Relay protection against high current was the earliest relay protection mechanism to develop. From this basic method, the graded overcurrent relay protection system, a discriminative short circuit protection, has been formulated. This should not be mixed with ‘overload’ relay protection, which typically utilizes relays that function in a time related in some degree to the thermal capacity of the equipment to be protected. On the contrary, overcurrent relay protection is completely directed to the clearance of short circuits, even though with the settings typically assumed some measure of overload relay protection may be obtained.

Types of Overcurrent Relay

  • Instantaneous Overcurrent Relay
  • Define Time Overcurrent Relay
  • Inverse Time Overcurrent Relay (IDMT Relay)
  • Directional overcurrent Relay
  • Mixed IDMT and high set instantaneous

Instantaneously overcurrent relay operates when current exceeds its Pick-up value. The operation of this relay is based on current magnitude and it is without any time delay.


Instantaneous Overcurrent Relay

Leave a comment on this post, we will send you the Overcurrent Fundamental. pdf

STANDARD IDMT OVERCURRENT PROTECTION RELAYS

The current/time tripping characteristics of IDMT protection relays may need to be changed according to the functioning time needed and the characteristics of other relay protection elements used in the electrical network. For these needs, IEC 60255 determined a number of standard characteristics. These are:

  • Standard Inverse characteristic (SI)
  • Very Inverse characteristic (VI)
  • Extremely Inverse characteristic (EI)
  • Definite Time characteristic (DT)
inverse time relay coordination
Time Delay between Relay

MIXED IDMT AND HIGH SET INSTANTANEOUS OVERCURRENT PROTECTION RELAYS

A high-set instantaneous device can be utilized where the source impedance is small in comparison with the protected circuit impedance. This allows a decrease in the operating time at high short circuit levels possible. It also enhances the overall electrical system grading by allowing the ‘discriminating protection curves’ behind the high set instantaneous device to be reduced. One of the benefits of the high set instantaneous devices is to decrease the tripping time of the circuit protection. If the source impedance stays constant, it is then feasible to accomplish high-speed relay protection over a large part of the protected circuit. The quick short circuit clearance time helps to decrease damage at the short circuit location. Grading with the protection relay directly behind the protection relay, which has the instantaneous devices enabled, is accomplished at the current setting of the instantaneous devices and not at the maximum short circuit level.

Leave a comment on this post, we will send you the “Overcurrent Protection Fundamentals. pdf ” for FREE

DIRECTIONAL OVERCURRENT RELAY

When short circuit current can go in both directions through the protection relay location, it may be required to make the response of the protection relay directional by the initiation of a directional control device. The device is provided by the use of extra voltage inputs to the protection relay. There are many ways for an appropriate connection of voltage and current signals. The different connections depend on the phase angle, at unity system power factor, by which the current and voltage used to the protection relay are displaced

directional overcurrent protection basic principal
directional overcurrent protection

ABB Overcurrent Relay
AREVA Overcurrent Relay

Leave a comment on this post, we will send you the “Overcurrent Protection Fundamentals. pdf ” for FREE