Skip to main content

To join our protection relay WhatsApp group, please send “interest” on WhatsApp: https://elec-engg.com/whatsapp-group-for-protection-engineers/

sample discussions


– While I connect sip 5 bcu like that error I got. how can I solve that
– Differential initial setting is 0.2*In?
– What is the meaning of it?

– Anybody has breaker dcrm result & procedure for testing breaker dcrm with megger TM1740 kit.
– I think the problem is your RAM.
– maybe you can upgrade it to 8GB or 16GB.


– What is this problem?
– Install the device driver for 7sj80.
– My breaker got tripped on differential Relay is not showing any current
-87BD In phases R, Y, B But no current.
– W1 or W2 -It’s tap changing problem.
– It is due to an imbalance of voltage.
– Tap was not changed. In relay 5th harmonic and 2nd harmonic is blocked.
– Not showing any winding.
– I just updated the firmware of my 7SA82 relay from 7.82 to 8.06, now the relay shows firmware 8.06 but CFG 7.82, when I go to the device information page of offline extracted settings, here upgrade option is missing at configuration version, please guide me how can I get upgrade option.


here you can see, upgrade option is not there near CFG


this is what the manual shows, but in my case, this upgrade option is not there as you can see in the above picture.
– Did u import the communication firmware for this device?
– issue resolved, by following this “You can go to – Upgrade project device” in the project tree, and you will find for upgrade CFG-

To join our protection relay WhatsApp group, please send interest on WhatsApp, Click


– Got this error when installing digsi 4.94, plz help.
– When I am taking megger for pt primary to secondary, then when taking b/w primary and 1a and primary getting 400 Mega ohms, and primary to 1n getting 1.9 Giga. Oh, why is the difference?
– What is the applied test voltage? – 5kV.
– Remove secondary connections either connected 1a or 1n. Apply test voltage case1: primary to 1a
Case 2: primary to 1n. The values more or less should come the same. Sometimes it will show some difference due to testing machine (Megger) measurement and also ambient temperature(T)
– IN the 7SR relay where to find the Characteristic angle?
– Using reydisp evolution.
– take PRI. to earth at 5kv and seco. to earth at 500 v.
Has anybody tested the GIPAM 10NZ relay? Where is the direction selection for 67G SGR Protection In software?
– Check-in current protection folder – +-45 by default.

– any ziv zlv distance protection engineer urgent need, Unbalance settings are given 30%
– How to test and justify this 30%
– How to Test 100% Stator Earth fault protection?
– With 3rd Harmonic. It is the power setting. When u give the fault with power above 30%. Then only the relay will be active.
– Which relay Model?
– 7UM622
– Control cable length is 700mtr, then how to calculate voltage drop.

– if 220 kv or any kv panel which receiving end panel thus their relationship angle between v-i is 180 degrees apart.? is this right?

For joining our discussion groups: https://elec-engg.com/whatsapp-group-for-protection-engineers/


– Vph to Vph selected. The setting is 121 V.
– Then for secondary injection how to inject?
– How to test under excitation protection in Siemens relay 7UM?
– U have to first take the capability curve of the generator and then on under excitation side make 3 part one at 0deg angle, 90deg angle, and 120 deg angle
– For each angle, u will get a certain MW and Mvar which u can inject through ur secondary injection kit in terms of voltage and current?


PSCAD training information: Click

– Can anyone provide the DNP3 protocol standard?
– On the upper side of Relay Ready LED is Blinking. That’s why it’s not communicating by software, How to fix it
– which led?
– Ready LED
– relay faulty indiction is going on annunciation.
– No annunciation is coming on other. but I think the relay gets faulty.

– Is the relay restarting again and again? Because it blinks when in test mode
– Is it in test mode?
– Is it rebooting?
– u can also check the error code in the relay
– Not rebooting.
– HMI working properly
– When you read the data from relay through software what error it is showing?
– oh ABB show on the display
– this is an error inside
– Not communicating with software
– must repair
– What is the fault code relay is showing?
– Not showing any fault Or warning code, the Only ready LED is Blinking


– Now communicated with relay, But the Blinking problem is not fixed
– Go to main menu/monitoring/IED status/self-supervision, Check for the faulty hardware module. If it is a diagnostic failure then also it flashes
– Check IRF alarm contact status to find the reason, It is an internal fault maybe.
– Why is current in the R phase so much high on normal voltage
– Load on the R phase might be more as compared to other phases.
– Normal voltage is injected, And the normal current is injected.
– whats the ct ratio?
– 400/1
– check backup relay measurement.
– how many the core in ct?
– But I am injecting to relay directly.
– How secondary set Check ct wiring?
– Star point of relay Input Is correctly wired.
– Star point is only for protection.
– R u injected or the line is the charge?
– Relay is separated from PT CT, I am injecting current from omicron.
– PT as well
– R u injecting balance current?
– 1 A
– Yes
– check ct ratio in the relay.
– CT ratio is OK in the relay when u inject is there any current in IN?
– Yes same as the R phase.
– Check-in this, it was fluctuating
– inject only r phase backside of the relay terminal not on tb
– It’s 934 A is showing when I inject only in R phase
– led is blinking for this relay (REL670).


– Is circuit breaker contact resistance temperature-dependent
-Yes the hotter it has the higher the value. That’s why you would have seen that the current is injected for a very short duration. As not to elevate the temperature
– Does variations in input voltage affect breaker timing?
– Input supply varies from 110V to 170V. The ideal voltage is 110 V

Join by texting on WhatsApp: https://elec-engg.com/whatsapp-group-for-protection-engineers/


– 132 kV breaker close time =77 ms
– At160V
– PT ki 110 v vary kr rhi h
– No pt
– Direct supply from AC source for testing
– ac supply for the kit, No for breaker control supply
– Usually, the higher volts may not affect the timing but will damage the insulation of the coil
– Is this value is acceptable
– ac supply use in break only for motor. Refer to the manual.
– Input ac supply for the kit is 260V For MV, I have less than 60ms for one while 40 ms for the other type. The source is giving 260 V
– So you have to compare with the values in manual
-Trip time is 46 ms, CO=39ms
– please check these angle diff. is correct or wrong?

– Can you tell me what is the name of this marked portion? And why it is connected there?
– It’s correct, inductive.
– When I charge the 132kv line, then I get the all secondary 3phase voltage at the panel TB from line CVT. But I trip the breaker, now the line remains back charge bcz of opposite end connected. In this case, I get only R, B phase voltage from the same line CVT. Y ph voltage is near to zero(i.e, y=7 v) How it is possible?
– line pt install
– May you phase jumper opened in transmission line?
– please check from the remote end voltage.
– It is also perfectly correct. remote end all three voltage is perfect?
– tell me all three voltage.
24abb , 18:32 -abb pcm600: R=63.8.
Y=63.03
B=63.35
– Now it is charged at both ends. When I cut our end breaker, then I get only 2 ph voltage
– r u seeing in the panel?

– No seeing at pt MB
– cut the break from remote end charge from our end then check
– same problem
– I get all 3 ph voltage
– It is clear
– CVT after breaker or before when charging from both ends then what about the load
– all three loads are balance
– Does the problem solved now? Check the wiring of pt at tb
– Is it loose
– It is perfectly connected
– What about pt secondary phase to phase voltage?
– 110 if it is charged at both ends
– What about all other phases?
– All three-phase to phase voltage is 110 if the line is charged at both ends.
– If I cut my end breaker then I get 2 phase voltage only
– I am not getting Yph voltage

– Does the LA inline side shows leakage current?
– If our side is charged and the other side breaker is off in this case I get all three-phase voltage
– Yes check for leakage current in LA.


– Does DNP communicate over RS 485?
– Yes, if supported by the relay manufacturer.

– Correct, RS485 RS232 RS422etc is just a standard for serial communication
– DNP is a protocol that can be communicated over RS232 or RS485 serial port. DNP can be daisy-chained, just use a terminating resistor
– The motor got tripped on 51n but all three-phase currents are equal, the protection on the calculated value of three-phase currents internally by the relay. the relay was 7sj66. What are the causes?
– IR value of the motor is good

– Anyone can explain the difference between DNP and Rs 485
– RS 485 is port, DNP is protocol, DNP is a protocol
– Used in the process automation system
– Anyone can explain how to collect ABT meter load survey data through RS 485 port?
– Ok thanks, so the DNP3 outstation address will act like node ID?

– How many relays can we drop on an RS485 using DNP3?
– I mean DNP3 slave address ranges up to 65535
– The maximum IEDs that were successfully daisy-chained was 255, however, I won’t use anything close to that.
– Read through the RS485 standard, all is specified, this is not my area is expertise, but I’ve seen them work over 200m, use a 9600bd 2 wire comms, With 2 pair, 0.5 twisted shielded pair, proper earthing of spare wires and shield, I used till1400 meter closed loop
– anyone uses kocos Artes 440 three-phase secondary innection set.

click for details of the Professional video training pack (DIGSI 4, DIGSI 5 & IEC 61850)

– Please share a detailed explanation of under excitation Protection
– Please tell me about the LBB scheme in 220kV
– Local Breaker protection scheme depends on the type of busbar scheme you applied for.
– What is the type of bus bar scheme used in your 220kV station
– It is a trip matrix for designing protection schemes
– For which type of unit? Is it for generator
– Class A is for Turbine trip class B is for the GCB trip
– Whenever Turbine tripping occurs, GCB trips consequently.
– No correlation with a generator in this case. It is for a transformer. The above transformer is a GT.
-Though it is a GT, protection group A and Group B is for transformer breaker itself. Hv side and LV side (GCB), 86.1 & 86.2
– GT doesn’t have HV side CB. 86 means Master tripping. I’m saying for transformer
– Here in the trip matrix, Group A & B are categorized for master trips only.
– You mean, GT doesn’t have hv side CB
– Sorry LV side doesn’t have CB I meant to say. if it is 11/33kV GT. CB will be at the 33kV side in small power plants.
– It is a transformer
– I want a wrt generator For the 7UM relay.
– Low impedance busbar having main and check zone For busbar trip. how this is working?
– I understood the scheme is a double busbar with a transfer bus scheme.
– The main and check zone concept is different from LBB. We use a zone system in busbar differential. Whereas, LBB operates when the corresponding breaker fails to trip under feeder fault/bay fault condition. LBB will extend to the trip concerned busbar of that breaker(two main and transfer scheme) and other ends of the line (i.e., opposite end station).
– You will be more clear with protection schemes, showing LBB operated page.

PROTECTION RELAY SYSTEM DIGSI 4 & 5
Elec-engg.com

– does float dc ammeter show which current In the battery charger?
– From DIGSI 5 can we communicate Siprotec 4 relay?
– No, But you can install them on single pc

– anyone has drawn for this 11 kv panel siemens?
– I am having two MFM in different panels both having the same voltage and current but KWH is different. Is this possible?
– Check CTR in both
-Checked it is correct, Current may be the same now but it might be different in different timings, so results in different KWh ratings.
– Load in two feeders could not need to be the same all the time. Eventually, results in different kwh ratings.
– One is incomer and one is outgoer. Only- one feeder connected in that bus?
– No. Then how both current ratings were same
– it is a plant of 30mw where incomer is trf and connected to og line
– That incomer is getting input from 6 5MW sources
– How much is the difference in values in both meters183 and 258
– Is meter calibration done?
-Check PT also
R-Y 115, Y-B 121 B-R 120
– Angles in 7SR relay.
– TCS Protection is not there in the 7SR17 Relay
-How to make logic for TCS in 7SR17 Relay?
– this will work only in the case of DC coil in VCB
– OK, but how to make an equation for that?
– My existing relay is Rho 3
– In the 7SR relay how to make the equation Like logic? How to make TCS Logic in-display evolution software. How many trip coils are in your breaker?
– Two
– Use two equations
– Assign binary input to 74TCS-1 to 4 in the input matrix. Then assign the same in output matrix by virtual input
– Use E1=V1V2, E2=V3V4
– 74TCS is not available in relay
– Which relay?
– 7SR17
– Is it possible to Use TCS if we don’t have 74TCS?

Our WhatsApp team to join discussion group: https://elec-engg.com/whatsapp-group-for-protection-engineers/


– SEL 311B Manual Operating Password please Share
– Should be TAIL or OTTER
– Level 1:OTTER. Level 2: TAIL
– In CT, Due to leakage the oil reaches a minimum level. In that case how to refill the oil?
Whether we refill directly from the top of the CT oresle vacuum pulling thereby bottom filling?

– What can someone recommend as a voltage regulator for a 33kv line that experiences voltage fluctuations once there is any loss of any other 33kv feeder all feeding from the same 132kv bus. Meanwhile, the one that experiences the voltage dips is not on the 33kv bus.
– can we communicate the Schneider relay p442 in Micom S1 studio software?
– Can anyone tell me that when I am injecting 63.5in phase to neutral why I am getting voltages in ph to ph
– You are injecting in one phase or two-phase?
– Only phase to neutral. Rph only
– In the Y phase also 31V shows Not injecting. If injecting in the R phase, it should not show in the Y and b phase, but it will show in VRY AND VBR.
– Is there a neutral problem?
– Try to ground the other two phases and check
– Check with three-phase injection also

Hello, thank you for visiting our site
By joining our WhatsApp and Telegram groups, talk to the electrical engineers around the
world and solve your problems about electricity. You can also see our training packages at the link below.
https://elec-engg.com/category/training-course/


– during installation of Schneider electric studio and the net frame is not supported on this window
– how can I download the data model package for Schneider
– You have Schneider software?
– You can download it through the data model manager
– server did not respond
– If you need any particular data model, I will check and send it to you.
– P442 distance protection relay all software version
– I will check in my system, if available I will send, email id?
– Plz check data model if have then plz
– I am connecting two power supplies in a series of 48 V but the current of one is 10A and 2 A what will be the resultant
– Current
– Download data models
– Current will be added in series
– Check your email. I sent P442 data models
– yes I received thank you so much. server not respond
– Use Ge Micom S1 Agile
– How to make a Close circuit supervision configuration in 7SR Relay
– earth resistance value without grid must be less than 5 ohms, Is it correct?
– It depends upon the soil, for some soil should be less than 1 ohm
– What’s the meaning of 4 temperature inputs?
– Maybe for RTD connections
– Yeah. For bearings, stator, and rotor.
– What is the application of RTD, Monitoring the temperature.
-Resistance temperature detector. The resistance changes concerning the temperature.
– Do we need any configuration in the 7SR relay for RTD?
-I haven’t worked on 7sr but RTDs need configuration

– How to test low impedance ref?
– Anybody has a testing format for REM 615 Like overcurrent, earth fault, thermal overload, phase reversal, negative sequence overcurrent protection for the motor, motor load jam protection, and motor start-up supervision?
– The testing procedure of 7SA522 if anyone has please share it? Which relay to set directional
– Does anyone have a SIPROTEC 5 .sim file to share?
– Single-phase pick up and three-phase pickup will be different for overcurrent Protection in relay Or not?
– In relay 7SJ64
– Idmt time at normal setting and 2 times current injection are coming same is this possible
– At a normal setting, the relay will pick up only.
– Check the output trip logic

– Can anyone clarify me LBB scheme 220kV
– Can earthing of CT 2ndry neutral on both sides (at panel side and field side) can cause this differential current?
– Does anyone has experienced this case?

– That a transformer differential relay tripped even when the breaker is opened? Some differential current flowing when the breaker is opened
– In this case, the current doesn’t flow in the relay coil. it will circulate if both field side and panel side star point earthed
– Check DR
– if transformer trip on diff. relay on through fault what’s the reason?
– Check differential settings and harmonic blocking during energization.
– can we disable the external fault trip in Micom p642 diff?

– after running the generator for 3hrs the turbine guide bearing temperature would rise from 50-62, and if the machine is not shut down it will continue to alarm and trip point.
– Our plant has 6 generators of 96.4mw each, suddenly one of them developed high-temperature issue from the turbine guide bearing. It is a hydropower plant
– Increase the bearing temperature limit up to 85-degree Setpoint
– Won’t that cause bearing burnout as all other generators don’t get up 58 degrees?
– What about the oil temperature in that system?
– If the oil temp is high, too the bearing temp will be high. So you need to inspect cooling systems for turbine oil. The oil temperature also do rise but as usual, it should be lagging and that is what we are getting
– If you are using water in a cooling system, just inspect the water entry. Especially valves which allow cooling water to circulate.
– It’s self-cooling, when the shaft rotates it stir up oil in between the gap between it and the bearing providing lubrication and cooling at the same time
– forbearing to be at low temperature, the oil in its gap must be at a low temperature too. But the oil is cooled by either air or cold water system. So I am advising you to inspect the cold water system or air system. Because this shows that the system that cools oil is not working properly.
– Ok sir, our system is an enclosed type, no water cooling system, and we checked all the breeder points but no issues.
– Ok continue to troubleshoot bro.

– Hello, how to check if fiber optic between two relays is a healthy connection?
– Siprotec 5
– Anybody service provider near Bagalkot Karnataka. Like: TL, T/f, ht Panel relay breaker, cables
– How to make it possible for these two devices to communicate, they are connected using optic duplex LC
– anyone has the 7SJ85 test procedure, please?
– do you mean communicate as a protection interface for line diff 87L?
-Check device id

Our WhatsApp team to join discussion group, Click


– Can anyone tell me how to test low impedance ref Secondary injections or stability?
– Secondary injection
– I am facing a problem with distance signals Configure in the extended system interface
– You will get the signals which you require

– Need to apply 1500V DC voltage for testing. Have anyone come through the 1500V DC voltage injector kit?
– In the 220kV scheme with two main and one transfer bus does the logic inputs of TBC and Bus coupler are fed to that bay relay or not Or using Goose it is done can anyone tell me
– If I am understanding correctly, I would say yes you would get those signals wired to your bay relay as inputs then if needed send it via GOOSE to any other relay that needs it for its logic. Only during maintenance, you shift to transfer bus through 89T…so bus bar protection should not Operate for transfer bus For bay units, only bus isolators status (89A&89B) should be given. It should operate for Bus-A and Bus-B fault.

– For directional earth fault relay uses positive sector negative or zero?
– Generally, we negative and zero sequences not positive sequence

– Relay is showing negative power instead of positive, In this case, the current is lagging voltage, How, it is leading As PF is negative

– In capacitive load current leads voltage, In inductive load, current lags voltage, Current Our is an inductive load
– I guess real power is flowing in the reverse direction. You have to reverse the CT staring, change the PQ direction in Siemens bcu

– if you have calculations for differential relay for transformer 132/33, 132/33/11 Kv, can provide us with my regard

– There is interference between drawing possible to amended and reupload, I’ll try to convert it from my pc Relay is not time synced
– What is the SPS scheme used in the Power station?
– in Micom p442 relay how R1, R2, R3, R4 PP, and PG CALCULATE How-to measure the resistivity of water?
– Trafo is getting tripped at night in transfo differential Even though there is no current at night why it is tripping on differential

– I am testing an MFM em6400, I want to change the power factor From lag to lead
– Using a single phase is it possible Only positive and negative is changing in inductive
– anybody tells me how set the R1, R2, R3, and R4 P-P and P-G in Micom p442 it’s very urgent
– Which relay?

Can you send fault data? And DR Abb vd4 (vcb medium voltage) technical manual Required Trip, close coil, etc details

join our Protection Relay Discussion Group in Telegram: https://t.me/joinchat/Cmyg2FiXX-qlTYqyXQ_pjg


– what is phase over-current, and over current in relays, Can anyone tell me what is Sf in the earthing calculation
– As I referred, it is the diversion factor for which fault is being distributed across the ground network through transmission line ground wires.
– Ratio of Ig/ 3Io. MTA is -15deg, RCA is +- 90, Then angle will be 60-0-240 For earth fault 75 0 255 have anyone use kocos artes kit for test distance protection relay
– How much is the knee point voltage of nct
– Vkp = K * If/CTR * (RCT + RL + RR)
– Vkp is the knee point voltage. K constant taken as 2 If – max. Fault current
– CTR is the CT ratio. Rct CT winding resistance
– RL loop lead resistance in ohms. RR relay burden Or do knee point voltage test
– What mean by 40Rct+400v in ct details?
– <= 40-ohm winding resistance 400v knee point voltage < 30mA at 100 volt while knee point test 21/10/2020, 19:35 –
Greetings house, up till now our problem of guide bearing temperature rise has not been resolved. This sketch is my observation when the generator is operating but I’m not a mechanical engineer.


– Other generators don’t behave this way How to test under Impedance? The setting is 0.02 P. U, Relay is REM545
– how to test Micom p442 distance protection relay as well as setting.
– In the transfer bus how the sequence of operation will be performed
– what is the cause of tripping of incomer due to outgoing feeder trip on high set earth fault.
– How to test pole slip

-For overcurrent protection, On Which side CT low forward power protection and reverse power Protection is generally there?
– Neutral side CT or Phase side CT
– What’s the meaning of the four-step in this protection?
-Four steps mean four different stages, 4 different levels of NPS you can configure.

– Which version of DIGSI is compatible with window 8?
– One problem we are facing is that with stator earth interterm trip is also coming
Wiring checked what may be other problem

– I can’t change the common mode to RSTP Updated the firmware to P14231QB….B60L.
– How to enter in setting mode
– What do you want to do in settings To view setting only And to check measurements?
– Press down arrow, System data will come Then press right now, You will find measurements, configuration, settings
– I found these now But I am not able to enter any option
-If you found measurements, you have to press the down arrow
– Yea but nothing is happening
– You have to reset the trip and alarm, then you try
– Press the book 📖 symbol, It will show all Alarms, then press c.
– I am pressing the book key but nothing is happening
– How come out of this menu
– Press c
– Nothing is happening by pressing the c key also

– Once u can restart and do the same
– You have to switch off the relay, wait for some time then switch on.


– How compensation factor is used in the distance relay?
– When I change the star point then does protection operate or not?
– In the case of non-directional overcurrent, Relay is showing power in negative So I want to change the polarity.
– In directional it will not
– Depending on each direction (reverser or forward ) Starpoint to consider, I have set as forward
– P1 is the bus side and P2 is the line side, With S1 as star point

– When I am shorting the TB for changing the meter the current is still not zero. It is showing as 5A
– Actual load current is 64A, After shorting it is showing as 5A, not 0
– Please Share 7UM6211 Test Report
– Is this a balanced phase or are Y and B interchanged
– Yes the rotation is clockwise, According to me it is an ACB phase sequence. So Y and B needs to be interchanged


– I Am asking if anyone in here knows how to run two generators in parallel and kindly assist with the schematic diagram
-I have two generators

Be a part of our WhatsApp group member: https://elec-engg.com/whatsapp-group-for-protection-engineers/

Our completed Courses:

To join our protection relay WhatsApp group, please click

Join 20 WhatsApp groups for protection engineers

20 WhatsApp Groups for protection engineers

  • WhatsApp Grp 01: Protection Relay – General
  • WhatsApp Grp 02: Substation Automation – General
  • WhatsApp Grp 03: Transmission line protection
  • WhatsApp Grp 04: Transformer protection
  • WhatsApp Grp 05: Motor protection
  • WhatsApp Grp 06: Generator protection
  • WhatsApp Grp 07: Overcurrent and Earth Fault Protection
  • WhatsApp Grp 08: Busbar protection and Bay controller
  • WhatsApp Grp 09: Breaker protection and control
  • WhatsApp Grp 10: Protection Relay Testing and commissioning
  • WhatsApp Grp 11: DIgSILENT
  • WhatsApp Grp 12: ETAP
  • WhatsApp Grp 13: PSCAD
  • WhatsApp Grp 14: IEC 61850 configuration
  • WhatsApp Grp 15: Switchgear GIS & AIS
  • WhatsApp Grp 16: GE Relay Configuration
  • WhatsApp Grp 17: SIEMENS Relay configuration
  • WhatsApp Grp 18: Schnider Relay configuration
  • WhatsApp Grp 19: SEL Relay Configuration
  • WhatsApp Grp 20: ABB Relion configuration or more services,
  • send a message to our WhatsApp support team, click

Sample discussion:

– I want to know what is the main Reasons for Transformer Bushing Failures.
– Can u share the image?
– Sir Actually Site Pic Regarding any Problem does not allow to Share as per Site Policy.
So I can’t share it.
– Good afternoon, would anyone know what the default password for ZIV protection relays?
– Try with Ziv or zivercom.
– Username; zivercom Password; Ziv
– It worked.
– Anyone has substation CAD or Revit.

– I am facing Digsi 4.91 installation problem in windows8.1
– It shows that Digsi 4.91 can’t install in Windows 8.1
-Please check the system requirements for software installation.
– Check, in the manual.


If anyone is interested in ETAP discussion Whatsapp group, send ETAP to me on Whatsapp (Click)



– Which power analyzer is best for Harmonic measurement? I need to measure Harmonics order’s magnitudes and phase angle.
– Fluke 1735
– Fluke 434

Which power companies are using the whole IEC61850 (Sample Value, GOOSE, and MMS) in their substations? or are they just adept GOOSE and MMS only? The CT and PT are still conventional types?

– How to check this relay?
– the setting is 20%

Inject the current above that value and check the trip time. Pick up and all.
– How to test locked rotor in Easergy p3 g32 relay?
– How do know the TMS and type of curve of this overcurrent relay? how to Calculate the time of tripping?
…3-sec normal inverse curve.
– TMS 0.2
– Would you please explain?
– How do you get it?
-100% IDMT settings. 800% instantaneous setting.
– Check there I don’t know what to call them, those toggle switch which side they are selected just sum it, And multiply by the factors mentioned and you will get the setting.
– For the left side instant setting
200 + (2+1) 200 = 800 % For TMS 0.12= 0.2

-The upper two are for different purposes.
– Different tables are mentioned over there Just check the S 1 -8 no. And then see the upper two toggle positions.
– I hope it is clear to you.

– We have two transformers (66/11.5 kV, 50/55 MVA, 600A NGR earthed on the 11.5kV side). There is two incomer-one bus coupler scheme at 11kV bus.
– Due to some constraints, we are not able to get a 66 kV supply from the grid. However, 11kV direct supply is offered by the grid for no-load charging at an 11kV bus from the identical transformer on the grid side.
– Please revert with technical constraints related to the subject.
– Hi everyone, l hope you are well, and safe; could you share ” relay coordination and setting for substation 230/400kv(excel sheet+ explanation) thanks in advanced.

– We are facing one issue in one of the plants that we have laid 3Core 400 Sq.mm 22KV XLPE cable to provide power supply to one of the small production units. The cable length is approximately 2500Mtrs and the state electricity board has implemented KVAH billing now. So the problem is even though there are zero loads at receiving end source end meter shows 40KVAH apparent power and 40KVAR reactive power. Is it because of cable capacitance? If yes what is the solution to avoid the same?

– As KVAH billing is implemented it is directly impacting cost very heavily.

– Can experts give your valuable inputs on this.
– Since it is a cable then it will be generating ” VAR”.. hence it is not possible 40 kVAH & 40 kVAR
– there is a chance of a cable charging current. Once check with the leakage meter in the secondary side of metering MFM, check how much leakage current is showing. And also ensure whether c.t wiring is connected properly or not it means the metering core of c.t is to be connected to meter only and also protection core of c.t is always connected to be relaid. I think the only possibility is to charge current.
– We have checked the wiring and it doesn’t have any issue. Also, we have removed the cable earthing at one end which was connected to both ends earlier. But still, the problem persists.
– Check cable insulation.
– Pls share the SLD with CT location.. and also cable parameters.
– Is it a cable feeder or it is connected through a transformer at your end and of course power provider end power factor to be confirmed.
– I think it is OK, the cable is 2.5km long, 40kVAR is 1 amp at 22kV. Who can explain why it is wrong?
– Hi team, I want to know which electrical software is better to learn to come into the design side?
– If anyone from the design side or if anyone knows better share the knowledge so it will be helpful to someone who doesn’t know.

Electrical engineers can find us on WhatsApp, Likundon, Instagram, site, and email.
To follow:

Telegram
t.me/elec_engg

Instagram
instagram.com/elec_engg

Website
Elec-Engg.com
ProtectionRelay.com

Email
info@elec-engg.com

To join our protection relay WhatsApp group, please send interest on Whatsapp: +989129613659

-How to simulate protection function using a virtual injection in Vamp255
– How to assign the DR in Micom Esergy Studio soft

You can also benefit from our free files and see our training packages at the link below.
https://elec-engg.com/category/training-course/

– Can anybody pls provide R, X/Z values of 132kv & 220kv lines with Panther, Zebra ACSR conductors. Rgds
– To be used for distance relay settings.
– Anyone can suggest pole slipping protection calculation for 4.9 MW TG. There is a total of 3 incomers on the 11 kv switchboard. 2 from grid trafo and 1 from TG. In the normal operating scenarios, all 3 incomers are synchronized and BC is closed. I have doubts regarding the considering impedance of the transformer.

-Even when the differential is less than restraining current Relay operated on minimum operating current.

– Maybe it tripped on cross-phase tripping like detection in one phase trips the other two.
– Because differential always has three-phase tripping.
-Is there any formulae for calculating? I didn’t find any cross-phase calculation in the relay manual
– No sir, the formula is not there, in siemens relay, the function is there. Cross tripping function which we can enable or disable.
– Which relay is this?
– P632
– I don’t think it’s there in this relay.
– But it is the case usually, protection operation in one phase, operates the three-phase protection.
-Does anyone have a catalog or technical manual of power panel/receptacle panels/ lighting panels?
– RET? And REM

– Can anyone explain the purpose of cable sheath tests
– It can make sure the cable sheath functionality like a uniform, induced voltage, and one end grounding, etc.
– I mean that are power cables. I am not sure that your meaning is a control or power cable.
– Yes for power cables
– I’m glad to inform you that I finalized my one-year apprenticeship as a relay testing engineer trainee in KSEB Pvt Ltd in India. Now I’m looking forward to entering a new opportunity in the same field. I will be grateful if you inform any suggestions or vacancies related to the same for improving my skill and career. Don’t hesitate to contact me if you have any concerns.
– Guys wanted to know regarding the excitation current of ct.. what will happen if the excitation current is more than the given nameplate data.. for ex: knee voltage >= 500 and knee current <= 25mA in nameplate for px class. But during testing, if knee voltage is more than 800V and knees current 32mA. so what will be the effect on protection in this case?

– I need to change the IP address through the screen of relay 7SJ80 but not accepted relay so how will change only by screen
MAIN MENU > Settings > Setup/Extras > IP-Config > PC port > IP-Address

– Can any Share 220 kV GIS building layout??
– Does anyone has a test report of the p111 relay.
– What is the reason for this?
– I think installation problem once reinstall the software PCM600
– Thank you will come back to you tomorrow
– Can we check coordination between generator 51V and outgoing Transformer feeder 51?
– Yes for phase faults

If anyone is interested in the IEC61850 discussion Whatsapp group, send ETAP to me on Whatsapp

Hello, thank you for visiting our site
By joining our WhatsApp and Telegram groups, talk to the world’s electrical engineers and solve your problems about electricity. You can also benefit from our free files and see our training packages at the link below.
https://elec-engg.com/category/training-course/

– Why this ramping button is inactive?
– Because of size value is zero.
– Ramp it by 0.01A or 0.001A whatever your requirement is.
– Got it to thank you
– Can someone explain the Total Owning cost of the Transformer?
– If you have Can send ABB Ekip training slides?

– Can anyone tell me how to rectify this issue installation problem?
– Need to know one info Freja 300 relay testing kit
– Is it a very good kit or Omicron kit is good lne For CT? 1st core used for main protection 2nd core used for backup protection. 3rd core use for metering purpose Then what is the purpose of the 4th core?
– There may be 6 cores too, for different purposes, like main1, main2, bus bar1, busbar2, metering, spare.
Depends upon the requirement and scheme of the system.
– Yes It’s True.

– Could you please help me with how to configure in ABB RED670 front panel push bottom configuration to activate one binary output?
– Pcm 600??
-Yes
– please share the screenshots I am waiting
– Go to HW configuration?
– 7sd610 is not communicating to pc when I tried thru the device to DIGSI plug and play
– How to clear this error?
– Do power recycling
– And check supervision relay elements after that upload Pspx file again

– Anyone has an idea how to connect SEL351A with SEL651R?
– How to block power sing in a distance relay? Simply, disable power swing in settings
– Blocking & disable are two different thing
– Which relay do you have sir
– SEL

– One HV motor has two feeders for redundancy. we want seamless changeover from one feeder to another in case of mechanical failure. Is it possible for a higher rating HV motor? How?

– What kind of problem and how do you expect mechanical problems in the feeder when it is running
– Basically, the client wants to prevent an outage of power by this. Is it possible in the HV system?
– Online
– Don’t Think mechanical failure expected
– Nice to meet you too, I am Peter
For RTU needs 4 cards: 1. digital input, 2. digital output, 3. analog input 4. analog output
– Bay control unit for SAS system
– Can we say it is like PLC, But with higher availability, redundancy, robust voltage, and disturbance handling, With different comm protocols and Network redundancy.
– Yes
– does it follow any standards like PLC has IEC61131?
– IEC 601850 – 101 & 104
– This is for communication and data sharing. What about logic programming?
– WHAT IS THE WORK OF THE FOTE PANEL?
– IEC 601850
– What should be done if VCB doesn’t pass contact resistance criteria? VCB should be used or not?
– What should be done if VCB doesn’t pass closing time criteria?
VCB should be used or not?
– Fiber optic terminal equipment. This is for line communication like PLCC
– No. must repair/service before put into the system
– Yes digital power line carrier
– What about hipot test?
– hipot is passed, CB is old.
– If both contact resistance and timing test fail then it is recommended to go for replacement even hipot passed.
– Finally, check if any mechanical problem can be rectified.
– Is this a vacuum contactor or vacuum circuit breaker?
– Also, compare all 3 phases of contact resistance and timing. And all these tests can be compared with the last test results, FAT.
-How old is this?
– What manual says about a lifetime? With this, you can decide whether it is premature failure due to quality or any inbuilt issues, or lack of maintenance
– What is the distance between ZONE 1, ZONE 2, ZONE 3?
– In distance protection or busbar protection?
– Distance protection
-What is the means of this relay?
– Carrier aided trip or communication aided trip, As per RK commission, Z1 is 80 percent of PL, Z2 is 150 percent of PL and Z3 is 120 percent of PL and Longest line.
– On which mode u have set the line DTT, DUTT, PUTT, or POTT
– It means that this relay is tripped based on the signal received from the far end relay.

– “How to configure RCBs and Data sets in ABB RED670 relays by referring to existing CID files?
– If any kind of procedure/guidelines, please share them with me

– You must be able to upload the CID file into the IEC61850 tool and it’ll help you to configure the IED
– Still, I am not clear. Can you elaborate on it?
– Use the PCM600 configuration tool from abb to upload the CID file into IED. Download and install PCM600 from the ABB website
– I have PCM600 V2.8 software
– I have an existing PCMP project file that doesn’t have datasets and RCBs. But I have commissioned the CID file back up. Now I want to create new data set and RCBs in the PCMP Project file with help of commissioned CID file. Pls, note I am doing it for V1.1 relays. So pls check and advise me
– Do we need to go for a higher CT ratio If CT secondary is not suitable for peak fault?
Please share your opinion
– Yes. Greater Knee point voltage CT to be chosen
– you can connect two secondaries of the same CT in a series. You can use a secondary reserve, both secondaries must be equals (ratio, class,….)

– This connection is similar to installing a higher knee point CT
– I have 1s1-1s2 and 2s1-2s2. How to connect both ct sec in series? Moreover these 2 secondary connections 2 different relays. In such a case how it should be connected?
– I am facing a problem that after under-voltage takes place, the breaker is tripped, and after reset and normalization of voltage, I can’t able to ON the breaker. So after turning off /on the breaker control supply then I can able to turn on the breaker.

Electrical engineers can find us on WhatsApp, Likundon, Instagram, site, and email.
To follow
And use our WhatsApp groups and easily talk to engineers around the world.
plz text on Whatsapp: https://elec-engg.com/whatsapp-group-for-protection-engineers/

Telegram:
t.me/elec_engg

Instagram
instagram.com/elec_engg

Websites:
Elec-Engg.com
ProtectionRelay.com

Email:
info@elec-engg.com

– How to make the Rio file for the ABB (rel670) relay be tested in the distance feature of the omicron 3-ph testing kit?
– Open parameters settings, go to file, export, save as Rio
– Option is export parameters in xrio format?
-Export in xrio
– Load PTL file of RED670 in omicron software, Then import this xrio file But when that was imported in ptl file, only z1 p-e is coming
– Check graphs of all enabled zones are showing or not
– Graphs are showing but when a fault is given, no response
– Relay is sensing fault or not?
– Mean operating or not?
– Not sensing fault
– Not operating
– I think the problem in ptl file, is it is different for different version relays?
– Download the latest file from the PTL library
– Will it works in the distance module or in the advanced distance?
– Advance
– But what is the way to test with the distance module as I have only one distance module in my kit
– Anybody has ptl file for P545?
– It can be downloaded from the OMICRON website
– Third-party can download?
– Yes. you have to sign up and register
– Ok let me check
– Can anyone tell me what is the issue?
– Anybody from ABB LV?
– Can you send EKIP Connect the latest software manual? Or training slides
– Can anyone help me to find out transformer vector group Dy11d0d (-15)d(+15)

– Anyone has procedure test sheets for test commissioning protection relays
– Any opening for the oil and gas sector?
– Anybody has FCMA soft starting settings

– This is DC supervision relay, often this relay gets the problem, In my out of 11, 4 were not working. Although Input DC was correct.
– Please teel why it is getting problem?
– How do we have to troubleshoot my site?
– There is some short between two terminals… is that done( I think it I some status)
– Terminals for 220 and 110v dc are different.
– I think you would have connected 220 v dc to 110vvdc terminal
– I have checked 110 VDC from dcdb panel
– Check the relay on Which terminal has connected the supply?

– How to see ethernet NTP IP address in 7sa522 relays?
– Does anybody know the basic working difference of REF in autotransformer besides from REF in conventional transformer?
– Binary input/output card.

– How the mccb is protecting against cable heating issues due to undersize?
– Can anyone tell me how many NO & NC contacts are available for this model number? Alstom UV relay.
– Got it guys after seeing the sticker on the box. Thank you

– We lost the password for this how we can reset to default value please help Masibus 2330
– In the substation present, the DC source is 110 v, and the circuit breaker set at 220 v will the breaker operate or not.
Kindly help me.
– some substations have two supply 110v & 220v
– there is only one source 110v
The C.B isn’t working.
– Till now we have not charged the bay
– It’s under construction
– DO YOU TRY TO TEST BY 220V?
– 220v source is not available
– Could you replace the coil?
– manufacturers make different types of coils. For example, 48, 110, 125 and 220V
– Reactive power calculated formula?

– PSS FULL NAME?
– Power System Stabilizer

Electrical engineers can find us on WhatsApp, Likundon, Instagram, site, and email.
To follow
And use our WhatsApp groups and easily talk to engineers around the world.
plz text on Whatsapp:
https://elec-engg.com/whatsapp-group-for-protection-engineers/
Electrical engineer Dr. Saeed Roostaee with his online training on using and working with relays will help you to work with relays in the shortest possible time and at a reasonable price.
Follow us on

Whatsapp: +989129613659

Telegram:
t.me/elec_engg

Instagram:
instagram.com/elec_engg

Websites:
www.Elec-Engg.com
www.ProtectionRelay.com

Email:
info@elec-engg.com

– Anybody have an overflux curve of 500 MVA ICT of BHEL make?
– How to find excitation voltage in a brushless synchronous motor?
– please let me know if somebody has the loss figures for 100 MVA transformer 132/33kV. How to remove this error?
-What is the purpose of these dual delta primary windings in VFD configuration?
– Harmonic mitigation if phase shifting at secondary
– Ok. But why dual delta. Harmonic mitigation is possible with a single delta also
– Anybody has a download link for SEL ACSELERATOR QuickSet SEL-5030 Software, please?
– Can download it from the SEL website it’s free
– I have applied for an account, but it has not yet been authorized

– What is the password to change the settings
– 0002
– How to calculate the line losses in an ac transmission line? And how to disable directional overcurrent and earth fault settings at this relay
– Please share the DR standardization process of SIEMENS 7SA522 along with CFC.
– Anyone has REL 650 base connectivity package?

– 1I need the ERL LPRO4500 relay setting calculation sheet, if anyone has, pls send it.
– How to calculate REF fault current for transformer
-I injected the same current in all phases but it tripped in earth fault
-Why does this happen I checked the wiring it’s fine
– You check the star point of internal CT
– Injected directly at relay backside
– Check the phase angles
– It must be 0, 240 and 120
– Apply three current with the same magnitude and zero phase angle and check N current
– For earth, fault inject individual phase with phase angle 0 degrees. The phase angle is ok
– Which relay is this..?? Line protection..??
– simple over Current and earth fault only
– Can u share a pic of the relay showing phase angles while injecting a 3phase balanced current?
– Relay CT terminal neutral loop wrong
– Got corrected it was a mistake in setting
– How to calculate CT size for motor hp please suggest me
– Sizing of CT should include 120% of FLA and peak fault saturation and sub transient for dynamic half cycle


-Anyone in the group has an idea about microgrid relaying protection?
– Do anyone knows about Schnider ltmr relay custom logic preparation?
-No you can’t connect. Because the Current will flow on a low resistance path only. If you used 0-500 tap for R1. The same core you can’t connect R2.
– You can connect two relays in serious on a single adequate tap and configure accordingly. But don’t connect two relays in parallel, as boopathi said, the current will flow on a low resistance path. If it’s a high impedance differential protection, then don’t share the CT.
– And relay may malfunction due to the current magnitude flow into 2 different relays and the direction of the current subject type of protection.
– Can’t we use the same tap for overcurrent and then in series for high impedance REF? Not on different taps but on different cores
-In the REF phase and Neutral CTs are connected in such a way that current is nullified. So it is not possible to use over current with REF.
– In a High impedance circuit, stabilizing resistor and metrosil will be part of the ct circuit, so it’s not advisable to combine both in the same ct core
– Actually, we have commissioned many projects like this. The only thing we extended inputs to overcurrent element first then conjugated with neutral ct adding metrosil and stabilization resistance and fed to REF element.
– Technically we don’t find any issue. Maybe you have any practical experience, please share for taking care. Phase ct and neutral ct should be paralleled in such a way that the current is nullified during normal conditions. Further, how the OC relay will get the correct measurement with a high impedance circuit? Please check your secondary circuits
– High impedance coil input to relay is dedicated and it is voltage-operated although we give current as an input. However, OC elements core must be different than high Z core.
-Are you using RET 670 relay?
– Technically not correct. It may work but note that REF opération depand on CT magnétisation characteristics. It can malfunction also. REF should not operate for external faults. This is RET 670 relay CT connection for REF and over current used

Electrical engineers can find us on WhatsApp, Likundon, Instagram, site, and email.
To follow
And use our WhatsApp groups and easily talk to engineers around the world.
plz text on Whatsapp:
https://elec-engg.com/whatsapp-group-for-protection-engineers/

– I support everyone’s input if the overcurrent element is not in the relay and phase CT star point is not made thru the relay and parallel with neutral ct.
– It all depends on the relay features and how you are making start point phase CTs.
Thanks for all your inputs.
– Hi do anyone have abb ret 543 relay communication software
– What should be the value of coil current taken by a trip coil of the breaker?
– 400 kV GE make Breaker
– Nonmagnetic cable gland is required in single-core DC cables?

– I am facing a problem with the abb rel670 relay. When the line is charged condition with both main and tie breakers in close position. If we open the main breaker, abb rel 670 is sending DT on another end. But we check the DT send logic, it is ok we checked it by taking a shutdown.
– What will be the problem?
– This is the normal logic for DT. DT is for Over Voltage, Manual Open, LBB, and Busbar trip.
– On manual-open main CB, DT will send only if tie CB is already open
– Ok. Tie CB status is given to this relay? But here the problem is when is in charged condition with both main & tie CB in the closed condition when we open the main CB only DT is sending
– Normally REL670 will not mal operate. I think there may be an issue with the logic.
– You check online signal monitoring and find out which outputs are energized during that time

– main incomer breaker of capacitor bank get trips by using relay when the power factor exceeds 0.86. The capacitor banks are newly installed. What May the reason for capacitor banks to draw more current
– Did u check each capacitor’s bank-wise currents?
– Check the load settings of the breaker.
– We are using Tapcon 320 expert in one of our sites, in which we are trying to communicate the Tapcon using the ethernet port. During which link/activity light is not glowing in ethernet port. Tapcon is showing error event 38. No connection to the communication interface card. Communication info is showing as blank; no version available in the Tapcon

Our completed Courses: