Current and voltage inputs | Standard variants with 4 CT and 4 VT inputs | Standard variants with 4 or 8 CT and VT inputs |
| Standard hardware variants | 5 | 7 |
| Binary inputs | 11 to 75 | 11 to 75 |
| Binary outputs | 9 to 41 | 9 to 41 |
| Synchrocheck | Optional, depending on configuration | Available |
| Automatic reclosing | Not a standard distinguishing feature; check configuration | Optional |
| Circuit-breaker failure protection | Not a standard distinguishing feature; check configuration | Optional |
| Point-on-Wave switching | Not a standard distinguishing feature | Supported, depending on configuration |
| Hardware expansion | Supported | Supported |
| Engineering software | DIGSI 5 | DIGSI 5 |
The 6MD85 is suitable for many distribution and high-voltage bay control applications. The 6MD86 is intended for more demanding transmission applications and provides additional functionality options, including point-on-wave switching and extended switching-related functions.
The number of available functions depends on the ordered device variant, firmware, functional scope and project configuration. Always check the Siemens device configurator and technical documentation before finalizing a project specification.
Sources: Siemens SIPROTEC 6MD85 and 6MD86 product information and SIPROTEC 5 catalog.
4. SIPROTEC 6MD85 – Bay Controller for Distribution and High-Voltage Applications
The SIPROTEC 6MD85 is a general-purpose bay controller designed for distribution and high-voltage applications.
It combines bay control, automation, monitoring and configurable protection functions in one modular device.
Main characteristics
- Integrated bay control and switchgear operation
- Flexible binary input and output configuration
- Four current and four voltage measurement inputs in the standard variants described by Siemens
- Modular hardware expansion
- Configurable protection functions
- Synchrocheck functionality, depending on configuration
- Switchgear interlocking
- Programmable logic using CFC
- IEC 61850 communication
- Fault recording and measurement functions
- Optional PMU functionality
Typical applications
The 6MD85 can be applied in:
- Medium-voltage feeder bays
- Transformer bays
- Incoming and outgoing feeder panels
- Bus coupler and bus section bays
- High-voltage line bays
- Distribution substations
- Industrial power distribution systems
The device can also combine selected protection functions with bay control, reducing the need for separate equipment in applications where the design permits this arrangement.
5. SIPROTEC 6MD86 – Bay Controller for Transmission Applications
The SIPROTEC 6MD86 is designed for more demanding control and automation applications, particularly in transmission systems.
It provides modular bay control with extensive configurable functions from the SIPROTEC 5 function library.
Main characteristics
- Integrated bay control and automation
- Flexible hardware and I/O expansion
- Standard variants with four or eight current and voltage measurement inputs
- Switchgear interlocking
- Synchrocheck
- Automatic reclosing, depending on configuration
- Circuit-breaker failure protection, depending on configuration
- Point-on-Wave switching
- Phase-selective breaker control capabilities
- PMU functionality
- Fault recording
- CFC-based automation
- IEC 61850 communication
Typical applications
- 110 kV, 220 kV and 400 kV transmission substations
- Transmission line bays
- Transformer bays
- Bus coupler and bus section bays
- Complex switchgear arrangements
- Applications requiring advanced switching sequences
- Substations with advanced automation requirements
The 6MD86 is particularly useful when the project requires bay control, protection functions, advanced switching logic and automation within a single modular IED.
6. Bay Control Functions
The primary purpose of a 6MD85 or 6MD86 is to provide safe and reliable control of substation switching equipment.
6.1 Circuit-Breaker Control
The bay controller can receive circuit-breaker commands from different control locations.
Typical commands include:
- Circuit breaker ON
- Circuit breaker OFF
- Local control
- Remote control
- Operation through the station HMI
- Operation through the control centre
The device receives breaker position indications through binary inputs and processes them to determine the actual equipment status.
A typical breaker position arrangement uses two auxiliary contacts:
- Circuit breaker open
- Circuit breaker closed
These signals can be configured as a double-point indication to identify the breaker position and detect inconsistent or intermediate states.
6.2 Disconnector Control
Disconnectors are operated to establish the required electrical isolation and switchgear configuration.
The bay controller can process:
- Disconnector open command
- Disconnector close command
- Disconnector position feedback
- Disconnector interlocking
- Operation blocking conditions
The control logic must ensure that the disconnector is not operated under prohibited electrical conditions.
6.3 Earthing-Switch Control
Earthing switches are important for personnel and equipment safety during maintenance.
The bay controller can monitor and control earthing switches according to the approved switching philosophy.
Typical interlocking requirements include preventing the closing of an earthing switch while the associated circuit is energized and preventing circuit energization while an earthing switch remains closed.
The actual conditions must be designed according to the switchgear arrangement and operational safety rules.
6.4 Local and Remote Control
A bay controller normally supports several control levels.
Local control
The operator controls the bay from the local device interface or associated local control panel.
Station control
The operator uses the substation HMI or station-level automation system.
Remote control
The control centre sends commands through the communication system.
The local/remote selection logic determines which control authority is permitted to operate the equipment.
The control hierarchy and command authority must be clearly defined during engineering.
7. Switchgear Interlocking
Interlocking is one of the most important functions of a bay controller.
Its purpose is to prevent unsafe or incorrect switching operations.
Interlocking conditions are normally developed from the primary substation topology, equipment positions and operational rules.
7.1 Circuit-Breaker Interlocking
Typical conditions may include:
- Correct disconnector position
- Correct earthing-switch position
- No active blocking signal
- Equipment available for operation
- No maintenance or test blocking condition
7.2 Disconnector Interlocking
A disconnector should only operate when the associated circuit-breaker and switchgear conditions permit the operation.
For example, a disconnector may be blocked from operation when the associated circuit breaker is closed.
The exact rules depend on the busbar arrangement and the approved switching philosophy.
7.3 Earthing-Switch Interlocking
Earthing-switch interlocking is especially important because incorrect operation can result in severe equipment damage and personnel hazards.
Typical conditions include:
- The associated circuit must be isolated.
- The required disconnectors must be open.
- The circuit breaker must be open.
- Voltage-related blocking conditions must be satisfied where applicable.
7.4 Interlocking Between Bays
In complex substations, interlocking conditions may involve equipment in different bays.
For example, a busbar disconnector operation may depend on the status of another bay or a bus coupler.
Such interlocking can be implemented through:
- Hardwired binary signals
- IEC 61850 GOOSE communication
- Station-level automation logic
- A combination of local and station-level logic
When GOOSE is used, the engineering must consider message supervision, quality information, communication redundancy and the safe response to communication failure.
8. Synchrocheck – Function 25
Synchrocheck verifies whether the electrical conditions on two sides of a circuit breaker are suitable for closing.
It is particularly important for:
- Bus coupler circuit breakers
- Bus section circuit breakers
- Transmission line circuit breakers
- Generator connection circuit breakers
- Transformer and network interconnections
The synchrocheck function typically evaluates:
- Voltage magnitude difference
- Frequency difference
- Phase-angle difference
- Live and dead bus conditions
- Live and dead line conditions
A simplified synchrocheck condition can be represented as:
[
|\Delta U| \leq \Delta U_{\text{max}}
]
[
|\Delta f| \leq \Delta f_{\text{max}}
]
[
|\Delta \varphi| \leq \Delta \varphi_{\text{max}}
]
Where:
- (\Delta U) is the voltage difference.
- (\Delta f) is the frequency difference.
- (\Delta \varphi) is the phase-angle difference.
The actual limits are determined by the system requirements and device configuration.
A close command is permitted only when the configured synchronism conditions are satisfied, unless an approved alternative operating mode is selected.
9. Automatic Reclosing – Function 79
Automatic reclosing is an important function in overhead transmission and distribution systems.
After a protection trip, the automatic reclosing function can issue a closing command following a configured dead time.
Typical settings include:
- Single-shot or multi-shot operation
- Dead time
- Reclaim time
- Reclosing mode
- Single-pole or three-pole reclosing, where supported
- Blocking conditions
- Synchronism-check supervision
- Interaction with protection functions
The 6MD86 supports automatic reclosing as an optional function, subject to the ordered configuration.
The protection relay and bay controller coordination must be carefully engineered. The protection trip, breaker status, reclosing initiation and closing command must operate in the correct sequence.
10. Circuit-Breaker Failure Protection – Function 50BF
Circuit-breaker failure protection detects situations where a circuit breaker does not interrupt the fault current after receiving a trip command.
A typical breaker-failure sequence includes:
- A protection function issues a trip command.
- The breaker-failure logic starts.
- The device checks whether current has disappeared or the breaker has reached the expected open state.
- If the breaker fails to clear the fault within the configured time, backup tripping is initiated.
Depending on the protection scheme, backup tripping may involve adjacent circuit breakers or busbar protection logic.
Important engineering considerations include:
- Breaker-failure initiation signals
- Current detection thresholds
- Breaker position supervision
- Timer settings
- Retrip logic
- Backup trip outputs
- Coordination with busbar protection
The 6MD86 supports circuit-breaker failure protection as an optional function. Its availability must be checked against the selected device configuration.
11. Point-on-Wave Switching
Point-on-Wave (PoW) switching is an advanced switching technique that controls the exact electrical instant at which a circuit breaker operates.
It is used to reduce switching transients and improve equipment performance.
Typical applications include:
- Power transformers
- Shunt reactors
- Capacitor banks
- Other switching applications where controlled energization is beneficial
The controller calculates or determines the appropriate switching instant based on electrical conditions and the operating characteristics of the circuit breaker.
The actual performance depends on:
- Voltage and current waveforms
- Breaker operating time
- Pole scatter
- Switching equipment characteristics
- Application-specific control settings
The 6MD86 supports Point-on-Wave switching as a configurable capability. The required hardware, function scope and application suitability should be verified before project implementation.
12. Protection Functions
Although the 6MD85 and 6MD86 are bay controllers, they can also include protection functions from the SIPROTEC 5 function library.
Depending on the ordered configuration, application and available resources, these may include functions such as:
- Overcurrent protection
- Earth-fault protection
- Voltage protection
- Frequency protection
- Directional protection
- Thermal overload protection
- Other application-specific protection functions
The availability of each function must be verified against the specific device configuration.
A bay controller should not automatically be considered a complete replacement for a dedicated protection relay. The protection philosophy, redundancy requirements, required protection functions and reliability assessment must determine whether protection and control are combined or separated.
13. Measurement and Monitoring
The 6MD85 and 6MD86 can provide electrical measurements and equipment monitoring.
Depending on the hardware and configured functions, available information may include:
- Phase currents
- Phase voltages
- Residual current
- Residual voltage
- Active power
- Reactive power
- Apparent power
- Power factor
- Frequency
- Energy measurements
- Equipment status information
These measurements can be used for:
- Local operation
- SCADA indication
- Operational monitoring
- Alarm processing
- Event analysis
- Maintenance activities
Correct CT and VT ratios, polarity, phase assignment and measurement configuration are essential for accurate results.
14. Fault Recording and Event Analysis
Fault recording and event information help engineers understand the behavior of the electrical system and the operation of the bay controller.
The SIPROTEC 5 platform provides recording and analysis capabilities, subject to the device configuration.
Useful information includes:
- Binary event records
- Switching operation records
- Protection and automation events
- Electrical disturbance records
- Time-stamped status changes
- Operational alarms
Recorded information can be used to investigate:
- Incorrect switching operations
- Unexpected interlocking
- Breaker operation failures
- Communication problems
- Protection and control coordination issues
Engineers can use the available DIGSI 5 tools and associated analysis functions to review recorded information.
15. IEC 61850 Communication
IEC 61850 is a major part of modern SIPROTEC 5 substation automation engineering.
The 6MD85 and 6MD86 can communicate with other IEDs, station controllers, gateways and SCADA systems using supported IEC 61850 services.
15.1 IEC 61850 MMS
Manufacturing Message Specification (MMS) is used for client-server communication.
Typical applications include:
- Reading measurements
- Reading equipment status
- Receiving alarms and events
- Remote control
- Reporting
- Device information exchange
An IEC 61850 client, such as a station-level automation system, can communicate with the bay controller through the configured logical nodes and data objects.
15.2 IEC 61850 GOOSE
Generic Object-Oriented Substation Event (GOOSE) communication provides fast event-based data exchange between IEDs.
Typical applications include:
- Interlocking between bays
- Breaker status exchange
- Blocking signals
- Protection-related signals
- Trip and permissive signals
- Automation logic
For example, a GOOSE message can transfer the status of a circuit breaker or disconnector to another IED for interlocking purposes.
GOOSE engineering requires correct configuration of:
- Publisher and subscriber datasets
- GOOSE control blocks
- VLAN settings, where used
- Application identifiers
- MAC addresses
- Communication supervision
- Signal quality and validity
A GOOSE communication failure must be considered in the safety and interlocking design.
15.3 IEC 61850 SCL Engineering
Substation Configuration Language (SCL) is used to describe the IEC 61850 system configuration.
Important SCL file types include:
- ICD – IED Capability Description
- CID – Configured IED Description
- SCD – Substation Configuration Description
- IID – Instantiated IED Description
SCL engineering helps coordinate the bay controller with the rest of the substation automation system.
The engineering workflow should include checking the device capabilities, logical nodes, datasets, report control blocks, GOOSE subscriptions and communication parameters.
16. Other Communication Protocols
Besides IEC 61850, the SIPROTEC 5 platform supports different communication protocols depending on the device hardware and communication modules.
These may include:
- IEC 60870-5-103
- IEC 60870-5-104
- Modbus TCP
- DNP3 serial
- DNP3 TCP
- PROFINET IO
- IEC 61850-9-2 Client
The exact protocol availability depends on the device variant and ordered communication modules.
The devices also support network redundancy technologies such as PRP and HSR where the appropriate hardware and configuration are provided.
Communication architecture should be defined during the substation design stage rather than treated as a final commissioning detail.
17. DIGSI 5 Engineering for 6MD85 and 6MD86
DIGSI 5 is the engineering software used to configure, parameterize, test and manage SIPROTEC 5 devices.
It is an essential tool for bay controller engineering.
Typical engineering activities include:
- Creating a new project
- Adding the 6MD85 or 6MD86 device
- Selecting the correct device variant
- Configuring hardware modules
- Assigning binary inputs and outputs
- Configuring measurement inputs
- Adding protection functions
- Engineering bay control
- Configuring switchgear interlocking
- Defining control authority
- Configuring IEC 61850 communication
- Creating and checking GOOSE signals
- Engineering CFC logic
- Downloading the configuration
- Performing functional tests
17.1 Creating a DIGSI 5 Project
The first step is to create a project and insert the correct SIPROTEC 5 device.
The engineer must select the correct device type and hardware configuration.
An incorrect hardware selection can lead to differences between the engineering project and the physical device.
17.2 Hardware Configuration
The hardware configuration defines the available measurement inputs, binary inputs, binary outputs and communication interfaces.
The engineer should check:
- Current input arrangement
- Voltage input arrangement
- Binary input voltage levels
- Binary output characteristics
- Communication modules
- Expansion modules
- Front panel and display options
17.3 Configuring Binary Inputs
Binary inputs are used to receive signals from primary equipment and auxiliary circuits.
Examples include:
- Circuit breaker open
- Circuit breaker closed
- Disconnector open
- Disconnector closed
- Earthing switch open
- Earthing switch closed
- Spring charged
- Protection trip
- Local/remote selection
- External blocking
- Gas or pressure alarm
The correct assignment and signal polarity must be checked during engineering and commissioning.
17.4 Configuring Binary Outputs
Binary outputs are used to operate external equipment or communicate control signals.
Examples include:
- Circuit-breaker closing command
- Circuit-breaker tripping command
- Disconnector operation
- Earthing-switch operation
- Alarm output
- External interlocking signal
- Indication output
Output contacts must be checked against the actual control circuit drawings and equipment requirements.
17.5 Configuring CFC Logic
Continuous Function Chart (CFC) is used to create automation and logic functions in SIPROTEC 5 devices.
CFC can be used for:
- Interlocking logic
- Signal processing
- Alarm generation
- Control conditions
- Blocking logic
- Switching sequences
- Logical combinations
- Data processing
The logic must be documented and tested before the device is placed into service.
18. Practical Example – Circuit-Breaker Closing Logic
Consider a typical high-voltage line bay.
An operator sends a circuit-breaker closing command from the station HMI.
The bay controller receives the command and checks the configured conditions.
A simplified closing permission can be represented as:
[
ClosePermission =
CBReady \land DSPositionOK \land ESOpen \land InterlockOK
]
Where:
- (CBReady): circuit breaker is ready for operation.
- (DSPositionOK): required disconnector positions are correct.
- (ESOpen): earthing switch is open.
- (InterlockOK): all configured interlocking conditions are satisfied.
If synchrocheck is required, the closing permission must also include the synchrocheck result:
[
ClosePermission =
CBReady \land DSPositionOK \land ESOpen
\land InterlockOK \land SyncOK
]
This is a simplified engineering example, not a universal Siemens logic template. Actual logic must consider the switchgear design, control philosophy, device function configuration and safety requirements.
19. Testing and Commissioning
Commissioning a SIPROTEC 6MD85 or 6MD86 requires more than checking whether the device communicates with the station HMI.
The complete control and automation functions must be tested.
19.1 Hardware Inspection
Check:
- Device type and order number
- Auxiliary supply voltage
- Hardware modules
- Terminal connections
- CT and VT wiring
- Binary input wiring
- Binary output wiring
- Ethernet connections
- Grounding and shielding
- Panel installation
19.2 Binary Input Testing
Verify all relevant status signals.
For example:
| Signal | Expected indication |
|---|---|
| Circuit breaker open | Open position |
| Circuit breaker closed | Closed position |
| Disconnector open | Open position |
| Disconnector closed | Closed position |
| Earthing switch open | Open position |
| Earthing switch closed | Closed position |
| Local control selected | Local mode |
| Remote control selected | Remote mode |
Check the correct signal mapping and ensure that inconsistent double-point indications are handled correctly.
19.3 Binary Output Testing
Test each control output according to the approved commissioning procedure.
Examples include:
- Circuit-breaker trip
- Circuit-breaker close
- Disconnector open
- Disconnector close
- Earthing-switch operation
- Alarm outputs
Before testing outputs, ensure that the primary equipment is in a safe condition and that unintended operation is prevented.
19.4 Interlocking Tests
Interlocking testing is one of the most important commissioning activities.
Test both permitted and prohibited operations.
For example:
- Attempt to close a circuit breaker with the earthing switch closed.
- Attempt to operate a disconnector under a prohibited condition.
- Check interlocking between bays.
- Verify blocking signals.
- Verify the response to invalid or missing position indications.
The expected result should be defined in the approved interlocking matrix.
19.5 Synchrocheck Testing
Where synchrocheck is configured, verify:
- Voltage measurement inputs
- Voltage difference limits
- Frequency difference limits
- Phase-angle difference limits
- Live/dead bus selection
- Live/dead line selection
- Closing permission
- Blocking conditions
The test should cover both permissive and non-permissive operating conditions.
19.6 IEC 61850 Testing
Communication testing should include:
- MMS communication
- Report control blocks
- Measurements
- Status indications
- Remote control
- GOOSE publishing
- GOOSE subscription
- GOOSE signal mapping
- Communication redundancy, where used
- Communication failure response
Tools such as Siemens IEDScout and suitable IEC 61850 test tools can help engineers verify the communication model and message exchange.
19.7 Omicron Testing
An Omicron CMC test set can be useful for testing measurement-dependent functions and protection functions included in the bay controller configuration.
For example, it can be used to inject current and voltage signals and verify relevant protection or synchrocheck behavior, where supported by the test setup.
Binary I/O testing and communication testing should be included in the overall commissioning plan. The use of a secondary injection test set does not replace the need to verify the complete primary equipment control circuits.
20. Common Problems and Troubleshooting
Problem 1: Circuit Breaker Closing Command Is Not Executed
Possible causes:
- Interlocking condition is not satisfied.
- Circuit breaker position is incorrect.
- Disconnector position is incorrect.
- Earthing switch is closed.
- Local/remote control selection is incorrect.
- Synchrocheck is blocking the command.
- An external blocking signal is active.
- Binary input mapping is incorrect.
Recommended checks:
Review the control command, equipment position indications, interlocking conditions and event records in DIGSI 5.
Problem 2: Incorrect Disconnector Position
Possible causes:
- Incorrect binary input assignment.
- Wiring problem.
- Incorrect signal polarity.
- Faulty auxiliary contacts.
- Inconsistent double-point indication.
Recommended checks:
Compare the physical auxiliary contacts with the DIGSI 5 signal status and check the terminal wiring.
Problem 3: GOOSE Interlocking Does Not Work
Possible causes:
- Incorrect publisher dataset.
- Incorrect subscriber configuration.
- Wrong GOOSE control block.
- Network configuration problem.
- VLAN or multicast filtering issue.
- Incorrect signal mapping.
- Invalid or poor-quality received information.
Recommended checks:
Verify the SCD configuration, GOOSE publisher and subscriber settings, network parameters and received signal quality.
Problem 4: Incorrect Measurement Values
Possible causes:
- Incorrect CT or VT ratio.
- Incorrect phase assignment.
- Incorrect polarity.
- Wiring errors.
- Incorrect measurement configuration.
Recommended checks:
Verify the physical wiring, device settings and injected reference values.
Problem 5: Communication With SCADA Is Unavailable
Possible causes:
- Incorrect IP configuration.
- Network connection problem.
- Incorrect IEC 61850 configuration.
- Client/server configuration mismatch.
- Communication module problem.
- Network redundancy configuration error.
Recommended checks:
Check the communication settings, network infrastructure, device diagnostics and IEC 61850 configuration.
Problem 6: Switching Sequence Does Not Execute
Possible causes:
- Incorrect sequence configuration.
- Missing permissive conditions.
- Incorrect equipment feedback.
- Active blocking signals.
- Incorrect sequence timing.
Recommended checks:
Review the switching sequence logic and verify each required condition step by step.
21. Cybersecurity and Network Reliability
Cybersecurity is an important consideration in modern substation automation systems.
SIPROTEC 5 devices provide security-related features such as:
- Role-based access control
- Security event logging
- Signed firmware
- Authenticated network access
- Secure engineering practices
Network architecture may also include redundancy technologies such as:
- PRP – Parallel Redundancy Protocol
- HSR – High-availability Seamless Redundancy
- VLAN-based network segmentation
These features must be implemented as part of a complete cybersecurity and network engineering strategy.
Correct user management, engineering access control, firmware management and network configuration are essential for secure operation.
22. 6MD85 and 6MD86 in Substation Automation Systems
The bay controller is an important component of a modern substation automation architecture.
A simplified system may include:
Process level
- Circuit breakers
- Disconnectors
- Earthing switches
- CTs and VTs
- Auxiliary equipment
Bay level
- SIPROTEC 6MD85 or 6MD86
- Protection IEDs
- Bay-level automation functions
Station level
- SICAM PAS or another station automation system
- Station HMI
- Gateway
- Engineering workstation
Control-centre level
- Remote SCADA
- Network control centre
- Supervisory and operational systems
The bay controller communicates with the station-level system and exchanges information with other IEDs.
IEC 61850 MMS and GOOSE can be used to support communication between the different levels, depending on the architecture.
23. SIPROTEC 6MD85 and 6MD86 vs SIPROTEC 4 Bay Controllers
Siemens SIPROTEC 5 devices are the newer generation compared with the SIPROTEC 4 platform.
Some older Siemens bay controllers include:
- SIPROTEC 4 6MD61
- SIPROTEC 4 6MD63
- SIPROTEC 4 6MD66
The SIPROTEC 5 6MD85 and 6MD86 use DIGSI 5 rather than DIGSI 4.
Important differences include:
| Subject | SIPROTEC 4 | SIPROTEC 5 |
|---|---|---|
| Engineering software | DIGSI 4 | DIGSI 5 |
| Hardware architecture | Earlier device architecture | Modular and expandable |
| IEC 61850 engineering | Supported on applicable devices | Integrated SIPROTEC 5 engineering environment |
| Function configuration | Device-dependent | Flexible function configuration |
| Communication | Depends on model | Modular communication options |
| Hardware expansion | More limited | Modular expansion system |
| Automation engineering | Device-dependent | CFC and advanced automation capabilities |
Replacing a SIPROTEC 4 bay controller with a SIPROTEC 5 device is not simply a matter of transferring the old configuration.
The engineer must review:
- Hardware and terminal arrangements
- Binary input and output mapping
- Control philosophy
- Interlocking logic
- IEC 61850 data model
- Communication configuration
- SCADA signal mapping
- Commissioning and testing procedures
24. Important Engineering Considerations
Before selecting or engineering a SIPROTEC 6MD85 or 6MD86, consider the following:
- Define the bay control philosophy.
- Prepare the complete switchgear single-line diagram.
- Develop the interlocking matrix.
- Define the local, station and remote control hierarchy.
- Identify the required number of binary inputs and outputs.
- Determine the CT and VT measurement requirements.
- Select the appropriate hardware configuration.
- Define the required protection functions.
- Design the IEC 61850 communication architecture.
- Define GOOSE signals and inter-IED logic.
- Prepare the DIGSI 5 project.
- Develop the commissioning and functional test procedures.
A well-engineered bay controller project requires coordination between protection engineers, substation automation engineers, switchgear designers and commissioning personnel.
25. Training on Siemens SIPROTEC 5 Bay Controllers
Elec-Engg provides practical training in Siemens SIPROTEC 5 protection, control and substation automation systems.
Our training programs are designed for protection engineers, commissioning engineers, electrical maintenance engineers, substation automation engineers and professionals working with Siemens protection and control equipment.
Relevant training subjects include:
- SIPROTEC 5 architecture and hardware
- SIPROTEC 6MD85 and 6MD86 bay controller configuration
- DIGSI 5 project creation and device configuration
- Binary input and output assignment
- Circuit-breaker and disconnector control
- Switchgear interlocking engineering
- Synchrocheck configuration
- CFC logic engineering
- IEC 61850 MMS communication
- IEC 61850 GOOSE engineering
- SCL files and system integration
- Testing and commissioning
- Troubleshooting and practical engineering examples
Available Training Methods
Elec-Engg provides:
- Online training: Instructor-led technical training for engineers in different countries.
- Structured self-paced training: Organized lessons, practical exercises, assignments and assessments.
- Face-to-face training: Practical classroom training for engineering and maintenance teams.
- Customized in-house training: Training programs developed around the equipment, project requirements and experience level of a company.
Our objective is to help engineers understand not only the device functions but also how to configure, test, commission and troubleshoot real substation protection and automation systems.
For more information about Siemens SIPROTEC 5 training and customized programs, visit Elec-Engg.com.
- Siemens SIPROTEC 5
- SIPROTEC 6MD85
- SIPROTEC 6MD86
- Siemens Bay Controller
- Bay Control Unit
- Substation Automation
- DIGSI 5
- IEC 61850
- GOOSE
- Switchgear Interlocking
- Synchrocheck
- Circuit Breaker Control
- Protection and Control
- Siemens Protection Relays
26. Frequently Asked Questions
What is the Siemens SIPROTEC 6MD85?
The SIPROTEC 6MD85 is a modular bay controller designed for distribution and high-voltage applications. It provides bay control, automation, monitoring and configurable protection functions.
What is the Siemens SIPROTEC 6MD86?
The SIPROTEC 6MD86 is a modular bay controller designed for more demanding applications, particularly in transmission systems. It supports advanced control and automation functions, including optional automatic reclosing, circuit-breaker failure protection and Point-on-Wave switching.
What is the main difference between 6MD85 and 6MD86?
The 6MD85 is primarily positioned for distribution and high-voltage applications, while the 6MD86 is designed for transmission applications and offers additional functional options. Their hardware variants and functional scope are different.
Which software is used to configure 6MD85 and 6MD86?
Both devices are configured using Siemens DIGSI 5 engineering software.
Do 6MD85 and 6MD86 support IEC 61850?
Yes. They support IEC 61850 communication, including MMS and GOOSE, subject to the device configuration and communication hardware.
Can the 6MD85 and 6MD86 control circuit breakers and disconnectors?
Yes. They are designed for bay control and can process switching commands, equipment status signals and interlocking conditions.
Does the 6MD86 support automatic reclosing?
Yes, automatic reclosing is available as an optional function, subject to the selected device configuration.
Does the 6MD86 support Point-on-Wave switching?
Yes. Siemens identifies Point-on-Wave switching as one of the advanced capabilities of the 6MD86, subject to the ordered functional scope and application requirements.
Can a 6MD85 or 6MD86 replace a dedicated protection relay?
It may combine bay control with selected protection functions, but whether it can replace a dedicated relay depends on the protection philosophy, required functions, redundancy and project requirements.
Is DIGSI 4 used for 6MD85 and 6MD86?
No. These are SIPROTEC 5 devices and are engineered using DIGSI 5.
27. Conclusion
The Siemens SIPROTEC 5 6MD85 and 6MD86 are powerful modular bay controllers for modern substation control and automation applications.
They combine switching-device control, interlocking, measurement, monitoring, configurable protection functions and IEC 61850 communication in a flexible IED platform.
The 6MD85 is particularly suitable for distribution and high-voltage applications, while the 6MD86 offers additional capabilities for demanding transmission applications.
Correct hardware selection, DIGSI 5 configuration, interlocking engineering, IEC 61850 integration and comprehensive commissioning tests are essential for reliable operation.
For engineers working with modern substations, understanding these devices is an important part of protection, control and substation automation engineering.