GE Multilin Reverse Power Protection (ANSI 32): Generator Motoring, Directional Power Measurement, Pickup Settings, Time Delays and Testing

Table Of Contents
  1. 1. Introduction
  2. 2. What Is Reverse Power Protection?
  3. 3. Why Does Generator Motoring Occur?
  4. 4. Generator Motoring in Different Power Plants
  5. 5. Principle of Active Power Measurement
  6. 6. Directional Power Measurement
  7. 7. Reverse Power Protection Operating Principle
  8. 8. Reverse Power Protection Settings
  9. 9. Reverse Power Time Delay
  10. 10. Practical Reverse Power Calculation
  11. 11. Reverse Power Protection and Generator Shutdown
  12. 12. Reverse Power Protection and Other Generator Protection Functions
  13. 13. Reverse Power Protection and Low Forward Power
  14. 14. CT and VT Configuration for ANSI 32
  15. 15. GE Multilin Relay Applications
  16. 16. General GE Multilin Configuration Workflow
  17. 17. Reverse Power Protection Testing and Commissioning
  18. 18. Common Reverse Power Protection Problems
  19. 19. Reverse Power Protection Commissioning Checklist
  20. 20. Best Engineering Practices
  21. 21. Training on GE Multilin Protection Relays by Elec-Engg
  22. 22. Frequently Asked Questions
  23. Conclusion

1. Introduction

Reverse power protection is an important function in synchronous generator protection schemes. It detects the condition in which a generator begins absorbing active power from the electrical network instead of supplying power to it.

This condition is commonly known as generator motoring.

During normal operation, a generator converts mechanical energy supplied by a turbine or prime mover into electrical energy. The generator delivers active power to the connected network.

If the mechanical input is lost or becomes insufficient while the generator remains connected to the grid, the machine may continue operating as a synchronous motor. It then draws active power from the network to drive the turbine or prime mover.

Depending on the type of prime mover, this condition can cause serious mechanical problems.

ANSI device number 32 is associated with directional power protection. Reverse power protection uses this principle to identify active power flowing in the undesired direction.

GE Multilin generator protection relays, including selected G60, G30, and 889 applications, may provide reverse power protection. Function availability and implementation depend on the exact relay model and firmware.

This article explains reverse power principles, generator motoring, directional power measurement, practical calculations, settings, GE Multilin configuration, testing, and troubleshooting.

2. What Is Reverse Power Protection?

Reverse power protection monitors the direction of active power flowing through the generator connection.

Under normal generator operation:

[
P>0
]

when the selected sign convention defines power exported from the generator as positive.

During motoring:

[
P<0
]

The relay detects this reverse active-power condition and initiates an alarm or trip after the configured delay.

The actual positive and negative sign conventions depend on the relay’s measurement configuration. The engineer must verify the relay’s power direction indication before enabling the trip function.

Normal generator operation

  • Mechanical power enters the generator shaft.
  • The generator converts mechanical energy into electrical energy.
  • Active power flows from the generator to the network.
  • The generator operates as a source of electrical power.

Generator motoring

  • Mechanical input decreases or is lost.
  • The generator remains synchronized with the network.
  • Active power flows from the network into the generator.
  • The generator operates as a synchronous motor.
  • The prime mover may be driven by the electrical network.

Reverse power protection detects this abnormal operating condition.

3. Why Does Generator Motoring Occur?

Generator motoring generally occurs when the generator remains connected to an energized network after the mechanical input from its prime mover has been interrupted or significantly reduced.

Typical causes include:

  • Turbine steam supply failure.
  • Loss of fuel supply to a turbine.
  • Failure of a gas turbine fuel system.
  • Loss of hydraulic input to a hydro turbine.
  • Mechanical coupling problems.
  • Governor malfunction.
  • Incorrect shutdown sequence.
  • Prime mover trip without generator breaker opening.
  • Control-system or interlocking failure.

The exact consequences depend on the prime mover technology and operating condition.

4. Generator Motoring in Different Power Plants

The effects of motoring differ depending on the type of prime mover.

4.1 Steam turbine generators

When steam supply is interrupted while the generator remains connected to the network, the generator may begin drawing active power from the grid.

The synchronous generator then drives the steam turbine.

Possible consequences include:

  • Turbine blade ventilation losses.
  • Excessive heating.
  • Mechanical stress.
  • Abnormal operating conditions in the turbine.
  • Potential damage if the condition persists.

The permissible motoring time and power depend on the turbine manufacturer’s requirements.

4.2 Gas turbine generators

In gas turbine applications, loss of fuel or another prime mover trip condition may result in the generator absorbing power from the network.

The generator may drive the turbine and associated rotating equipment.

The consequences depend on the turbine design, auxiliary systems, and shutdown philosophy.

4.3 Hydroelectric generators

A hydroelectric generator may motor when hydraulic input is lost while the generator remains connected to the electrical network.

The resulting operation can cause abnormal hydraulic and mechanical conditions.

The protection scheme must be coordinated with the turbine and water-control system.

4.4 Diesel generator sets

A diesel generator connected in parallel with a network may motor if the engine stops producing sufficient mechanical power.

The electrical network can drive the generator and engine through the shaft.

The protection and shutdown arrangements should consider the engine manufacturer’s motoring restrictions.

5. Principle of Active Power Measurement

Reverse power protection is based on the measurement of active power.

For a balanced three-phase system:

[
P=\sqrt{3}V_LI_L\cos\varphi
]

Where:

  • (P) = three-phase active power.
  • (V_L) = line-to-line voltage.
  • (I_L) = line current.
  • (\cos\varphi) = power factor.

Active power depends on the magnitude of voltage, current, and the phase angle between them.

The relay measures voltage and current signals and calculates active power.

The direction of active power depends on the relationship between voltage and current phasors and the configured CT/VT polarity and phase assignments.

Important engineering point

A reverse power element can operate incorrectly if:

  • CT polarity is reversed.
  • VT polarity is incorrect.
  • Phase assignments are wrong.
  • Current and voltage phases are mismatched.
  • The relay’s power direction convention is misunderstood.

Therefore, power-direction verification is essential during commissioning.

6. Directional Power Measurement

A numerical relay calculates active power using measured voltage and current signals.

For a three-phase system, the relay may calculate total active power by combining the phase power quantities or using an appropriate three-phase measurement algorithm.

The protection engineer must confirm:

  • CT connections.
  • VT connections.
  • Phase rotation.
  • Power measurement reference.
  • Forward power direction.
  • Reverse power direction.
  • Generator operating mode.

6.1 Generator power direction

For generator protection, the normal direction is usually defined as power exported from the generator toward the grid.

The reverse direction represents power entering the generator from the grid.

However, the exact indication and sign convention must be verified in the relay documentation and measurement display.

6.2 CT and VT polarity

Correct polarity is critical for directional power functions.

A CT polarity error may reverse the measured current direction.

A VT polarity or phase assignment error may produce incorrect power calculations.

The engineer should verify the complete voltage and current measurement chain before testing the ANSI 32 element.

7. Reverse Power Protection Operating Principle

A simplified reverse power operating condition is:

[
P_{\text{reverse}}>P_{\text{pickup}}
]

for a specified time.

Where:

  • (P_{\text{reverse}}) = measured active power in the reverse direction.
  • (P_{\text{pickup}}) = configured reverse power pickup.

The relay may use a negative power threshold or a dedicated reverse-power setting, depending on its implementation.

When reverse power exceeds the pickup threshold, the element starts its timer.

If the condition persists for the configured delay, the relay operates.

The actual logic may include:

  • Minimum voltage supervision.
  • Minimum current supervision.
  • Power measurement validity.
  • Breaker status.
  • Generator operating status.
  • External blocking signals.
  • Time delay.
  • Reset behavior.

8. Reverse Power Protection Settings

Reverse power settings are commonly expressed as a percentage of generator rated active power.

A simplified relationship is:

[
P_{\text{pickup}}=k\times P_{\text{rated}}
]

Where:

  • (P_{\text{pickup}}) = reverse power pickup magnitude.
  • (k) = selected per-unit or percentage value.
  • (P_{\text{rated}}) = generator rated active power.

For example, if an illustrative generator has a rated active power of 50 MW and the selected reverse power pickup is 5%:

[
P_{\text{pickup}}=0.05\times50
]

[
P_{\text{pickup}}=2.5\text{ MW}
]

This means the reverse power element is intended to detect a reverse active-power magnitude of approximately 2.5 MW, subject to the relay’s actual setting convention.

The appropriate pickup depends on the prime mover’s motoring characteristics and the manufacturer’s recommendations.

9. Reverse Power Time Delay

The time delay prevents unwanted operation during temporary power reversals or short-duration disturbances.

Possible causes of temporary reverse power include:

  • Synchronization transients.
  • Generator loading changes.
  • Governor response.
  • Power oscillations.
  • Network disturbances.
  • Measurement fluctuations.

The time delay must be long enough to avoid unwanted trips but short enough to protect the prime mover.

The correct delay depends on:

  • Prime mover type.
  • Generator operating conditions.
  • Manufacturer recommendations.
  • Shutdown sequence.
  • Breaker operating time.
  • Control-system response.
  • Grid operating requirements.

There is no single universal reverse power delay suitable for every generator.

10. Practical Reverse Power Calculation

Consider a generator with the following ratings:

  • Rated apparent power = 62.5 MVA.
  • Rated power factor = 0.8.
  • Rated active power = 50 MW.
  • Reverse power pickup = 5% of rated active power.

First, calculate rated active power:

[
P_{\text{rated}}=S_{\text{rated}}\times PF
]

[
P_{\text{rated}}=62.5\times0.8
]

[
P_{\text{rated}}=50\text{ MW}
]

Calculate the reverse power pickup:

[
P_{\text{pickup}}=0.05\times50
]

[
P_{\text{pickup}}=2.5\text{ MW}
]

If the generator absorbs 3 MW from the network, the reverse power magnitude is:

[
3\text{ MW}>2.5\text{ MW}
]

The reverse power element should pick up, provided all supervision and enabling conditions are satisfied.

Whether it trips depends on the configured time delay and logic.

This is an illustrative calculation, not a recommended setting for an actual generator.

11. Reverse Power Protection and Generator Shutdown

Reverse power protection is commonly integrated into the generator shutdown scheme.

A typical sequence may be:

  1. The prime mover receives a trip command.
  2. Mechanical input decreases.
  3. Generator active power approaches zero.
  4. The generator begins absorbing active power.
  5. ANSI 32 detects reverse power.
  6. The configured timer expires.
  7. The generator breaker receives a trip command.
  8. The generator is disconnected from the network.

The actual sequence may differ depending on the plant design.

Some schemes initiate generator breaker tripping directly from the prime mover protection system, while reverse power protection provides independent backup or confirmation.

The protection engineer should review the complete shutdown philosophy.

12. Reverse Power Protection and Other Generator Protection Functions

Reverse power protection operates alongside other generator protection functions.

Protection functionANSI numberMain purpose
Reverse power32Detect generator motoring
Generator differential87GInternal stator phase faults
Loss of excitation40Abnormal excitation conditions
Negative sequence46Current unbalance
Thermal overload49Thermal protection
Overcurrent50/51Excessive current
Overvoltage59Excessive voltage
Underfrequency81ULow system frequency
Overfrequency81OHigh system frequency
Stator earth fault64GStator ground faults
Out-of-step78Power swing and loss of synchronism

ANSI 32 does not replace prime mover protection or generator differential protection.

It provides a specific function for detecting reverse active-power operation.

13. Reverse Power Protection and Low Forward Power

Low forward power and reverse power are related but different conditions.

A low forward power element detects when generator output falls below a threshold.

A reverse power element detects power flowing into the generator.

For example:

  • Generator output = 1 MW: low forward power may operate, depending on its setting.
  • Generator output = 0 MW: generator is approximately at the transition point.
  • Generator input = 2 MW from the grid: reverse power protection may operate.

A protection scheme may use both functions where supported and justified.

14. CT and VT Configuration for ANSI 32

Correct CT and VT configuration is essential for reverse power protection.

The relay requires accurate voltage and current phasors to determine the direction of active power.

The following should be checked:

Current transformer circuits

  • CT primary ratio.
  • CT secondary rating.
  • CT polarity.
  • Phase identification.
  • Current input assignment.
  • CT wiring continuity.

Voltage transformer circuits

  • VT primary voltage.
  • VT secondary voltage.
  • VT ratio.
  • Voltage phase assignment.
  • Polarity.
  • Phase rotation.
  • Measurement reference.

Power measurement verification

Before enabling the trip function:

  1. Verify the relay’s phase-current measurements.
  2. Verify the relay’s phase-voltage measurements.
  3. Confirm the measured power factor.
  4. Compare the relay’s active-power measurement with an independent instrument.
  5. Confirm that normal generator export is indicated in the expected direction.
  6. Confirm the reverse-power sign convention.

15. GE Multilin Relay Applications

Selected GE Multilin generator protection relays may provide reverse power protection.

Potential applications include:

  • G60 generator protection.
  • G30 generator protection.
  • 889 generator protection.
  • Other supported GE Multilin generator protection devices.

The exact ANSI 32 function availability and implementation depend on the relay model and firmware.

Before configuring the function, verify:

  • Reverse power element availability.
  • Active power measurement method.
  • Forward and reverse power conventions.
  • Pickup setting range.
  • Time-delay options.
  • Voltage and current supervision.
  • Reset behavior.
  • Output logic.
  • Event recording.

Do not assume that all GE Multilin generator relays use identical reverse power setting menus or measurement conventions.

16. General GE Multilin Configuration Workflow

The following is a generic engineering workflow. Actual setting names and menu paths depend on the relay model and EnerVista software version.

Step 1 – Identify the relay

Record:

  • Relay model.
  • Product order code.
  • Firmware version.
  • Hardware configuration.
  • CT and VT input ratings.
  • Available ANSI 32 functions.

Step 2 – Verify CT configuration

Check:

  • CT ratios.
  • CT secondary rating.
  • CT polarity.
  • Phase assignment.
  • Current scaling.

Step 3 – Verify VT configuration

Check:

  • VT primary and secondary ratings.
  • VT ratio.
  • Voltage phase assignment.
  • Polarity.
  • Phase sequence.

Step 4 – Verify active power measurement

With the generator operating normally, confirm:

  • Active power magnitude.
  • Power factor.
  • Reactive power.
  • Power direction.
  • Phase-current measurements.
  • Phase-voltage measurements.

Compare the results with the plant’s independent metering system.

Step 5 – Configure reverse power pickup

Determine the required pickup using:

  • Generator rated active power.
  • Prime mover characteristics.
  • Manufacturer recommendations.
  • Operating philosophy.
  • Relay scaling.

Step 6 – Configure time delay

Select the delay based on the prime mover’s permissible motoring time and the complete shutdown sequence.

Step 7 – Configure supervision and logic

Where supported, verify:

  • Voltage supervision.
  • Current supervision.
  • Breaker status.
  • Generator operating status.
  • Blocking signals.
  • Alarm output.
  • Trip output.

Step 8 – Verify trip matrix

Confirm that the reverse power element operates the intended trip and control outputs.

Step 9 – Save and document

Save the approved settings and record the configuration revision.

17. Reverse Power Protection Testing and Commissioning

Reverse power protection should be tested using a suitable three-phase relay test set capable of controlling voltage, current, and phase angles.

The test should verify:

  • Correct active power measurement.
  • Correct power direction.
  • Reverse power pickup.
  • Operating time.
  • Reset behavior.
  • Alarm and trip logic.

17.1 Pre-test checks

Before testing:

  • Confirm the approved settings.
  • Verify relay model and firmware.
  • Check CT and VT configuration.
  • Confirm the power direction convention.
  • Review the trip logic.
  • Ensure safe isolation of the breaker trip circuit where required.

17.2 Forward power measurement test

  1. Apply balanced three-phase voltage.
  2. Inject balanced three-phase current.
  3. Set voltage and current phase angles to represent normal generator export.
  4. Confirm the relay measures forward active power.
  5. Compare the result with the test-set calculation.

17.3 Reverse power measurement test

  1. Maintain the voltage signals.
  2. Change the current phase relationship to represent reverse active power.
  3. Confirm the relay indicates power flowing into the generator.
  4. Record the measured power.
  5. Verify the direction against the expected test condition.

The exact phase-angle arrangement depends on the test-set convention and relay measurement reference.

17.4 Reverse power pickup test

  1. Apply reverse active power below the pickup threshold.
  2. Confirm that the element remains reset.
  3. Increase reverse power gradually.
  4. Monitor the element pickup indication.
  5. Record the measured pickup.
  6. Compare the result with the approved setting.

17.5 Operating-time test

  1. Apply reverse power above pickup.
  2. Start the timing measurement.
  3. Record the relay operating time.
  4. Compare the result with the configured delay and applicable tolerance.
  5. Repeat as required.

17.6 Reset test

Reduce reverse power below the reset threshold.

Verify:

  • Element reset.
  • Timer reset behavior.
  • Alarm reset.
  • Trip output behavior.
  • Latching logic, if configured.

17.7 Trip circuit verification

Where ANSI 32 is connected to the generator trip scheme, verify:

  • Protection element operation.
  • Logic equation.
  • Output contact.
  • Interposing relay.
  • Lockout relay.
  • Generator breaker trip coil.
  • Breaker auxiliary contact feedback.

Testing must follow the approved commissioning and safety procedures.

18. Common Reverse Power Protection Problems

Problem 1 – Relay indicates reverse power during normal generation

Possible causes:

  • Incorrect CT polarity.
  • Incorrect VT polarity.
  • Incorrect phase assignment.
  • Wrong phase sequence.
  • Incorrect current-to-voltage phase relationship.
  • Incorrect power direction convention.

Recommended checks:

  • Verify CT polarity.
  • Verify VT wiring.
  • Check phase identification.
  • Compare relay measurements with independent metering.
  • Perform a controlled power-direction test.

Problem 2 – Reverse power protection does not operate

Possible causes:

  • Function disabled.
  • Pickup setting too high.
  • Incorrect CT or VT scaling.
  • Reverse power measurement not enabled.
  • Blocking signal active.
  • Output logic not assigned.

Recommended checks:

  • Review function enable status.
  • Verify reverse active-power measurement.
  • Check pickup settings.
  • Review blocking logic.
  • Verify the trip matrix.

Problem 3 – Unwanted reverse power trip

Possible causes:

  • Pickup setting too sensitive.
  • Time delay too short.
  • Incorrect power measurement.
  • Temporary power reversal.
  • Generator operating conditions not considered.

Recommended checks:

  • Review event records.
  • Examine power measurements before the trip.
  • Verify CT and VT configuration.
  • Review the prime mover shutdown sequence.
  • Confirm the approved pickup and delay.

Problem 4 – Reverse power pickup is incorrect

Possible causes:

  • Incorrect generator rated power reference.
  • Wrong per-unit scaling.
  • Incorrect CT ratio.
  • Incorrect VT ratio.
  • Different relay power reference.
  • Incorrect setting units.

Recommended checks:

  • Verify generator nameplate data.
  • Review relay power scaling.
  • Recalculate the expected pickup.
  • Confirm the manufacturer’s setting convention.

Problem 5 – Reverse power trip operates but the breaker does not open

Possible causes:

  • Output contact problem.
  • Interposing relay failure.
  • Lockout relay problem.
  • Trip coil failure.
  • DC supply failure.
  • Breaker mechanism problem.

Recommended checks:

  • Monitor the relay output.
  • Verify the DC trip supply.
  • Test the trip circuit.
  • Check breaker auxiliary contacts.
  • Inspect the breaker mechanism.

19. Reverse Power Protection Commissioning Checklist

No.Inspection or testResult
1Confirm relay model and firmware☐
2Verify ANSI 32 availability☐
3Check CT primary and secondary ratios☐
4Verify CT polarity☐
5Check VT ratio and polarity☐
6Confirm phase assignment and sequence☐
7Verify forward power measurement☐
8Verify reverse power measurement☐
9Compare power measurement with independent metering☐
10Test reverse power pickup☐
11Test operating time☐
12Verify reset behavior☐
13Check voltage and current supervision☐
14Verify blocking logic☐
15Test alarm and trip outputs☐
16Verify generator breaker trip circuit☐
17Review event records☐
18Save final settings and test report☐

20. Best Engineering Practices

For reliable reverse power protection:

  1. Understand the generator’s normal active-power direction.
  2. Verify CT and VT polarity before enabling the trip function.
  3. Confirm the relay’s power sign convention.
  4. Calculate pickup using the correct generator power reference.
  5. Coordinate the time delay with the prime mover’s motoring limits.
  6. Consider the complete generator shutdown sequence.
  7. Coordinate ANSI 32 with turbine, engine, and generator protection.
  8. Test forward and reverse power measurement.
  9. Verify the complete breaker trip circuit.
  10. Maintain approved settings and commissioning records.

Reverse power protection is a critical safeguard against generator motoring. Its reliability depends on correct power measurement, suitable settings, and coordination with the prime mover protection system.

21. Training on GE Multilin Protection Relays by Elec-Engg

Practical reverse power protection engineering requires knowledge of generator operation, directional power measurement, CT/VT circuits, power-system protection, relay logic, and commissioning.

Elec-Engg provides practical technical training by Dr Saeed Roostaee (Electrical Engineering) for engineers involved in generator protection, power-system protection, commissioning, operation, and maintenance.

Relevant training subjects include:

  • GE Multilin generator protection.
  • G60, G30, and 889 generator protection applications.
  • Reverse power protection (ANSI 32).
  • Generator motoring and prime mover protection.
  • CT and VT configuration.
  • Directional power measurement.
  • Generator trip and shutdown logic.
  • EnerVista configuration and settings management.
  • Secondary injection testing.
  • Protection coordination and troubleshooting.

Training delivery options include:

  • Pre-recorded video courses.
  • Structured self-paced training.
  • Live online training.
  • Face-to-face technical training.
  • Customized in-house training for companies and utilities.

Explore available courses at Elec-Engg or contact us to discuss a customized technical training program.

22. Frequently Asked Questions

What is ANSI 32 reverse power protection?

ANSI 32 is directional power protection. In generator applications, reverse power protection detects when active power flows from the network into the generator.

What is generator motoring?

Generator motoring occurs when a generator connected to an energized network absorbs active power and operates as a synchronous motor, driving its prime mover.

Why is reverse power protection required for steam turbines?

If steam supply is lost while the generator remains connected to the grid, the generator may drive the turbine. Depending on turbine design and operating conditions, this can cause damaging mechanical and thermal effects.

How is reverse power pickup calculated?

It is commonly expressed as a percentage of generator rated active power. The actual setting must follow the prime mover manufacturer’s recommendations and the approved protection study.

Does reverse power protection measure reactive power?

The ANSI 32 reverse power function normally detects active power direction. Reactive power measurement may be available separately and should not be confused with reverse active power.

Can reverse power protection operate during synchronization?

Temporary power reversals can occur during synchronization and loading transitions. Suitable supervision and time delay help prevent unwanted operation.

Does every GE Multilin relay support ANSI 32?

No. Function availability and setting characteristics depend on the specific relay model, hardware, and firmware.

How is reverse power protection tested?

A three-phase relay test set applies controlled voltage and current phasors to verify forward and reverse power measurement, pickup, timing, reset, and trip logic.

Conclusion

Reverse power protection is an essential part of generator protection. It detects when a generator begins absorbing active power from the network and operating as a motor.

This condition may occur following loss of mechanical input or failure of the prime mover. Depending on the machine design, prolonged motoring can cause mechanical and thermal damage.

ANSI 32 protection therefore monitors active power direction and initiates an alarm or trip when reverse power exceeds the configured threshold for the specified time.

Reliable implementation requires correct CT and VT polarity, accurate power measurement, appropriate pickup and delay settings, and coordination with the prime mover shutdown scheme.

For GE Multilin applications, always verify the exact ANSI 32 capabilities and setting requirements of the selected relay model and firmware.