- 1. Introduction
- 2. Cybersecurity in Digital Substations
- 3. Understanding IEC 61850 and Cybersecurity
- 4. IEC 62351 and Its Role in Substation Cybersecurity
- 5. Network Segmentation for GE Multilin Protection Relays
- 6. User Accounts and Access Control
- 7. Protecting Relay Settings and Configuration Files
- 8. Secure Engineering Access to GE Multilin Relays
- 9. GOOSE Cybersecurity Considerations
- 10. MMS Cybersecurity Considerations
- 11. Firmware and Software Management
- 12. Security Logging and Monitoring
- 13. Network Intrusion Detection and Monitoring
- 14. Cybersecurity Risk Assessment for a GE Multilin Installation
- 15. Practical Cybersecurity Commissioning Procedure
- 16. Example: Securing a GE Multilin Feeder Protection Relay
- 17. Cybersecurity Checklist for GE Multilin Protection Relays
- 18. Frequently Asked Questions
- Does IEC 61850 automatically provide cybersecurity?
- Does every GE Multilin relay support IEC 62351?
- Is MMS communication encrypted by default?
- Is GOOSE communication secure?
- Can a firewall protect a GOOSE network?
- Should protection relays be connected directly to the corporate network?
- How often should relay configurations be backed up?
- Can cybersecurity testing affect protection relay operation?
- 19. Training on GE Multilin IEC 61850 Cybersecurity by Elec-Engg
- 20. Conclusion
1. Introduction
Modern electrical substations increasingly depend on Ethernet-based communication between protection relays, bay controllers, station computers and SCADA systems. GE Multilin protection relays equipped with supported communication capabilities can participate in IEC 61850-based substation automation systems, exchanging measurements, protection indications, alarms and control information.
Although IEC 61850 improves interoperability and enables advanced substation automation, it also introduces cybersecurity considerations. Protection and control devices are connected through communication networks that must be protected against unauthorized access, configuration changes, malicious traffic and accidental operational errors.
A cybersecurity incident affecting a protection relay or its communication network can have consequences beyond the loss of monitoring. Depending on the architecture and protection scheme, it may affect remote control, interlocking, protection coordination, event reporting or engineering access.
This article explains practical cybersecurity considerations for GE Multilin protection relays and IEC 61850 substation networks. It covers network segmentation, access control, secure engineering access, protocol security, monitoring, configuration management and commissioning checks.
Important: Cybersecurity features vary significantly across GE Multilin relay families, hardware platforms, firmware versions and communication modules. Do not assume that a relay supports every security feature discussed here. Verify the exact capabilities and limitations in the applicable manufacturer’s documentation.
2. Cybersecurity in Digital Substations
A digital substation contains several interconnected systems:
- Protection and control IEDs.
- Bay control units.
- Station controllers.
- SCADA servers.
- Engineering workstations.
- Human-machine interfaces.
- Ethernet switches.
- Time synchronization equipment.
- Remote access gateways.
- Network monitoring systems.
Each component can introduce cybersecurity risks if it is incorrectly configured, inadequately protected or connected to an untrusted network.
2.1 Why Protection Relays Need Cybersecurity
Protection relays are operational technology devices. Their primary responsibility is to detect abnormal power system conditions and initiate appropriate protection actions.
Cybersecurity must therefore preserve three important properties:
Availability: Protection and control functions must remain available when required.
Integrity: Protection settings, logic, measurements and communication data must not be modified without authorization.
Confidentiality: Sensitive engineering information, credentials and operational information must be protected against unauthorized disclosure.
In protection systems, availability and integrity are particularly important because communication interruptions or unauthorized configuration changes may affect the operation of electrical equipment.
2.2 Typical Cybersecurity Threats
Potential threats include:
- Unauthorized engineering access.
- Compromised engineering workstations.
- Weak or shared passwords.
- Uncontrolled remote connections.
- Malware introduced through removable media.
- Unauthorized relay setting modifications.
- Network reconnaissance.
- Denial-of-service attacks.
- Unauthorized MMS client connections.
- Misuse of control services.
- Unauthorized GOOSE configuration changes.
- Exposure of engineering files and configuration backups.
Not every threat can be prevented by the relay itself. Cybersecurity must be implemented across the complete substation architecture.
3. Understanding IEC 61850 and Cybersecurity
IEC 61850 defines communication and engineering models for substation automation. It does not mean that every communication service is automatically secure.
Important IEC 61850 communication services include:
- MMS client-server communication.
- GOOSE event communication.
- Sampled Values, where implemented.
- Engineering access and SCL configuration.
- Time synchronization.
Each service has different communication characteristics and security considerations.
3.1 MMS Communication
MMS is commonly used for:
- Monitoring relay measurements.
- Reading protection indications.
- Receiving event reports.
- Accessing device information.
- Executing supported control operations.
A cybersecurity assessment should consider:
- Which clients are permitted to connect.
- Whether access restrictions are implemented.
- Whether authentication is available.
- Whether the network path is protected.
- Whether control operations are appropriately restricted.
- Whether communication activity is monitored.
Traditional MMS communication over TCP/IP should not automatically be assumed to provide encryption or strong authentication.
3.2 GOOSE Communication
GOOSE provides fast Ethernet-based event messaging between IEDs.
Typical applications include:
- Protection blocking.
- Breaker failure signals.
- Interlocking.
- Trip distribution.
- Transfer trip.
- Busbar protection communication.
Because GOOSE is often used for protection-related functions, unauthorized or malformed messages can present a significant operational risk.
Security considerations include:
- Restricting access to the relevant Ethernet network.
- Controlling switch-port access.
- Managing multicast traffic.
- Protecting engineering configurations.
- Monitoring unexpected GOOSE publishers.
- Verifying publisher and subscriber configurations.
- Implementing supported message authentication mechanisms where required and available.
Do not assume that every GE Multilin relay supports IEC 62351-based GOOSE security or that every GOOSE implementation provides message authentication by default.
3.3 SCL File Security
SCL files can contain important information about the substation communication architecture.
Examples include:
- IED names.
- Logical device structures.
- Communication parameters.
- IP addresses.
- Datasets.
- Report control blocks.
- GOOSE control blocks.
- External references.
Unauthorized modification of an SCD or device-specific configuration can affect communication between IEDs.
SCL files should therefore be managed as controlled engineering assets.
4. IEC 62351 and Its Role in Substation Cybersecurity
IEC 62351 is a family of standards addressing cybersecurity for power system information exchange.
Its scope includes security considerations for communication protocols and power system information systems.
Relevant parts of the IEC 62351 family address topics such as:
- Security architecture.
- Authentication.
- Role-based access control.
- Security for MMS-based communication.
- Security for GOOSE and Sampled Values.
- Network and system management.
- Security event logging.
The applicable requirements depend on the selected IEC 62351 part, edition, implementation profile and equipment capabilities.
4.1 IEC 62351-3
IEC 62351-3 addresses security for protocols based on TCP/IP, including the use of transport-layer security mechanisms in applicable profiles.
For an IEC 61850 station-bus architecture, secure transport can help protect supported client-server communication.
However, the availability of TLS in a GE Multilin relay must be confirmed for the exact product and firmware.
4.2 IEC 62351-4
IEC 62351-4 addresses security for profiles used with MMS-based communication.
It is relevant when assessing secure client-server communication between IEDs and station-level systems.
Engineers should verify the supported security mechanisms and interoperability requirements of both communicating devices.
4.3 IEC 62351-6
IEC 62351-6 addresses security for IEC 61850-based communication protocols.
It is relevant to the security of GOOSE and Sampled Values communication where the applicable mechanisms are implemented.
Do not assume that a relay supports secure GOOSE simply because it supports conventional GOOSE communication.
4.4 IEC 62351-8
IEC 62351-8 addresses role-based access control for power system management.
Role-based access control can help ensure that users receive only the permissions needed for their responsibilities.
For example:
- An operator may need monitoring and approved control permissions.
- A protection engineer may need access to relay settings.
- A system administrator may manage accounts and security policies.
- A commissioning engineer may require temporary engineering privileges.
The actual roles and available permissions depend on the device and system implementation.
5. Network Segmentation for GE Multilin Protection Relays
Network segmentation is one of the most important cybersecurity measures in a substation.
The objective is to separate systems according to their operational functions and security requirements.
5.1 Typical Substation Network Zones
A simplified architecture may contain:
Protection and control zone
- GE Multilin protection relays.
- Other protection IEDs.
- Bay controllers.
Station automation zone
- Station controllers.
- SCADA servers.
- HMI systems.
- IEC 61850 communication gateways.
Engineering zone
- Engineering workstations.
- Relay configuration software.
- SCL engineering tools.
- Diagnostic computers.
Enterprise or external network zone
- Corporate IT systems.
- Remote support infrastructure.
- Approved external connections.
The architecture should prevent unnecessary direct communication between these zones.
5.2 VLAN Configuration
VLANs can be used to separate communication traffic at Layer 2.
For example:
| VLAN | Example function |
|---|---|
| VLAN 10 | Protection IED communication |
| VLAN 20 | Station SCADA communication |
| VLAN 30 | Engineering access |
| VLAN 40 | Network management |
These are illustrative values only.
VLAN separation is not a complete security boundary by itself. Additional access controls, firewall policies and network monitoring may be required.
5.3 Firewall Configuration
Firewalls can restrict communication between network zones.
For example, a firewall policy may permit an authorized engineering workstation to access a defined set of relay services while blocking unnecessary traffic from other networks.
A firewall rule should specify:
- Source network or host.
- Destination network or host.
- Protocol.
- Destination port, where applicable.
- Direction.
- Business or operational justification.
- Rule owner.
- Review date.
Avoid broad rules that permit unrestricted communication between corporate and substation networks.
5.4 Important Network Ports
Commonly relevant communication services include:
| Service | Typical port or transport | Purpose |
|---|---|---|
| MMS | TCP 102 | IEC 61850 client-server communication |
| SNTP/NTP | UDP 123 | Time synchronization |
| SSH | TCP 22 | Secure remote administration, if supported |
| HTTPS | TCP 443 | Secure web access, if supported |
| Syslog | UDP/TCP 514 or secure alternatives | Event logging, depending on implementation |
These are common service assignments, not a statement that every GE Multilin relay exposes them.
The actual port requirements must be obtained from the device documentation and the approved network design.
6. User Accounts and Access Control
Unauthorized access to protection relay settings is a serious operational risk.
Where the relay supports account management and role-based permissions, implement an access-control policy.
6.1 User Roles
A typical policy may define:
| Role | Typical responsibility |
|---|---|
| Operator | Monitoring and authorized operational control |
| Protection engineer | Protection settings and engineering |
| Commissioning engineer | Testing and temporary commissioning access |
| Administrator | Account and security administration |
| Auditor | Read-only access to approved records |
The actual roles available on a GE Multilin device may differ.
6.2 Password Management
Good password practices include:
- Use unique credentials.
- Avoid shared engineering accounts where individual accounts are supported.
- Avoid default credentials.
- Use sufficiently strong passwords.
- Store credentials securely.
- Change credentials according to the organization’s policy.
- Remove or disable accounts that are no longer required.
- Avoid including passwords in configuration documents.
Do not assume that all GE Multilin relays support the same password policy or centralized authentication mechanism.
6.3 Least-Privilege Principle
Users should receive only the permissions needed for their assigned tasks.
For example, an operator who only needs to monitor relay measurements should not automatically receive permission to modify protection settings.
This reduces the risk of accidental or unauthorized changes.
7. Protecting Relay Settings and Configuration Files
Protection settings are critical engineering information.
An unauthorized change to a differential setting, distance protection characteristic or overcurrent coordination parameter can affect protection performance.
7.1 Configuration Backup
Maintain controlled backups of:
- Relay settings.
- Relay logic configurations.
- Communication parameters.
- SCL files.
- Firmware information.
- Device configuration reports.
- Commissioning test records.
Each backup should be associated with:
- IED name.
- Relay model.
- Serial number or approved equipment identifier.
- Firmware version.
- Configuration revision.
- Date of backup.
- Engineer responsible.
- Approval status.
7.2 Configuration Integrity
Where suitable tools are available, use file checksums or cryptographic hashes to detect unintended changes.
For example, a SHA-256 hash can be calculated for a configuration file using an approved workstation tool.
Example command:
sha256sum relay_configuration.cid
The resulting hash can be recorded alongside the approved configuration revision.
A matching hash helps confirm that two files are identical at the byte level. It does not prove that the configuration is correct or safe.
7.3 Change Management
Every protection or communication configuration change should follow an approved process.
A controlled change procedure should include:
- Change request.
- Technical justification.
- Risk assessment.
- Configuration backup.
- Review and approval.
- Implementation.
- Functional testing.
- Independent verification.
- Updated documentation.
- Final configuration archive.
This process is particularly important for GOOSE mappings and protection-related interlocking signals.
8. Secure Engineering Access to GE Multilin Relays
Engineering workstations are an important cybersecurity consideration because they may have access to relay settings, logic and communication configurations.
8.1 Engineering Workstation Hardening
Recommended measures include:
- Use dedicated engineering workstations where practical.
- Apply approved operating system security updates.
- Restrict administrator privileges.
- Use endpoint protection approved for the operational environment.
- Control removable media.
- Maintain approved engineering software versions.
- Avoid unnecessary internet access.
- Use secure credential storage.
- Maintain workstation backups.
- Record engineering activities.
Security controls must be tested for compatibility with the relay configuration software. An endpoint security product should not be allowed to interrupt a critical engineering or commissioning activity unexpectedly.
8.2 Removable Media Control
USB devices can introduce malware or transfer unauthorized configuration files.
A controlled removable-media procedure should include:
- Authorize the media.
- Scan it using an approved process.
- Verify the file source.
- Check configuration revision and integrity.
- Transfer only the required files.
- Record the transfer.
- Store or sanitize the media according to organizational policy.
8.3 Remote Engineering Access
Remote access can be useful for maintenance and technical support, but it introduces additional security risks.
Recommended controls include:
- Use an approved remote-access gateway.
- Require strong authentication.
- Use encrypted connections.
- Restrict access to authorized personnel.
- Use time-limited access where possible.
- Record remote sessions.
- Disable access when the work is complete.
- Avoid direct exposure of relay interfaces to public networks.
A remote support connection should never bypass the organization’s operational authorization and cybersecurity policies.
9. GOOSE Cybersecurity Considerations
GOOSE communication can carry critical protection and control signals.
Examples include:
- Blocking signals.
- Trip indications.
- Breaker failure signals.
- Busbar interlocking.
- Transfer trip signals.
9.1 Risks Associated with GOOSE
Potential risks include:
- Unauthorized message injection.
- Unexpected GOOSE publishers.
- Incorrect subscriber configuration.
- Malicious or accidental configuration changes.
- Network flooding.
- Multicast traffic manipulation.
- Denial of service.
9.2 Practical GOOSE Security Measures
Implement appropriate controls such as:
- Restrict physical access to network switches.
- Limit switch-port access.
- Use VLANs according to the network design.
- Restrict multicast traffic where appropriate.
- Monitor expected publisher identities and traffic.
- Maintain approved GOOSE configuration matrices.
- Protect SCL files and relay configuration backups.
- Verify subscriber mappings during commissioning.
- Investigate unexpected GOOSE traffic.
Where supported and required, consider applicable IEC 62351 security mechanisms for GOOSE communication.
9.3 GOOSE Monitoring
A network monitoring system or engineering diagnostic tool can help identify:
- Unexpected GOOSE source MAC addresses.
- Unexpected APPIDs.
- Unknown publishers.
- Unusual traffic volume.
- Missing expected messages.
- Unexpected communication interruptions.
Monitoring should be designed to avoid adding unacceptable traffic or load to the protection network.
10. MMS Cybersecurity Considerations
MMS provides access to data and, depending on implementation, control services.
An MMS client may read measurements and status information or execute supported control operations.
10.1 Restrict MMS Clients
Maintain an approved list of MMS clients.
Examples include:
- Station SCADA server.
- Approved engineering workstation.
- Authorized diagnostic computer.
- Approved gateway.
Avoid allowing every computer on the network to connect to every protection relay.
10.2 Protect Control Operations
Where MMS control services are available, verify:
- Which clients can issue commands.
- Which control models are supported.
- Whether select-before-operate is required.
- Whether direct operate is permitted.
- Whether command origin and authorization are checked.
- Whether command execution is logged.
- Whether interlocking remains effective.
Control access must follow the operational design and authorization policy.
10.3 Secure Transport
Where supported by both communicating systems, use appropriate secure transport mechanisms.
Verify:
- TLS support.
- Supported protocol versions.
- Certificate requirements.
- Certificate validation.
- Trusted certificate authorities.
- Certificate expiration.
- Key management.
- Compatibility between client and server.
Do not assume that enabling TLS in a SCADA system automatically secures communication with every relay.
11. Firmware and Software Management
Firmware updates can address defects, improve functionality or introduce security fixes.
However, updating protection relay firmware requires careful engineering assessment.
11.1 Firmware Management Checklist
Before an update:
- Confirm the exact relay model.
- Check hardware compatibility.
- Verify the approved firmware package.
- Review manufacturer release notes.
- Identify security-related changes.
- Check configuration compatibility.
- Back up existing settings and logic.
- Assess operational risk.
- Obtain approval.
- Prepare a rollback or recovery plan where supported.
After an update:
- Verify the firmware version.
- Check the relay health status.
- Review protection settings.
- Verify communication configuration.
- Test MMS services.
- Test GOOSE services where applicable.
- Verify time synchronization.
- Perform required functional tests.
- Archive the final configuration.
11.2 Engineering Software Updates
Relay configuration software and SCL tools should also be managed carefully.
An updated engineering tool may change file handling, device descriptions or configuration compatibility.
Before changing software versions, confirm that the new version supports the installed relay firmware and project files.
12. Security Logging and Monitoring
Logging helps engineers identify abnormal activity and investigate cybersecurity incidents.
Relevant records may include:
- User login events.
- Failed login attempts.
- Configuration changes.
- Relay setting changes.
- Firmware updates.
- Communication interruptions.
- Device restart events.
- Remote access activity.
- Security alarms.
- Network switch events.
The available logging capabilities depend on the relay model and the surrounding system architecture.
12.1 Centralized Logging
Where supported, relevant logs can be collected by a centralized monitoring or security information and event management system.
The monitoring architecture should consider:
- Device log capabilities.
- Supported log protocols.
- Network traffic restrictions.
- Timestamp accuracy.
- Storage and retention.
- Access permissions.
- Alarm escalation.
Do not assume that a GE Multilin relay supports a particular centralized logging protocol without checking its documentation.
12.2 Monitoring Important Events
Examples of events that may deserve investigation include:
- Repeated failed authentication attempts.
- Unexpected engineering connections.
- Unapproved setting changes.
- Unexpected device restarts.
- New or unknown network devices.
- Unusual GOOSE traffic.
- Unexpected MMS connections.
- Loss of time synchronization.
A single event does not necessarily indicate an attack. It should be assessed against the operational context and other available evidence.
13. Network Intrusion Detection and Monitoring
Intrusion detection can provide additional visibility into substation communication.
A monitoring system may analyze network traffic to identify unusual patterns.
13.1 Passive Monitoring
Passive monitoring is often preferable in protection networks because it observes traffic without actively interacting with the IEDs.
Possible monitoring sources include:
- Switch mirror ports.
- Network TAPs.
- Dedicated monitoring interfaces.
- Security monitoring appliances.
13.2 What Should Be Monitored?
A monitoring policy may include:
- Expected IED IP addresses.
- Approved MAC addresses.
- Expected MMS communication partners.
- Expected GOOSE publishers.
- Known multicast groups.
- Communication volume.
- Unusual connection attempts.
- Unexpected engineering access.
13.3 Avoid Active Scanning Without Approval
Aggressive network scanning can introduce unnecessary traffic or interact unpredictably with operational devices.
Before conducting vulnerability scans or penetration tests:
- Obtain written authorization.
- Define the scope.
- Assess operational risk.
- Use a controlled test environment where possible.
- Coordinate with protection and control personnel.
- Follow the organization’s OT testing procedure.
Do not perform intrusive security testing on an operational protection network without explicit approval.
14. Cybersecurity Risk Assessment for a GE Multilin Installation
A practical risk assessment should consider the likelihood and consequences of cybersecurity events.
Example:
| Asset | Potential threat | Possible consequence | Example control |
|---|---|---|---|
| Protection relay | Unauthorized setting modification | Incorrect protection response | Access control and change management |
| Engineering workstation | Malware infection | Compromised configuration files | Workstation hardening |
| Station network | Unauthorized access | Exposure of operational data | Segmentation and firewall rules |
| GOOSE network | Unauthorized message injection | Incorrect interlocking or protection signalling | Network controls and monitoring |
| SCADA server | Compromised credentials | Unauthorized monitoring or control | Strong authentication |
| SCL files | Unauthorized modification | Incorrect communication configuration | Version control and integrity checking |
| Time source | Incorrect synchronization | Misleading event sequence | Time-source monitoring |
The assessment should identify critical assets, attack paths, existing controls and residual risks.
A generic table is not a substitute for a site-specific cybersecurity risk assessment.
15. Practical Cybersecurity Commissioning Procedure
Cybersecurity should be included in the commissioning plan rather than postponed until after the substation is operational.
Stage 1 – Asset Identification
Record:
- Relay model.
- Serial number or asset identifier.
- Firmware version.
- Ethernet interfaces.
- Communication services.
- Engineering software version.
- Network location.
Stage 2 – Network Review
Verify:
- Network segmentation.
- VLAN configuration.
- Firewall rules.
- IP address allocation.
- Switch access controls.
- Remote access architecture.
- Network management arrangements.
Stage 3 – Access Control Review
Check:
- Default credentials have been addressed.
- User accounts are approved.
- Permissions match assigned roles.
- Unnecessary accounts are disabled.
- Engineering access is controlled.
- Remote access is authorized.
Stage 4 – Configuration Integrity
Verify:
- Approved relay settings are installed.
- Approved logic configuration is installed.
- SCL files match the approved project revision.
- GOOSE publisher and subscriber mappings are correct.
- Configuration backups are available.
- Changes are recorded.
Stage 5 – Communication Security Review
Check the supported security features of the installed equipment.
Where applicable, verify:
- Secure communication configuration.
- Certificate validity.
- Authentication.
- Access restrictions.
- Network monitoring.
- Logging.
Stage 6 – Functional Verification
Confirm that cybersecurity measures have not unintentionally affected:
- MMS monitoring.
- GOOSE communication.
- Protection interlocking.
- SCADA reporting.
- Time synchronization.
- Engineering access.
- Required remote support functions.
Stage 7 – Documentation
Archive:
- Asset inventory.
- Network architecture.
- Access-control matrix.
- Firewall rule register.
- Configuration backups.
- Firmware register.
- Security test results.
- Approved exceptions.
- Final commissioning report.
16. Example: Securing a GE Multilin Feeder Protection Relay
Consider a feeder protection relay connected to an IEC 61850 station bus.
The relay provides:
- Protection functions.
- Measurement data.
- Breaker status.
- MMS reporting.
- GOOSE communication with another protection IED.
- Engineering access through an approved workstation.
A practical security design may include the following measures.
Network design
Place the protection relay within the designated protection network.
Restrict communication from other network zones through approved network controls.
MMS access
Allow only the approved SCADA server and authorized engineering clients to access the required MMS services.
GOOSE communication
Restrict access to the relevant communication network and verify the expected publisher and subscriber relationships.
Engineering access
Use an authorized engineering workstation and individual user credentials where supported.
Configuration management
Maintain an approved backup of the relay settings, logic and communication configuration.
Monitoring
Record important communication and configuration events using available device and network monitoring facilities.
Commissioning
Test MMS, GOOSE, protection logic and required access paths after implementing the security controls.
The final objective is to improve cybersecurity without compromising protection availability or operational performance.
17. Cybersecurity Checklist for GE Multilin Protection Relays
Asset and firmware management
- Relay model and hardware identified.
- Firmware version recorded.
- Supported security features documented.
- Engineering software version recorded.
- Firmware update process approved.
Network security
- Network architecture documented.
- Protection and engineering networks appropriately separated.
- VLAN configuration reviewed.
- Firewall rules documented.
- Unnecessary network services restricted.
- Switch access controlled.
- Remote access secured.
User access
- Default credentials addressed.
- Authorized users identified.
- Permissions reviewed.
- Shared accounts avoided where individual accounts are supported.
- Unnecessary accounts disabled.
- Engineering access recorded.
Configuration integrity
- Relay settings backed up.
- Logic configuration backed up.
- SCL files archived.
- Configuration revisions recorded.
- Changes approved.
- Final configuration verified.
IEC 61850 security
- MMS client access reviewed.
- GOOSE publisher and subscriber relationships verified.
- Network multicast controls reviewed.
- Supported secure communication mechanisms assessed.
- Time synchronization monitored.
- Communication diagnostics available.
Monitoring and response
- Relevant event logs reviewed.
- Network monitoring considered.
- Security incident procedure available.
- Backup restoration procedure documented.
- Cybersecurity responsibilities assigned.
18. Frequently Asked Questions
Does IEC 61850 automatically provide cybersecurity?
No. IEC 61850 defines communication and engineering services. Additional security measures and applicable IEC 62351 mechanisms are required to protect communication and access.
Does every GE Multilin relay support IEC 62351?
No. Support depends on the relay model, hardware, firmware and implementation. Verify the applicable manufacturer’s documentation.
Is MMS communication encrypted by default?
Do not assume that conventional MMS communication is encrypted. Secure transport capabilities depend on the device and communication implementation.
Is GOOSE communication secure?
GOOSE is designed for fast event-driven Ethernet communication. Its security depends on the implementation and network architecture. Network controls and supported IEC 62351 mechanisms should be considered where applicable.
Can a firewall protect a GOOSE network?
A firewall can contribute to network security, but it must be designed for the actual communication architecture and performance requirements. Incorrect filtering can interrupt protection-related communication.
Should protection relays be connected directly to the corporate network?
Direct connections should generally be avoided unless explicitly justified and protected by an approved OT network architecture. Segmentation and controlled access are important.
How often should relay configurations be backed up?
Follow the organization’s maintenance and change-management policy. Backups should be made before and after approved configuration changes, and periodically according to operational requirements.
Can cybersecurity testing affect protection relay operation?
Yes. Intrusive scanning, incorrect firewall rules, configuration changes or poorly controlled testing may affect communication or device performance. All testing should be authorized and risk-assessed.
19. Training on GE Multilin IEC 61850 Cybersecurity by Elec-Engg
Protection engineers need to understand both relay operation and the cybersecurity controls surrounding modern substation automation systems.
Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering).
Relevant training subjects include:
- GE Multilin protection relay engineering.
- IEC 61850 communication architecture.
- MMS and GOOSE communication.
- SCL configuration and file management.
- IEC 62351 cybersecurity concepts.
- Substation network segmentation.
- Ethernet, VLAN and multicast engineering.
- IED access control and configuration management.
- IEDScout and Wireshark diagnostics.
- Cybersecurity considerations during relay commissioning.
- Integration with Siemens SICAM PAS and other compatible SCADA systems.
Training delivery options include:
- Pre-recorded video courses.
- Structured self-paced training.
- Live online training.
- Face-to-face training.
- Customized in-house training for utilities, EPC contractors and industrial organizations.
Explore the technical training programs:
Website: https://elec-engg.com/
Contact: https://elec-engg.com/contact/
20. Conclusion
Cybersecurity is an essential engineering consideration in modern IEC 61850 substations. GE Multilin protection relays must be integrated into a secure operational technology environment that protects configuration integrity, restricts unauthorized access and maintains the availability of protection and control functions.
Effective cybersecurity requires coordinated measures across relay configuration, network architecture, engineering workstations, user access, remote connections, communication monitoring and change management.
IEC 62351 provides important security mechanisms for applicable power system communication protocols, but the actual capabilities of each relay must be verified.
The most important principle is to protect the complete protection and automation system rather than relying on a single security feature or device.
GE Multilin, IEC 61850, IEC 62351, Cybersecurity, Protection Relay Security, Substation Cybersecurity, GOOSE Security, MMS Security, OT Security, Network Segmentation, Access Control, Digital Substation, SCADA Security, Relay Configuration Management, Substation Automation