- 1. Introduction
- 2. What Is GOOSE Communication?
- 3. GOOSE Publisher and Subscriber Architecture
- 4. GOOSE Communication Compared with MMS
- 5. GOOSE Data Model and Dataset Engineering
- 6. GOOSE Control Block
- 7. GOOSE Multicast MAC Address
- 8. GOOSE APPID, VLAN and Priority
- 9. GOOSE Retransmission and State Changes
- 10. Practical Application 1: Feeder-to-Feeder Protection Blocking
- 11. Practical Application 2: Busbar Trip Distribution
- 12. Practical Application 3: Breaker Failure Signal Exchange
- 13. GE Multilin GOOSE Configuration Workflow
- Step 1 – Verify Relay Capability
- Step 2 – Obtain the Correct SCL File
- Step 3 – Import the IED
- Step 4 – Define the Publisher Dataset
- Step 5 – Configure the GOOSE Control Block
- Step 6 – Configure Subscribers
- Step 7 – Configure the Ethernet Switches
- Step 8 – Download Configuration
- Step 9 – Verify Communication
- Step 10 – Test the Protection Application
- 14. SCL Engineering for GOOSE
- 15. GOOSE Testing with IEDScout
- 16. GOOSE Testing with Wireshark
- 17. GOOSE Communication Failure Supervision
- 18. GOOSE Redundancy and Network Architecture
- 19. GOOSE Commissioning and End-to-End Testing
- 20. GOOSE Test Matrix
- 21. Common GOOSE Engineering Mistakes
- Mistake 1: Assuming All Relays Support GOOSE
- Mistake 2: Incorrect Dataset Selection
- Mistake 3: Incorrect APPID or Multicast Address
- Mistake 4: VLAN Mismatch
- Mistake 5: Incorrect Subscriber Mapping
- Mistake 6: Ignoring Communication Failure
- Mistake 7: Testing Only the Ethernet Message
- Mistake 8: Failing to Update Configuration Revisions
- 22. Practical GOOSE Commissioning Checklist
- 23. Training on GE Multilin GOOSE Communication by Elec-Engg
- 24. Conclusion
- 25. Frequently Asked Questions
- 1. What is GOOSE communication in GE Multilin relays?
- 2. What is the difference between a GOOSE publisher and subscriber?
- 3. Can GE Multilin relays exchange trip signals using GOOSE?
- 4. What is a GOOSE dataset?
- 5. What is a GOOSE Control Block?
- 6. What are APPID and VLAN in GOOSE communication?
- 7. Why are GOOSE messages retransmitted?
- 8. Can GOOSE replace all hardwired signals?
- 9. How can GOOSE communication be tested?
- 10. Can Wireshark analyse GOOSE messages?
- 11. What happens if GOOSE communication fails?
- 12. Where can I receive practical GE Multilin GOOSE training?
1. Introduction
Generic Object-Oriented Substation Event (GOOSE) communication is one of the most important services in IEC 61850-based substation automation. It enables intelligent electronic devices (IEDs) to exchange event information over Ethernet without requiring a separate hardwired connection for every signal.
For protection engineers working with GE Multilin relays, GOOSE communication can support applications such as:
- Protection blocking between feeder relays
- Breaker failure initiation and coordination
- Busbar protection trip distribution
- Transformer and feeder interlocking
- Transfer trip signals
- Circuit-breaker status exchange
- Trip permissive schemes
- Alarm and protection status exchange
However, successful GOOSE engineering requires more than enabling IEC 61850 communication. Engineers must understand publisher and subscriber configuration, datasets, GOOSE control blocks, multicast addressing, VLANs, APPID, configuration revisions, communication supervision and application logic.
This article explains the practical engineering principles of GOOSE communication for GE Multilin protection relays, including configuration, system design, testing and troubleshooting.
Important: GOOSE functionality varies by GE Multilin relay model, firmware, hardware and IEC 61850 implementation. The examples in this article describe general engineering principles. Confirm the exact GOOSE publishing, subscription, dataset and logic capabilities of the installed relay before applying them to a project.
2. What Is GOOSE Communication?
GOOSE is an IEC 61850 communication service designed for fast exchange of event information between IEDs.
Unlike conventional client-server communication, GOOSE uses a publisher-subscriber model.
- A publisher creates and transmits a GOOSE message.
- One or more subscribers receive the message.
- The subscriber processes the received information according to its configured logic.
GOOSE messages are transmitted using Ethernet multicast frames.
<AsyncImage query=”IEC 61850 GOOSE publisher subscriber communication architecture diagram with two protection relays and Ethernet switch” aspectRatio=”16:9″ width=”100%”/>
For example, a GE Multilin feeder relay detects a fault and publishes a protection-start signal. An upstream GE Multilin relay subscribes to this signal and uses it in a blocking or coordination scheme, if the required functions are supported.
2.1 Why Is GOOSE Used?
In a conventional substation, exchanging a protection signal between two relays may require:
- A binary output from the sending relay.
- A copper cable between panels.
- A binary input on the receiving relay.
- Input configuration and logic programming.
GOOSE can exchange the signal through the Ethernet network instead.
Potential advantages include:
- Reduced inter-panel wiring
- Flexible signal distribution
- Easier integration of multiple IEDs
- Standardized communication structures
- Support for advanced protection and interlocking schemes
- Improved access to communication diagnostics
GOOSE does not automatically replace all hardwired protection circuits. Critical trip circuits, safety-related circuits and project-specific functions may still require hardwired connections.
3. GOOSE Publisher and Subscriber Architecture
Understanding the publisher-subscriber architecture is fundamental to IEC 61850 engineering.
3.1 GOOSE Publisher
The publisher is the IED that transmits information.
For example, a GE Multilin feeder relay may publish:
- Overcurrent protection start
- Earth-fault protection operation
- Circuit-breaker position
- Breaker failure indication
- Protection blocking status
The published information is selected through an IEC 61850 dataset associated with a GOOSE Control Block.
3.2 GOOSE Subscriber
The subscriber receives the published information.
For example, an upstream relay may subscribe to a downstream feeder’s protection-start signal.
The received information can be connected to an internal logic function, provided the relay supports the required subscription and application functionality.
3.3 One Publisher and Multiple Subscribers
A GOOSE publisher can distribute information to multiple subscribers.
For example, a busbar protection IED may publish a trip signal that is received by several feeder or transformer IEDs.
The engineering design must verify that every intended subscriber supports the required GOOSE configuration and that the Ethernet network distributes the multicast traffic correctly.
3.4 GOOSE Communication Is Not a Direct Trip Guarantee
Receiving a GOOSE frame does not automatically mean that the intended circuit breaker will trip.
The complete application includes:
- Correct publisher information.
- Correct dataset configuration.
- Correct GOOSE transmission.
- Correct subscriber mapping.
- Valid communication supervision.
- Correct internal logic.
- Correct output configuration.
- Correct circuit-breaker trip circuit.
Every stage must be tested.
4. GOOSE Communication Compared with MMS
GOOSE and MMS are both used in IEC 61850 systems, but they serve different communication purposes.
| Feature | GOOSE | MMS |
|---|---|---|
| Communication model | Publisher-subscriber | Client-server |
| Main purpose | Event and status exchange | Data access and reporting |
| Transport | Ethernet multicast | Commonly TCP/IP |
| Typical application | Blocking, interlocking, trip signals | SCADA measurements and status |
| Communication pattern | Repeated event messages | Client requests and server responses |
| Typical subscribers or clients | Other IEDs | SCADA, gateway, engineering tools |
| Event handling | State-based retransmission | Reports and data access services |
A GE Multilin relay may support one or more IEC 61850 services depending on its implementation. Do not assume that GOOSE and MMS support are identical across all relay models.
5. GOOSE Data Model and Dataset Engineering
GOOSE communication depends on the IEC 61850 data model.
A GOOSE publisher does not simply transmit an arbitrary text signal. It publishes selected IEC 61850 data attributes through a configured dataset.
5.1 Logical Nodes
Logical nodes represent functions or information categories.
Examples relevant to protection and control include:
| Logical node | Typical information |
|---|---|
| PTOC | Time overcurrent protection |
| PIOC | Instantaneous overcurrent protection |
| PDIF | Differential protection |
| PDIS | Distance protection |
| PTRC | Protection trip conditioning |
| XCBR | Circuit-breaker information |
| XSWI | Switch information |
| GGIO | Generic process input/output |
| RBRF | Breaker failure protection |
The actual nodes and data objects available depend on the specific relay.
5.2 Data Objects and Attributes
A logical node contains data objects, which in turn contain data attributes.
For example, protection information may include:
- Start status
- Operate status
- Quality
- Timestamp
- Additional status or configuration information
The exact data reference must be taken from the actual IED data model.
5.3 What Is a Dataset?
A dataset is a collection of IEC 61850 data attributes.
For a feeder protection application, a dataset might contain:
- Overcurrent start
- Earth-fault start
- Protection trip
- Circuit-breaker position
- Device health status
A dataset should contain only the information required for its intended application.
5.4 Dataset Engineering Recommendations
When creating a GOOSE dataset:
- Identify the required protection or control information.
- Locate the relevant logical node.
- Select the correct data object.
- Select the required data attribute.
- Include quality information where required.
- Confirm that the publisher supports the selected data.
- Confirm that subscribers can process the information.
- Verify the final dataset in the system configuration.
Avoid selecting large quantities of unnecessary information. A carefully designed dataset is easier to maintain and troubleshoot.
6. GOOSE Control Block
The GOOSE Control Block (GoCB) defines the publishing configuration associated with a dataset.
It contains information required to transmit GOOSE messages.
Typical parameters include:
- GOOSE control block reference
- Dataset reference
- GOOSE identifier
- Application identifier
- Multicast destination address
- VLAN configuration
- Priority
- Configuration revision
- Minimum and maximum retransmission timing parameters, where applicable
The exact parameter availability and configuration method depend on the IED.
6.1 GOOSE Identifier
The GOOSE identifier is used to identify the GOOSE application or message.
It should be meaningful and managed consistently in the engineering project.
6.2 Dataset Reference
The dataset reference identifies the information being transmitted.
A mismatch between the publisher’s dataset and the subscriber’s expected data structure can result in incorrect or unsuccessful integration.
6.3 Configuration Revision
The configuration revision is important when a GOOSE publisher configuration changes.
When the dataset or GOOSE configuration is modified, the engineering team must ensure that subscribers have the corresponding updated configuration.
A configuration revision mismatch can result in communication or application problems.
7. GOOSE Multicast MAC Address
GOOSE uses Ethernet multicast communication.
The destination MAC address identifies the multicast group used by the GOOSE message.
The multicast address is part of the communication design and must be correctly configured in the system.
7.1 Why Is Multicast Used?
One publisher may need to transmit information to several subscribers.
Multicast allows the network to distribute a message to the intended group without requiring a separate unicast transmission for every subscriber.
7.2 Engineering Considerations
Check:
- Correct multicast address
- No unintended address duplication
- Correct switch multicast handling
- VLAN configuration
- Subscriber connectivity
- Network topology
- Switch port configuration
Do not assume that a GOOSE message visible on one switch port will automatically be visible on every other port.
8. GOOSE APPID, VLAN and Priority
Three important communication parameters are APPID, VLAN ID and Ethernet priority.
8.1 APPID
APPID is the Application Identifier used to identify a GOOSE application within the Ethernet communication environment.
The publisher and subscriber engineering must be consistent with the intended APPID.
8.2 VLAN ID
A Virtual Local Area Network can be used to separate GOOSE traffic from other Ethernet traffic.
For example, an engineering project may define separate VLANs for:
- GOOSE protection communication
- Station-level MMS communication
- Engineering access
- Other operational network services
The actual VLAN architecture should follow the project network design.
8.3 Ethernet Priority
Ethernet priority can help give time-critical traffic preferential treatment.
It must be coordinated with the switch configuration and overall network engineering.
8.4 Common Configuration Mistakes
Typical mistakes include:
- Different VLAN IDs on publisher and subscriber paths
- Incorrect APPID
- Incorrect multicast address
- Switch ports assigned to the wrong VLAN
- Inconsistent priority configuration
- Multicast filtering blocking the message
These problems can make a correctly configured GOOSE publisher appear unavailable to a subscriber.
9. GOOSE Retransmission and State Changes
GOOSE messages are transmitted repeatedly to improve communication reliability.
When an event occurs, the publisher sends a message indicating the new state. It then retransmits the message according to its configured retransmission strategy.
The retransmission interval generally increases after a state change until the steady-state transmission interval is reached.
When another state change occurs, the transmission process accelerates again.
9.1 State Number
The state number identifies a change in the published GOOSE state.
It is useful when examining whether a new event has been transmitted.
9.2 Sequence Number
The sequence number is associated with the transmission sequence for a particular state.
It helps identify repeated transmissions and changes in the message sequence.
9.3 Why Retransmission Matters
Repeated transmission helps subscribers receive the latest state even if an individual Ethernet frame is lost.
However, retransmission does not eliminate the need for network supervision and communication-failure handling.
9.4 Timing Considerations
GOOSE performance depends on:
- Publisher processing
- Network switch performance
- Network topology
- Ethernet traffic
- Subscriber processing
- Application logic
- Configuration of the communication services
For protection applications, verify the required end-to-end performance through appropriate testing. Do not assume a universal GOOSE operating time for every GE Multilin relay or network.
10. Practical Application 1: Feeder-to-Feeder Protection Blocking
Consider an 11 kV distribution system with two feeder relays.
The downstream feeder is protected by a GE Multilin relay. An upstream relay provides backup protection.
The objective is to use GOOSE communication to exchange a blocking signal.
10.1 System Operation
Under normal conditions:
- Both feeders operate normally.
- No blocking signal is active.
- The upstream protection remains available as backup.
When a downstream fault occurs:
- The downstream relay detects the fault.
- The downstream relay publishes the required protection-start or blocking information.
- The upstream relay receives the GOOSE message.
- The upstream relay applies the configured blocking logic.
- The downstream relay trips its circuit breaker.
- The upstream relay remains restrained for the coordinated fault, provided all scheme conditions are satisfied.
10.2 Illustrative Logic
A simplified conceptual expression is:
[
Trip_{upstream}=OC_{upstream}\land \neg Blocking
]
Where:
- (OC_{upstream}) is the upstream overcurrent operating condition.
- (Blocking) is the valid received blocking signal.
This is a conceptual equation, not a universal GE Multilin logic implementation.
10.3 Important Engineering Considerations
The engineer must define:
- Which protection element initiates the signal
- Whether the signal represents start or operation
- Blocking duration
- Communication supervision
- Behaviour during communication loss
- Backup trip timing
- Reset conditions
- Fail-safe or fail-secure philosophy
The scheme must be tested for both normal communication and communication failure.
11. Practical Application 2: Busbar Trip Distribution
A busbar protection scheme may need to trip multiple circuit breakers.
In a conventional system, separate hardwired trip outputs and wiring may be used.
Where supported and approved by the protection design, GOOSE can distribute selected trip information to several IEDs.
11.1 Illustrative Architecture
A busbar protection IED publishes a trip indication.
The intended feeder and transformer IEDs subscribe to the signal and process it through their configured trip logic.
11.2 Engineering Requirements
The design must verify:
- Correct bus-zone selection
- Correct breaker association
- Correct GOOSE dataset
- Correct subscriber mapping
- Correct trip logic
- Communication supervision
- Breaker failure coordination
- Redundancy requirements
- End-to-end operating performance
11.3 Important Safety Consideration
GOOSE-based trip distribution must only be used where the complete protection architecture, IED capabilities, network design and applicable project requirements support it.
A critical protection scheme must not rely on an unverified communication path.
12. Practical Application 3: Breaker Failure Signal Exchange
Breaker failure protection (ANSI 50BF) may require information to be exchanged between protection devices.
For example, a relay may publish breaker failure initiation or status information for another IED.
A GOOSE-based scheme may be used where the relevant relay functions and system design support it.
12.1 Typical Sequence
- A protection relay issues a trip command.
- The circuit breaker receives the trip command.
- Breaker auxiliary contacts and current supervision are monitored.
- If breaker failure is detected, the required signal is published.
- Other IEDs receive the information.
- The configured backup trip logic operates.
12.2 Engineering Checks
Verify:
- Breaker failure initiation
- Current supervision
- Breaker auxiliary contacts
- Breaker failure timer
- GOOSE publisher logic
- Subscriber logic
- Backup trip matrix
- Communication-loss response
The GOOSE signal must not replace the required local breaker failure detection unless the approved design explicitly provides for it.
13. GE Multilin GOOSE Configuration Workflow
The exact engineering software and configuration procedure depend on the GE Multilin relay family and firmware.
The following is a generic IEC 61850 engineering workflow.
Step 1 – Verify Relay Capability
Confirm:
- Exact model
- Hardware configuration
- Firmware version
- IEC 61850 edition
- GOOSE publishing support
- GOOSE subscription support
- Supported datasets
- Supported application logic
Step 2 – Obtain the Correct SCL File
Obtain the appropriate ICD or other applicable IED description file.
Check that it corresponds to the actual relay version.
Step 3 – Import the IED
Import the IED into the system configuration tool.
Review the available logical devices, logical nodes and data objects.
Step 4 – Define the Publisher Dataset
Select the data attributes required for the GOOSE application.
For example, select the relevant protection-start or breaker-status information.
Step 5 – Configure the GOOSE Control Block
Configure the required parameters, including:
- GOOSE control block
- Dataset reference
- GOOSE identifier
- APPID
- Multicast destination
- VLAN
- Priority
- Configuration revision
Use the actual parameter names and limits supported by the IED.
Step 6 – Configure Subscribers
Configure the receiving IEDs to subscribe to the required GOOSE information.
Map the received data to the appropriate internal logic.
Step 7 – Configure the Ethernet Switches
Check VLAN membership, multicast handling, priority and network topology.
Step 8 – Download Configuration
Transfer the configuration using the supported manufacturer procedure.
Verify that the configuration is accepted by the IED.
Step 9 – Verify Communication
Use suitable IEC 61850 tools and network analysis to confirm that messages are transmitted and received.
Step 10 – Test the Protection Application
Simulate the required signals and verify the complete protection or control response.
14. SCL Engineering for GOOSE
Substation Configuration Language is central to IEC 61850 system engineering.
GOOSE publisher and subscriber relationships are represented in the system configuration.
14.1 ICD File
The IED Capability Description file describes the IED’s supported data model and capabilities.
14.2 SCD File
The Substation Configuration Description file represents the system-level engineering configuration.
It can contain information about:
- IEDs
- Communication networks
- GOOSE control blocks
- Datasets
- Subscriber relationships
- Substation structure
14.3 CID File
The Configured IED Description file represents the configuration intended for an individual IED.
14.4 Engineering Process
A typical GOOSE engineering process is:
- Import the IED description files.
- Add the IEDs to the substation project.
- Define the required GOOSE datasets.
- Configure publisher control blocks.
- Define subscriber relationships.
- Configure network addressing.
- Generate the system configuration.
- Export the appropriate IED configuration.
- Load the configuration into the devices.
- Verify the resulting communication.
The final SCL files should be archived with the relay settings and commissioning records.
15. GOOSE Testing with IEDScout
IEDScout can be useful for inspecting IEC 61850 communication and IED data models.
Depending on the software version and available functionality, it can help engineers examine:
- IED data models
- Logical nodes
- Data objects
- Data attributes
- Communication services
- GOOSE-related information
15.1 Testing Procedure
- Connect the engineering computer to the substation Ethernet network.
- Configure the computer’s network interface.
- Verify network connectivity.
- Open IEDScout.
- Connect to the supported IEC 61850 server.
- Browse the data model.
- Inspect the required protection information.
- Check the configured GOOSE information using the available tools.
- Compare the observed information with the engineering configuration.
15.2 Important Limitation
IEDScout is an engineering and diagnostic tool, not a substitute for complete protection testing.
A visible GOOSE message does not prove that the subscriber’s internal logic or circuit-breaker trip circuit operates correctly.
16. GOOSE Testing with Wireshark
Wireshark is particularly useful for analysing GOOSE Ethernet frames.
It helps identify whether the publisher is transmitting the expected messages and whether the network is carrying them correctly.
<AsyncImage query=”Wireshark IEC 61850 GOOSE packet analysis Ethernet frame screenshot” aspectRatio=”16:9″ width=”100%”/>
16.1 Capture Preparation
Before starting a capture:
- Identify the publisher and subscriber IP or MAC addresses where applicable.
- Identify the relevant Ethernet switch ports.
- Configure a suitable mirror or monitoring port if necessary.
- Connect the engineering PC.
- Start the capture.
- Generate a controlled protection or test signal.
A capture point that does not receive the relevant multicast traffic may not show the messages.
16.2 GOOSE Packet Analysis
Inspect:
- Ethernet source MAC address
- Ethernet destination MAC address
- VLAN information
- APPID
- GOOSE control block reference
- Dataset reference
- State number
- Sequence number
- Configuration revision
- Test and simulation indicators, where applicable
- Time-related information
16.3 What to Look For
When a protection signal changes state:
- A new GOOSE state should be published.
- The message should contain the expected information.
- Retransmissions should follow the configured behaviour.
- The subscriber should receive the relevant message.
- The application logic should respond correctly.
16.4 Common GOOSE Packet Problems
| Observation | Possible explanation |
|---|---|
| No GOOSE frames visible | Publisher disabled, incorrect capture point or network issue |
| Wrong destination MAC | Incorrect publisher configuration |
| Wrong VLAN | Network or publisher configuration mismatch |
| Unexpected APPID | Incorrect communication engineering |
| Dataset differs from design | Wrong or outdated SCL configuration |
| State does not change | Publisher input or logic not operating |
| Subscriber reports invalid data | Configuration or communication mismatch |
| Frames visible but no operation | Subscriber mapping or application logic problem |
17. GOOSE Communication Failure Supervision
Protection engineers must consider what happens when GOOSE communication is interrupted.
Potential causes include:
- Ethernet cable failure
- Switch failure
- Publisher power failure
- Subscriber communication failure
- Incorrect VLAN configuration
- Network congestion
- Configuration mismatch
- Firmware or configuration problems
17.1 Communication Supervision
A subscriber should be engineered to recognize invalid or stale communication according to the supported IEC 61850 implementation.
The system must define how the subscriber behaves when the expected GOOSE information is no longer valid.
17.2 Fail-Safe and Fail-Secure Design
The appropriate response depends on the protection application.
For example:
- A blocking signal may require a carefully designed backup time delay if communication fails.
- A trip signal may require a different failure response.
- An interlocking application may need to prevent unsafe operation when status information is unavailable.
There is no universal failure response suitable for every GOOSE application.
17.3 Required Tests
Test at least:
- Normal GOOSE communication.
- Publisher power loss.
- Ethernet cable disconnection.
- Switch communication failure, where practical.
- Incorrect or invalid subscriber configuration.
- Communication restoration.
- Recovery of application logic.
- Alarm and event recording.
18. GOOSE Redundancy and Network Architecture
Protection communication networks should be designed according to the required availability and performance.
Possible network arrangements include:
- Single Ethernet network
- Redundant Ethernet networks
- PRP
- HSR
18.1 PRP
Parallel Redundancy Protocol provides two independent network paths.
Compatible devices can transmit duplicate frames over the two networks.
The receiving device accepts the first valid frame, allowing communication to continue during certain network failures.
18.2 HSR
High-availability Seamless Redundancy is a ring-based redundancy approach.
Frames are transmitted through the ring in both directions.
The devices and network components must support the required HSR architecture.
18.3 GE Multilin Compatibility
Do not assume every GE Multilin relay supports PRP or HSR.
Verify:
- Relay communication hardware
- Firmware
- Supported redundancy protocol
- Switch compatibility
- System architecture
- Required network performance
Redundancy must be tested as part of commissioning.
19. GOOSE Commissioning and End-to-End Testing
A successful GOOSE commissioning test must verify the complete signal path.
19.1 Publisher Testing
Verify:
- Correct source signal
- Correct dataset
- Correct GOOSE control block
- Correct APPID
- Correct multicast address
- Correct VLAN
- Correct state change
- Correct retransmission behaviour
19.2 Subscriber Testing
Verify:
- Correct publisher reference
- Correct dataset mapping
- Correct data interpretation
- Correct quality handling
- Correct communication supervision
- Correct internal logic
- Correct output operation
19.3 End-to-End Testing
An end-to-end test should confirm:
- The source relay receives the test condition.
- The protection or control signal changes state.
- The publisher transmits the GOOSE message.
- The network delivers the message.
- The subscriber receives the information.
- The subscriber logic operates correctly.
- The intended output or control action occurs.
- The event records and timestamps are correct.
19.4 Testing Safety
Before testing any trip or blocking application:
- Obtain the required work permit.
- Review the approved test procedure.
- Isolate unintended trip paths where necessary.
- Confirm the protection system’s operational status.
- Coordinate with the control room.
- Restore all trip and blocking circuits after testing.
- Independently verify the final system condition.
Never conduct uncontrolled GOOSE trip testing on an energized substation.
20. GOOSE Test Matrix
The following matrix provides an example of a commissioning test structure.
| Test | Test condition | Expected result |
|---|---|---|
| Publisher normal state | No protection operation | Correct normal-state message |
| Publisher event | Protection signal activated | New GOOSE state transmitted |
| Subscriber reception | Valid message received | Correct data indication |
| Logic operation | Required input condition applied | Intended logic response |
| Trip output | Approved trip test condition | Correct output response |
| Communication loss | Publisher or network disconnected | Defined failure response |
| Communication recovery | Network restored | Valid communication re-established |
| Configuration mismatch | Controlled mismatch test | Appropriate supervision or failure indication |
| Event recording | Signal changes state | Correct event and timestamp |
| Redundancy | One approved network path interrupted | Required communication continuity, where supported |
21. Common GOOSE Engineering Mistakes
Mistake 1: Assuming All Relays Support GOOSE
IEC 61850 support does not automatically mean that every GOOSE service is supported.
Recommendation: Verify the exact relay implementation and firmware.
Mistake 2: Incorrect Dataset Selection
The publisher may transmit information that does not correspond to the subscriber’s expected application.
Recommendation: Review the dataset and its data references.
Mistake 3: Incorrect APPID or Multicast Address
The subscriber may not identify the intended GOOSE application.
Recommendation: Compare publisher and subscriber configuration with the approved SCL project.
Mistake 4: VLAN Mismatch
The message may be blocked or isolated by the Ethernet network.
Recommendation: Verify VLAN configuration at all relevant switch ports.
Mistake 5: Incorrect Subscriber Mapping
The GOOSE message may arrive, but the wrong internal signal may be used.
Recommendation: Perform point-to-point signal verification.
Mistake 6: Ignoring Communication Failure
A protection scheme may operate incorrectly if the GOOSE signal becomes unavailable.
Recommendation: Define and test the communication-failure response.
Mistake 7: Testing Only the Ethernet Message
A visible packet does not prove that the protection application works.
Recommendation: Complete end-to-end functional testing.
Mistake 8: Failing to Update Configuration Revisions
The publisher and subscriber may use inconsistent configuration information.
Recommendation: Manage SCL revisions and configuration downloads under a controlled procedure.
22. Practical GOOSE Commissioning Checklist
Relay verification
- GE Multilin model confirmed
- Firmware version recorded
- IEC 61850 support confirmed
- GOOSE publisher capability verified
- GOOSE subscriber capability verified
- Required data objects available
Publisher configuration
- Dataset created
- Required data attributes selected
- GOOSE Control Block configured
- GOOSE identifier checked
- APPID checked
- Multicast MAC checked
- VLAN and priority checked
- Configuration revision recorded
Subscriber configuration
- Correct publisher identified
- Dataset mapping verified
- Data quality checked
- Communication supervision configured
- Internal logic verified
- Output mapping verified
Network verification
- Ethernet connectivity checked
- Switch port configuration checked
- VLAN configuration checked
- Multicast handling checked
- Network loading reviewed
- Redundancy tested, where installed
Functional testing
- Normal-state message verified
- State-change message verified
- Subscriber reception verified
- Internal logic tested
- Trip or blocking operation tested
- Communication failure tested
- Communication recovery tested
- Event recording checked
Documentation
- Final SCL files archived
- GOOSE matrix updated
- Relay configurations backed up
- Network configuration archived
- Test reports completed
- As-built documentation updated
23. Training on GE Multilin GOOSE Communication by Elec-Engg
GOOSE communication is a practical engineering subject that requires an understanding of protection functions, IEC 61850 data modelling, Ethernet communication and system commissioning.
Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for engineers working in power system protection, commissioning, operation, maintenance and substation automation.
Relevant training subjects include:
- IEC 61850 fundamentals
- GE Multilin IEC 61850 communication
- GOOSE publisher and subscriber configuration
- GOOSE datasets and control blocks
- Logical nodes and data objects
- APPID, multicast MAC and VLAN engineering
- Protection blocking schemes
- GOOSE-based interlocking
- Breaker failure signal exchange
- Busbar trip distribution
- SCL file engineering
- ICD, CID, IID and SCD files
- Integration with Siemens SICAM PAS
- IEDScout practical exercises
- Wireshark GOOSE packet analysis
- Communication failure supervision
- GOOSE commissioning and end-to-end testing
Training delivery options include:
- Pre-recorded video courses
- Structured self-paced training
- Live online technical training
- Face-to-face training
- Customized in-house training for utilities and industrial companies
The objective is to help engineers understand not only how GOOSE messages are configured, but also how they are applied in practical protection and substation automation schemes.
Visit Elec-Engg for technical training resources:
For customized training and technical enquiries:
24. Conclusion
GOOSE communication is a key technology in IEC 61850-based substation automation. It enables protection and control IEDs to exchange event information over Ethernet and supports applications such as protection blocking, interlocking, breaker failure coordination and trip distribution.
For GE Multilin relays, successful GOOSE engineering requires verification of the exact relay capabilities, correct dataset and control-block configuration, subscriber mapping, multicast communication, VLAN settings and application logic.
The most important commissioning principle is to test the complete communication and protection chain. Engineers must verify the publisher, Ethernet network, subscriber, internal logic and final output response.
A properly engineered and tested GOOSE application can improve substation integration and reduce wiring complexity while maintaining the required protection performance and system reliability.
25. Frequently Asked Questions
1. What is GOOSE communication in GE Multilin relays?
GOOSE is an IEC 61850 communication service that allows supported GE Multilin relays to exchange event information with other IEDs over Ethernet.
2. What is the difference between a GOOSE publisher and subscriber?
The publisher transmits the configured information. The subscriber receives that information and uses it in its configured application logic.
3. Can GE Multilin relays exchange trip signals using GOOSE?
Some supported relay configurations can exchange protection-related information using GOOSE. Whether a particular trip application is supported depends on the relay model, firmware, communication capabilities and approved protection design.
4. What is a GOOSE dataset?
A dataset is a collection of IEC 61850 data attributes selected for transmission through a GOOSE Control Block.
5. What is a GOOSE Control Block?
A GOOSE Control Block defines the publishing configuration associated with a dataset, including relevant communication parameters.
6. What are APPID and VLAN in GOOSE communication?
APPID identifies the GOOSE application, while VLAN configuration helps organize and separate Ethernet traffic.
7. Why are GOOSE messages retransmitted?
Repeated transmission improves the probability that subscribers receive the latest published state, even if individual Ethernet frames are lost.
8. Can GOOSE replace all hardwired signals?
No. GOOSE can replace selected signal connections where the protection design and project requirements permit it. Some hardwired circuits remain necessary.
9. How can GOOSE communication be tested?
Use suitable IEC 61850 engineering tools, network packet analysis and end-to-end functional tests to verify publisher transmission, subscriber reception and application operation.
10. Can Wireshark analyse GOOSE messages?
Yes. Wireshark can capture and inspect GOOSE Ethernet frames, including communication parameters and published information.
11. What happens if GOOSE communication fails?
The response depends on the subscriber implementation and protection design. Communication failure supervision and the resulting protection behaviour must be explicitly engineered and tested.
12. Where can I receive practical GE Multilin GOOSE training?
Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering). Visit https://elec-engg.com/ or contact https://elec-engg.com/contact/.
Learn GE Multilin GOOSE communication, including publisher and subscriber configuration, datasets, APPID, VLAN, protection blocking, SCL engineering and commissioning tests.
GE Multilin GOOSE, GE GOOSE Communication, IEC 61850 GOOSE, GOOSE Publisher, GOOSE Subscriber, GOOSE Control Block, GOOSE Dataset, GOOSE Configuration, GOOSE Testing, GOOSE Troubleshooting, GOOSE Interlocking, Protection Blocking, Breaker Failure Protection, Busbar Protection, APPID, VLAN, Multicast MAC Address, IEC 61850 SCL, GE Multilin Relay, Substation Automation, IEDScout, Wireshark, SICAM PAS, Protection Relay Communication, Relay Testing and Commissioning