| Error Code | Action to be Taken | |
| 0X83810002 | Check Software is loaded correctly into the relay. Upgrade the Firmware. | |
| 0X83818001 | Replaced Analog Opto Card, Ethernet Card, Relay Upgraded,& found Healthy & OK | |
| 0x0c0e0000 | The relay card is defective. Replace the Relay card. | |
| 0x0c250018 | Either the Processor Card or Analog Input Card is defective. Replace the Processor card or Analog Input Card. If the problem persists replace both cards. | |
| 0x0c0ddb1c | The Analog Input card is defective. Replace the Analog Input card. | |
| 0x0c170017 | The processor Card is defective. Replace the Processor card. | |
| 0x0c0ddb15 | The Analog Input card is defective. Replace the Analog Input card. | |
| 0x8c810000 | The Analog Input card is defective. Replace the Analog Input card. | |
| 0x0c170018 | The processor Card is defective. Replace the Processor card. | |
| 0x83810007 | The processor Card is defective. Replace the Processor card. | |
| 0x81170000 | The co-Processor Card is defective. Replace the Co-Processor card. | |
| 0x0c160011 | The processor Card is defective. Replace the Processor card. | |
| 0x0cc020041 | Model Number mismatch. Check the Model Number & reload the Model Number and Serial Number once again to the relay. | |
| 0x838b0808 | Opto card No.3 is defective. Replace Opto card No.3 | |
| OX838b2008 | Opto card No.2 is defective. Replace Opto card No.2 | |
| OX83818001 | Replaced CT/VT Module& Opto card 2 & 3 Relay Tested, Measured & found Healthy & OK. | |
| 0x838188001 | Replaced CT/VT Module, Relay Tested, Measured & found Healthy & OK. | |
| 0x02070be0 | The processor Card is defective. Replace the Processor card. | |
| 0x0202000e | Replaced CPU card, Analog input card, Opto card, hood, and backplate | |
| 0x0c0ddb1c | Replaced CPU card. Relay tested in Automatic Test bench. Found OK. Relay energized for 48 hours. Since the CPU card is defectively unable to extract & download the customer’s settings & PSL. | |
| 0x812A0003 | The Analog Input card is defective. Replace the Analog Input card. | |
| 0x0c220028 | The processor Card is defective. Replace the Processor card. | |
| 0x0c0ddb1c | The Analog Input card is defective. Replace the Analog Input card. | |
| 0x0c1600b3 | Relay card No.3 is defective. Replace Relay card No.3 | |
| 0x351afe03 | Ethernet Card is defective. Replace Ethernet Card. | |
| 0x0c1600b1 | Relay card No.1 is defective. Replace Relay card No.1 | |
| 0x0c1600b2 | Relay card No.2 is defective. Replace Relay card No.2 | |
| 0x0c0ed920 | Either the Processor Card or Analog Input Card is defective. Replace the Processor card or Analog Input Card. If the problem persists replace both cards. | |
| 0x08118000b | Opto Card is defective. Replace Opto card. | |
| 0x020b0b4a | The processor Card is defective. Replace the Processor card. | |
| 0X0C140002 | The processor Card is defective. Replace the Processor card. | |
| 0x8c01000. | The power Supply Card is defective. Replace the Power Supply card. | |
| 0x0c020020 | The processor Card is defective. Replace the Processor card. | |
| 0x81180002 | The processor Card is defective. Replace the Processor card. | |
| 0x07020020 | Communication card is defective. Replace Communication card. | |
| 0x0c020028 | Either Processor Card or Analog Input Card is defective. Replace Processor card or Analog Input Card. If the problem persists replace both cards. | |
| 0X811E0000 | Either Processor Card or Co-processor Card is defective. Replace Processor card or Co-processor Card. If the problem persists replace both cards. | |
| 0x82021C98 | Co-Processor Card is defective. Replace Co-Processor card. | |
| 0x8c8100000 | Anolg Input card is defective. Replace Anolg Input card. | |
| 0X8118002 | Anolg Input card is defective. Replace Anolg Input card. | |
| 0x0c0ddb15 | Opto Card is defective. Replace Opto card. | |
| 0x8c18000 | Replaced Transformer , relay tested and calibrated and found in order. | |
| 0x0c1600d00 | Either Processor Card or Analog Input Card is defective. Replace Processor card or Analog Input Card. If the problem persists replace both cards. | |
| 0x1c1200f6 | Processor Card is defective. Replace Processor card. | |
| 0x83818000 | Replaced CT/VT module from the P743 relay Excess stock to the defective relay. Relay tested from CP dept. Found OK. | |
| Error code 0x0C220028 | indicates that the IED configuration – based on the MCL file downloaded to the relay – cannot be initialised in flash memory. This can occur if the MCL file being downloaded to the relay is too large (>32kB) or the MCL file is corrupted during download. | |
What does the error code 0x0C170017 on a MiCOM P14x

What is the meaning of error code 0x0c170018

What does this Micom hex error code mean?
Error Code During Operation – GE MiCOM P40 Agile



Please can you explain to me this error code:
– Set Value command: C32CS Error
– Operation terminated: C32CS Error
Bonjour.
Ma protection Micom P242 affiche le code d’erreur 0x44010013 et interdit la marche de mon groupe (Pompe électropompe moteur de 6000V Puissance de 630KW.
Comment résoudre le problème?
Merci.
Dans l’attente d’une suite favorable.
Cordialement.